Plan Review Details - Permit 99100381
Plan Review Stops For Permit 99100381
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-29 Cont ID  
Sent By dpalmer Date 2000-02-29 Time 07:51 Rev Time 0.00
Received By dpalmer Date 2000-02-29 Time 07:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-19 Cont ID  
Sent By dpalmer Date 1999-10-19 Time 19:28 Rev Time 0.00
Received By dpalmer Date 1999-10-19 Time 19:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-19 Cont ID  
Sent By jleech Date 1999-10-19 Time 14:46 Rev Time 0.50
Received By jleech Date 1999-10-19 Time 14:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-16 Cont ID  
Sent By pschmitz Date 1999-10-16 Time 13:53 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-03-02 Cont ID  
Sent By jgomez Date 2000-03-02 Time 19:21 Rev Time 1.50
Received By jgomez Date 2000-03-02 Time 19:21 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-REVISE CALCULATIONS FOR TABLE 600 AT
 REAR ELEVATION.
 2-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SIDELITE ASSEMBLY.
 3-PROVIDE A COMPLETE INSTALLATION
 SCHEDULE, AS PER CITY SAMPLE SCHEDULE
 ATTACHED, AND A KEY PLAN THAT MATCHES
 ARCHITECTURAL PLANS.
 FILL IN ALL THE INFORMATION REQUIRED
 IN THE INSTALLATION SCHEDULE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-11-06 Cont ID  
Sent By jgomez Date 1999-11-06 Time 15:34 Rev Time 2.00
Received By jgomez Date 1999-11-06 Time 15:34 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE "A0". PROVIDE ELEVATION
 CERTIFICATE.
 2-BEDROOM #2 WINDOWS DON'T MEET THE MIN.
 SIZE REQUIREMENTS OF SEC 1005.4.4 OF
 SBC 1997. REVISE ORIGINAL DWG AS REQ'D
 3-SLIDING GLASS DOORS SPECIFIED ARE
 BIGGER THAN THE ONES IN PRODUCT
 APPROVAL. NEED ANOTHER PRODUCT
 APPROVAL OR SITE SPECIFIC ENGINEERING.
 -STORM PANELS: UPDATE INSTALLATION
 SCHEDULE (AS PER CITY SAMPLE) AND KEY
 PLAN. HIGHLIGHT SPECIFIC MOUNTING
 CONDITIONS AND ANCHORS TO BE USED.
 -PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SIDELITE ASSEMBLY.
 4-SOIL TEST REPORT TO BE SIGNED AND
 SEALED AND PROVIDE COPIES OF THE
 BORING TESTS.
 5-REVISE SIZE OF WINDOWS IN MASTER SUITE
 TO MEET TABLE 600 SBC 1997.
 6-SEE COMMENTS ON PLANS AND REVISE ALL
 ORIGINAL DRAWINGS AS REQUIRED.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-14 Cont ID  
Sent By gjoyce Date 1999-10-14 Time 12:41 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***