Plan Review Details - Permit 99100227
Plan Review Stops For Permit 99100227
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-13 Cont ID  
Sent By dpalmer Date 1999-10-13 Time 20:24 Rev Time 0.00
Received By dpalmer Date 1999-10-13 Time 20:24 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO*******************
  
 1)NOTE: NEED TO SUBMIT REVISED RISER
 LOAD CALCULATION. TO INCLUDE DISPLAY
 LIGHTING LOAD AS A CONTINUOUS LOAD.
 FIGURED AT 125% AS PER ART;220-3A
  
 PLEASE HAVE THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL BEFORE ROUGH
 ELECTRICAL INSPECTION.