Plan Review Stops For Permit 99100227 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
1999-10-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
1999-10-13 |
Time |
20:24 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
1999-10-13 |
Time |
20:24 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | *************PROVISO******************* | | | | 1)NOTE: NEED TO SUBMIT REVISED RISER | | LOAD CALCULATION. TO INCLUDE DISPLAY | | LIGHTING LOAD AS A CONTINUOUS LOAD. | | FIGURED AT 125% AS PER ART;220-3A | | | | PLEASE HAVE THE ABOVE SUBMITTED FOR | | REVIEW AND APPROVAL BEFORE ROUGH | | ELECTRICAL INSPECTION. |
|
|
|