Plan Review Details - Permit 99091004
Plan Review Stops For Permit 99091004
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-19 Cont ID  
Sent By dpalmer Date 1999-10-19 Time 19:05 Rev Time 0.00
Received By dpalmer Date 1999-10-19 Time 19:05 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO****************
  
 1)NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS AND BRANCH BREAKERS.
 AIC RATING IS FIGURED FROM FAULT
 CURRENT CALCULATIONS.AS PER ARTS:110-9/
 215-5.
 2)NOTE:RISER DIAGRAM SHOWS EQUIPMENT
 GROUND BEING INSTALLED FROM METER TO
 MAIN DISCONNECT. EQUIPMENT GROUND IS
 ONLY TO BE INSTALLED AFTER FIRST MEANS
 OF DISC.
 3)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE:AS PER ART:210-52H OUTLET REQ`D
 IN MASTER BEDROOM HALLWAY.
  
 PLEASE HAVE THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-15 Cont ID  
Sent By jleech Date 1999-10-15 Time 09:16 Rev Time 0.50
Received By jleech Date 1999-10-15 Time 09:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-02-03 Cont ID  
Sent By tlarge Date 2000-02-03 Time 07:22 Rev Time 0.25
Received By tlarge Date 2000-02-03 Time 07:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-02 Cont ID  
Sent By tlarge Date 1999-10-02 Time 06:05 Rev Time 0.33
Received By tlarge Date 1999-10-02 Time 06:05 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 1999-12-15 Cont ID  
Sent By jgomez Date 1999-12-15 Time 18:10 Rev Time 1.50
Received By jgomez Date 1999-12-15 Time 18:10 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS (WITH LEGIBLE DRAWINGS), ROUND
 AND ARCHED WINDOWS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 1999-11-20 Cont ID  
Sent By jgomez Date 1999-11-20 Time 14:14 Rev Time 1.50
Received By jgomez Date 1999-11-20 Time 14:14 Sent To  
Notes
2001-01-08 00:00:00REVISION:
 ROYAL WALL SYSTEM IN LIEU OF CBS.
  
 CHECKLIST:
 1-FIRE RATED WALL DOESN'T MEET THE
 REQUIREMENTS FOR SECTIONS 709.2.1.4.4
 AND 709.2.1.4.5 SBC 1997. (CALCS ARE
 INCORRECT).
 2-WHEN WALL FINISHES ARE ASSUMED TO
 CONTRIBUTE TO THE TOTAL FIRE
 RESISTANCE OF THE WALL, THEN THEY
 SHALL BE INSTALLED AS PER SECTION
 709.3.1.6 SBC 1997.
 3-PROVIDE COMPLETE DETAILS AND SPECS
 FOR CONCRETE PANELS WITH ROUND AND
 ARCHED OPENINGS. SEC 104.2.2 OF CITY
 AMENDMENTS TO SBC 1997.
 4-PROVIDE INFORMATION SHOWING THE R
 VALUE (12.9) CALCULATED IN THE ENERGY
 CALCULATIONS. SEC 104.2.2 CITY AMENDM.
 5-PROVIDE COPIES OF APPROVED DRAWINGS
 REFERENCED ON THE PRODUCT APPROVAL.
 6-PROVIDE COMPLETE DETAILS AND SPECS FOR
 COLUMN AT REAR PORCH.
 SEC. 104.2.2 CITY AMENDMENTS.
  
 FROM PREVIOUS PROVISO DATED 10/30/99:
 1-PROVIDE FULL SET OF PRODUCT APPROVALS.
 2-UPDATE ALL ENGINEERED TRUSSES. CUT AND
 PASTE IS NOT ACCEPTABLE.
 3-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE.
 -PROVIDE DETAIL FOR INSTALLATION OF
 STORM PANELS AT FRONT WINDOWS. SEE
 EXTERIOR SILL DETAIL AND INSTALLATION
 SCHEDULE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-10-30 Cont ID  
Sent By jgomez Date 1999-10-30 Time 14:01 Rev Time 1.50
Received By jgomez Date 1999-10-30 Time 14:01 Sent To  
Notes
2001-01-08 00:00:00 
 APPROVED WITH PROVISO:
 1-PLEASE REVISE ALL ORIGINALS SHOWING
 ALL CORRECTIONS/CLARIFICATIONS.
 2-PROVIDE SAFETY GLASS IN LIBRARY WINDOW
 SEC. 2405.2 SBC 1997.
 3-REVISE ENTRY DOOR SIZE TO HAVE 32" MIN
 CLEAR OPENING. TABLE 1004 SBC 1997.
 4-ENGINEERED TRUSS DRAWINGS:
 -UPDATE ALL DETAILS.
 -UPDATE DESIGN CRITERIA.
 -ENGINEER OF RECORD TO REVIEW ALL TRUSS
 DRAWINGS PRIOR TO SUBMITTAL.
 5-REVISE DESIGN CERTIFICATION FOR WIND
 LOAD COMPLIANCE FORM. MEAN ROOF HEIGHT
 IS INCORRECT. (21'-0" PLUS OR MINUS).
 6-SPECIFY SIZE OF CEILINGS FANS. TABLE
 6-6 FLORIDA ENERGY CODE 1997 EDITION.
 CREDIT FOR CEILING FANS WAS TAKEN IN
 THE ENRGY CALCULATIONS.
 7-PROVIDE FULL SET OF PRODUCT APPROVALS
 (MASTER PERMIT IS ON HOLD TILL ALL
 PLANS AND PRODUCT APPROVALS ARE
 PROPERLY CORRECTED).
 8-STORM PANELS:
 PROVIDE A COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE ATTACHED
 AND KEY PLAN.
 HIGHLIGHT SPECIFIC MOUNTING CONDITIONS
 AND ANCHOR SCHEDULE.
 9-PROVIDE ATTIC ACCESS AT MAIN ROOF.
 SEC. 2309.6 SBC 1997.
 10-PROVIDE COMPLETE SPECIFICATIONS FOR
 CEILING AT FRONT AND BACK PORCHES.
 SEC. 104.2.2 CITY AMENDMENTS.
 11-PROVIDE COMPLETE DETAILS AND SPECS
 FOR MOUNTING OF AHU'S.
 SEC. 104.2.2 CITY AMENDMENTS.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-09-30 Cont ID  
Sent By gjoyce Date 1999-09-30 Time 16:18 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***