Plan Review Details - Permit 99090749
Plan Review Stops For Permit 99090749
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-10-12 Cont ID  
Sent By hpiskura Date 1999-10-12 Time 14:08 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-07 Cont ID  
Sent By jleahy Date 1999-10-07 Time 09:58 Rev Time 0.45
Received By jleahy Date 1999-10-07 Time 09:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-10-12 Cont ID  
Sent By hpiskura Date 1999-10-12 Time 14:09 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-08 Cont ID  
Sent By ndenmark Date 1999-10-08 Time 11:04 Rev Time 0.33
Received By jleech Date 1999-10-08 Time 11:04 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 AHU'S WITH LESS THAN 2000 CFM BUT SERVIN
 G AREAS USED FOR EGRESS SHALL HAVE FAN
 SHUT DOWN BY DUCT SMOKE DETECTOR
 PER 1997 SMC 406
 NOTIFICATION OF FAN SHUT DOWN TO BE TIED
 TO BLDG FIRE ALARM OR HORN AND STROBE
 PER NFPA 90A 4-4.4.2 OR .3

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-11-27 Cont ID  
Sent By tlarge Date 1999-11-27 Time 11:58 Rev Time 0.33
Received By tlarge Date 1999-11-27 Time 11:58 Sent To  
Notes
2001-01-08 00:00:00PLBG.NOT AFFECTED THIS REVISION.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-09 Cont ID  
Sent By tlarge Date 1999-10-09 Time 11:34 Rev Time 0.75
Received By tlarge Date 1999-10-09 Time 11:34 Sent To  
Notes
***NONE***