Plan Review Details - Permit 99090717
Plan Review Stops For Permit 99090717
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-11-17 Cont ID  
Sent By bstaples Date 1999-10-01 Time 16:06 Rev Time 2.50
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. WOOD USED IN CONSTRUCTIONSHALL BE
 PRESSURE TREATED FIRE RETATDANT MATERIAL
 PROVIDE UL LISTING AND PRODUCT APPROVAL
 INFORMATION FOR ROOFING SYSTEMS 1997 SBC
 2. PAY IMPACT FEES
 3. WIND LOAD CERTIFICATION 1997 SBC
 4. CODE COMPLIANCE CERTIFICATION SEE FL
 STATUTES CHAPTER 553.79.
 5. SHEET S-2 INDICATE FLOOR LIVE LOADS
 SEE 1997 SBC, TABLE 1604.1.
 6. FLORIDA ENERGY SHEETS.
 7. SHEET S-4 SECTION 2-S4 INDICATES ROOF
 PITCHED BACK TO EXTERIOR WALL PROVIDE
 DETAIL.
 8. HEALTH DEPARTMNET APPROVED PLAN.
 9. WIND LOAD PRODUCT APPROVCALS FOR
 WINDOWS AND DOORS.
 10. INPACT PROTECTION FOR GLAZING
 PROVIDE PRODUCT APPROVAL INFORMATION.
 11. SHEET S-2 INDICATE EDITION OF ASCE7
 USED IN BUILDING DESIGN.
 12. FIRE RATINGSINDICATE THE FIRE
 RATING OF THE FOLLOWING,
 EXTERIOR WALLS SEE TABLE 600
 OCCUPANCY SEPARATION SEE CHAPTER 7

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2000-09-27 Cont ID  
Sent By jleahy Date 2000-09-27 Time 09:32 Rev Time 2.00
Received By jleahy Date 2000-09-27 Time 09:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2000-02-29 Cont ID  
Sent By dpalmer Date 2000-02-29 Time 08:29 Rev Time 0.00
Received By dpalmer Date 2000-02-29 Time 08:29 Sent To  
Notes
2001-01-08 00:00:00NO ELEC. REVISIONSON PLANS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-02-08 Cont ID  
Sent By jleahy Date 2000-02-07 Time 10:44 Rev Time 1.30
Received By jleahy Date 2000-02-07 Time 10:27 Sent To  
Notes
2001-01-08 00:00:00THIS REVISION WAS SUBMITTED USING THE
 ELECTRICAL PERMIT!!!!!
  
 REVISION ARE UNSATIFACTORY SEE PERMIT
 99110185 FOR ADDTIONAL COMMENTS.JLEAHY
 02/07/00MAINS, MAINS, MAINS,MAINS,MAIN

Review Stop E ELECTRICAL
Rev No 2 Status P Date 1999-12-06 Cont ID  
Sent By jleahy Date 1999-12-06 Time 09:14 Rev Time 0.00
Received By jleahy Date 2000-02-07 Time 10:22 Sent To  
Notes
2001-01-08 00:00:001- THIS IS FOR THE ROOM ONLY NO EQUIPMEN
  
 2- MAINS TO BE GROUPED WITH THE OTHERS
 FOR THIS BUILDING
  
 3- PANEL VL SHOULD HAVE A MAIN NO LARGER
 THAN 50 AMPERES OR WIRE IS TOO SMALL

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-16 Cont ID  
Sent By jleahy Date 1999-11-16 Time 09:33 Rev Time 1.15
Received By jleahy Date 1999-11-16 Time 09:32 Sent To  
Notes
2001-01-08 00:00:001- IF WALLS ARE INSTALLED AS PER PLANS
 OUTLETS WILL HAVE TO BE INSTALLED PER
 LOCAL CODE!!
  
 2- ALL MAINS IN SWITCH GEAR ROOM SHALL
 BE MARKED PER 230-2A!!!

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-09-13 Cont ID  
Sent By mcarsill Date 2000-09-13 Time 15:19 Rev Time 0.00
Received By mcarsill Date 2000-09-13 Time 15:19 Sent To  
Notes
2001-01-08 00:00:001) HANDRAILS TO COMPLY WITH NFPA 101,
 THE LIFE SAFETY CODE, 1985 EDITION,
 SECTION 5-2.2.6.4.
 2) GUARDS TO COMPLY WITH NFPA 101,
 THE LIFE SAFETY CODE, 1985 EDITION,
 SECTION 5-2.2.6.5.
 APPROVED PROVISO:

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-10-01 Cont ID  
Sent By bstaples Date 1999-10-01 Time 15:34 Rev Time 3.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00FIRE REVIEW BY LT. CARSILLO
 SEE CHECK LIST ATTACHED TO PLANS

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2000-09-07 Cont ID  
Sent By ndenmark Date 2000-09-07 Time 08:41 Rev Time 1.00
Received By ndenmark Date 2000-09-07 Time 08:41 Sent To  
Notes
2001-01-08 00:00:00REVISED M-1 AND M-2 DRAWINGS
 PROVISO: A/C UNIT SERVING CORRIDOR AREA
 TO HAVE FAN SHUT DOWN BY DUCT SMOKE DET-
 ECTOR OR SHUT DOWN WITH AREA SMOKES(BLDG
 FIRE ALARM) PER 1997 SMC 406.2 AREAS
 WITH LESS THAN 2000 CFM BUT SERVING AN
 AREA USED FOR EGRESS.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2000-05-08 Cont ID  
Sent By cthirben Date 2000-05-08 Time 13:49 Rev Time 1.00
Received By cthirben Date 2000-05-08 Time 13:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2000-02-03 Cont ID  
Sent By ndenmark Date 2000-02-03 Time 11:43 Rev Time 1.00
Received By ndenmark Date 2000-02-03 Time 11:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2000-01-12 Cont ID  
Sent By ndenmark Date 2000-01-12 Time 15:12 Rev Time 0.33
Received By ndenmark Date 2000-01-12 Time 15:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 1999-12-21 Cont ID  
Sent By ndenmark Date 1999-12-21 Time 08:29 Rev Time 0.33
Received By ndenmark Date 1999-12-21 Time 08:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-12-06 Cont ID  
Sent By ndenmark Date 1999-12-06 Time 14:08 Rev Time 0.33
Received By ndenmark Date 1999-12-06 Time 14:08 Sent To  
Notes
2001-01-08 00:00:00REVIEW FOR FOUNTAIN MECHANICAL ROOM

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-04 Cont ID  
Sent By ndenmark Date 1999-10-04 Time 07:04 Rev Time 1.50
Received By ndenmark Date 1999-10-04 Time 07:04 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1) EXHAUST DUCT ENCLOSURE SHALL BE USED
 EXCLUSIVELY TO ENCLOSE A SINGLE GREASE
 EXHAUST SYSTEM AND NO OTHER PURPOSE
 1997 SMC 505.9.1
 2) FAN SHUT DOWN REQUIRED FOR SYSTEMS W/
 LESS THAN 2000 CFM BUT SERVING AN AREA
 USED FOR EGRESS. 1997 SMC 406.2

Review Stop P PLUMBING
Rev No 12 Status P Date 2000-10-07 Cont ID  
Sent By tlarge Date 2000-10-07 Time 08:16 Rev Time 1.00
Received By tlarge Date 2000-10-07 Time 08:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 11 Status F Date 2000-06-12 Cont ID  
Sent By tlarge Date 2000-06-12 Time 19:44 Rev Time 1.25
Received By tlarge Date 2000-06-12 Time 19:44 Sent To  
Notes
2001-01-08 00:00:00SHT.P-2-CONDENSATE DRAINS SHALL NOT BE
 DIRECTLY CONNECTED TO THE STORM DRAINAGE
 SYSTEM PER SPC SEC.804.3.
  
 SHT.P-2-NOTES BAR SINKS/LAVS CONNECTED
 TO SANITARY SYSTEM.FIXTURES IN KITCHEN
 AREA EXCEPT DISHWASHER SHALL DISCHARGE
 INTO THE GREASY WASTE SYSTEM.SPC SEC.
 804.1.,1004.4.
  
 TWO WAY CLEANOUTS ARE REQD.ON THE INLET
 AND OUTLET OF THE GREASE INTERCEPTORS.
 SPC SEC.710.4.
  
 BRANCH LINES SHALL BE VALVED PER SPC
 610.4.2.(SEE NOTED AREAS ON PLANS.)
  
 SHT.P-4-NOTE #1-STATES DISHWASHER TO
 DISCHARGE INTO SANITARY.REVISE NOTE.
 DISHWASHER SHALL DISCHARGE TO SANITARY
 PER CITY OF WEST PALM BEACH ORDINANCE.
  
 CHECK DIMENSIONS AND CORRESPONDING
 CAPACITIES OF GREASE TRAPS.CAPACITY IN
 GALS.AND DIMENSIONS DON'T CORRELATE.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1

Review Stop P PLUMBING
Rev No 10 Status P Date 2000-03-14 Cont ID  
Sent By tlarge Date 2000-03-14 Time 11:45 Rev Time 0.50
Received By tlarge Date 2000-03-14 Time 11:45 Sent To  
Notes
2001-01-08 00:00:00REVISE GREASY WASTE AND CONDENSATE.
 SHTS.P-1,P-2.

Review Stop P PLUMBING
Rev No 9 Status P Date 2000-03-14 Cont ID  
Sent By tlarge Date 2000-03-14 Time 11:41 Rev Time 0.50
Received By tlarge Date 2000-03-14 Time 11:41 Sent To  
Notes
2001-01-08 00:00:00REVISE CONDENSATE AND RWL.SHT.P-1,P-5.
 ******************NOTE******************
 CONDENSATE CONNECTION TO STORM SHALL BE
 BY INDIRECT CONNECTION PER SPC 804.3.

Review Stop P PLUMBING
Rev No 8 Status P Date 2000-03-14 Cont ID  
Sent By tlarge Date 2000-03-14 Time 10:41 Rev Time 0.50
Received By tlarge Date 2000-03-14 Time 10:41 Sent To  
Notes
2001-01-08 00:00:00REVISE SHT.P-1.ADD 2-WAY CLEANOUT AT
 GREASE INTERCEPTORS AND FLOOR DRAIN.

Review Stop P PLUMBING
Rev No 7 Status F Date 2000-03-11 Cont ID  
Sent By tlarge Date 2000-03-11 Time 09:55 Rev Time 0.50
Received By tlarge Date 2000-03-11 Time 09:55 Sent To  
Notes
2001-01-08 00:00:00COMPLY W/PREVIOUS COMMENTS DATED 2/23/00

Review Stop P PLUMBING
Rev No 6 Status F Date 2000-02-23 Cont ID  
Sent By tlarge Date 2000-02-23 Time 19:34 Rev Time 1.75
Received By tlarge Date 2000-02-23 Time 19:34 Sent To  
Notes
2001-01-08 00:00:00DESIGN OF GREASE TRAP SHALL COMPLY W/
 FLA.ADMIN.CODE RULE 64E-6.013(5).
 A.)DELETE TEE FITTING FROM INLET TO
 GREASE TRAP.INLET INVERT SHALL DISCHARGE
 A MIN.OF 2 1/2" ABOVE LIQUID LEVEL LINE.
  
 B.)THE OUTLET SHALL EXTEND TO WITHIN 8"
 OF THE BOTTOM OF THE TANK.
  
 C.)GREASE INTERCEPTORS SHALL BE EQUAL
 CAPACITY WHEN INSTALLED IN SERIES.
  
 D.)APPROVAL FROM CITY OF WEST PALM BEACH
 UTILITIES IS REQUIRED FOR THE CHANGES TO
 THE GREASE INTERCEPTOR.CONTACT RODNEY
 COMPO AT(561)835-7423 FOR INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT (561)659-8096,EXT.8377.
 TIMOTHY K.LARGE, PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-02-11 Cont ID  
Sent By tlarge Date 2000-02-11 Time 12:21 Rev Time 0.50
Received By tlarge Date 2000-02-11 Time 12:20 Sent To  
Notes
2001-01-08 00:00:00SHOP DRAWINGS FOR PLUMBING EQUIP.

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-01-10 Cont ID  
Sent By tlarge Date 2000-01-10 Time 07:24 Rev Time 1.50
Received By tlarge Date 2000-01-10 Time 06:51 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
 OUTLET TEE FROM GREASE TRAP SHALL EXTEND
 TO WITHIN 8" OF BOTTOM OF TANK.DOH RULE
 64E-6.013(5).
  
 SHTS.P-1,P-2-BAR SINKS CANNOT DISCHARGE
 INTO SANITARY SYSTEM.MUST DISCHARGE THRU
 GREASE INTERCEPTOR PER SPC SEC.1004.3.
  
 CHECK DIMENSIONS FOR GREASE TRAPS AS
 LISTED ON SHT.P-2,NOTE #4.
 (5X10X6=300 CU.FT.X 7.5 GALS PER CU.FT.=
 2250 GALS.)
  
 ________________________________________
 SHTS.P-1,P-2,P-3,-REVISE SANITARY AND
 PIPE SIZES,REVISE CONDENSATE SYSTEM,
 REVISE WATER PIPING LAYOUT AND SIZES.

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-11-30 Cont ID  
Sent By tlarge Date 1999-11-30 Time 17:23 Rev Time 0.50
Received By tlarge Date 1999-11-30 Time 17:23 Sent To  
Notes
2001-01-08 00:00:00FOUNTAIN MECHANICAL ROOM :
 ******************PROVISO***************
  
 CHECK AND GATE VALVE SHALL BE LOCATED
 OUTSIDE OF PIT PER SPC SEC.717.2.

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-11-17 Cont ID  
Sent By tlarge Date 1999-11-17 Time 11:27 Rev Time 1.50
Received By tlarge Date 1999-11-17 Time 11:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-01-08 Cont ID  
Sent By tlarge Date 1999-10-04 Time 12:41 Rev Time 4.75
Received By tlarge Date 1999-10-04 Time 12:41 Sent To  
Notes
2001-01-08 00:00:00SHT.P-1 NOTES BAR SINKS CONNECTED TO
 SANITARY SYSTEM.SINKS SHALL CONNECT TO
 GREASY WASTE SYSTEM PER SPC SEC.1004.4.
  
 FLOOR DRAINS ARE NOT PROPERLY VENTED.
 COMPLY W/SPC SEC.901.2.
  
 CONTACT RODNEY COMPO AT CITY OF WEST
 PALM BEACH REGIONAL WASTEWATER TREATMENT
 PLANT FOR PROPER SIZINGOF GREASE TRAP.
 (PHONE # 835-7423.
  
 CLEARLY SHOW LOCATION OF G/T ON PLANS.
 AND DISTANCE FROM BUILDING.EXCAVATION
 SHALL COMPLY W/SBC SEC.1803.
  
 SHT.P-2.NOTE #10-TYPE"M" COPPER NOT
 PERMITTED U/G PER COUNTYWIDE AMENDMENTS
 TO BUILDING SEC.611.2.
  
 HOSE BIBBS SHALL BE VALVED PER SPC SEC.
 610.4.1.
  
 SHT.G-1.-GAS PIPE SHALL NOT BE INSTALLED
 UNDER BLDG.PER STD.GAS CODE SEC.308.3