Plan Review Stops For Permit 99090717 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
1999-11-17 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
1999-10-01 |
Time |
16:06 |
Rev Time |
2.50 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1. WOOD USED IN CONSTRUCTIONSHALL BE | | PRESSURE TREATED FIRE RETATDANT MATERIAL | | PROVIDE UL LISTING AND PRODUCT APPROVAL | | INFORMATION FOR ROOFING SYSTEMS 1997 SBC | | 2. PAY IMPACT FEES | | 3. WIND LOAD CERTIFICATION 1997 SBC | | 4. CODE COMPLIANCE CERTIFICATION SEE FL | | STATUTES CHAPTER 553.79. | | 5. SHEET S-2 INDICATE FLOOR LIVE LOADS | | SEE 1997 SBC, TABLE 1604.1. | | 6. FLORIDA ENERGY SHEETS. | | 7. SHEET S-4 SECTION 2-S4 INDICATES ROOF | | PITCHED BACK TO EXTERIOR WALL PROVIDE | | DETAIL. | | 8. HEALTH DEPARTMNET APPROVED PLAN. | | 9. WIND LOAD PRODUCT APPROVCALS FOR | | WINDOWS AND DOORS. | | 10. INPACT PROTECTION FOR GLAZING | | PROVIDE PRODUCT APPROVAL INFORMATION. | | 11. SHEET S-2 INDICATE EDITION OF ASCE7 | | USED IN BUILDING DESIGN. | | 12. FIRE RATINGSINDICATE THE FIRE | | RATING OF THE FOLLOWING, | | EXTERIOR WALLS SEE TABLE 600 | | OCCUPANCY SEPARATION SEE CHAPTER 7 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2000-09-27 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2000-09-27 |
Time |
09:32 |
Rev Time |
2.00 |
Received By |
jleahy |
Date |
2000-09-27 |
Time |
09:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
N |
Date |
2000-02-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-02-29 |
Time |
08:29 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-02-29 |
Time |
08:29 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | NO ELEC. REVISIONSON PLANS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2000-02-08 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2000-02-07 |
Time |
10:44 |
Rev Time |
1.30 |
Received By |
jleahy |
Date |
2000-02-07 |
Time |
10:27 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | THIS REVISION WAS SUBMITTED USING THE | | ELECTRICAL PERMIT!!!!! | | | | REVISION ARE UNSATIFACTORY SEE PERMIT | | 99110185 FOR ADDTIONAL COMMENTS.JLEAHY | | 02/07/00MAINS, MAINS, MAINS,MAINS,MAIN |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
1999-12-06 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
1999-12-06 |
Time |
09:14 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2000-02-07 |
Time |
10:22 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1- THIS IS FOR THE ROOM ONLY NO EQUIPMEN | | | | 2- MAINS TO BE GROUPED WITH THE OTHERS | | FOR THIS BUILDING | | | | 3- PANEL VL SHOULD HAVE A MAIN NO LARGER | | THAN 50 AMPERES OR WIRE IS TOO SMALL |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
1999-11-16 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
1999-11-16 |
Time |
09:33 |
Rev Time |
1.15 |
Received By |
jleahy |
Date |
1999-11-16 |
Time |
09:32 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1- IF WALLS ARE INSTALLED AS PER PLANS | | OUTLETS WILL HAVE TO BE INSTALLED PER | | LOCAL CODE!! | | | | 2- ALL MAINS IN SWITCH GEAR ROOM SHALL | | BE MARKED PER 230-2A!!! |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2000-09-13 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-09-13 |
Time |
15:19 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-09-13 |
Time |
15:19 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) HANDRAILS TO COMPLY WITH NFPA 101, | | THE LIFE SAFETY CODE, 1985 EDITION, | | SECTION 5-2.2.6.4. | | 2) GUARDS TO COMPLY WITH NFPA 101, | | THE LIFE SAFETY CODE, 1985 EDITION, | | SECTION 5-2.2.6.5. | | APPROVED PROVISO: |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
1999-10-01 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
1999-10-01 |
Time |
15:34 |
Rev Time |
3.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | FIRE REVIEW BY LT. CARSILLO | | SEE CHECK LIST ATTACHED TO PLANS |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
7 |
Status |
P |
Date |
2000-09-07 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-09-07 |
Time |
08:41 |
Rev Time |
1.00 |
Received By |
ndenmark |
Date |
2000-09-07 |
Time |
08:41 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REVISED M-1 AND M-2 DRAWINGS | | PROVISO: A/C UNIT SERVING CORRIDOR AREA | | TO HAVE FAN SHUT DOWN BY DUCT SMOKE DET- | | ECTOR OR SHUT DOWN WITH AREA SMOKES(BLDG | | FIRE ALARM) PER 1997 SMC 406.2 AREAS | | WITH LESS THAN 2000 CFM BUT SERVING AN | | AREA USED FOR EGRESS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
P |
Date |
2000-05-08 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-05-08 |
Time |
13:49 |
Rev Time |
1.00 |
Received By |
cthirben |
Date |
2000-05-08 |
Time |
13:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2000-02-03 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-02-03 |
Time |
11:43 |
Rev Time |
1.00 |
Received By |
ndenmark |
Date |
2000-02-03 |
Time |
11:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2000-01-12 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-01-12 |
Time |
15:12 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2000-01-12 |
Time |
15:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
1999-12-21 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
1999-12-21 |
Time |
08:29 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
1999-12-21 |
Time |
08:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
1999-12-06 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
1999-12-06 |
Time |
14:08 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
1999-12-06 |
Time |
14:08 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REVIEW FOR FOUNTAIN MECHANICAL ROOM |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
1999-10-04 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
1999-10-04 |
Time |
07:04 |
Rev Time |
1.50 |
Received By |
ndenmark |
Date |
1999-10-04 |
Time |
07:04 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO: | | 1) EXHAUST DUCT ENCLOSURE SHALL BE USED | | EXCLUSIVELY TO ENCLOSE A SINGLE GREASE | | EXHAUST SYSTEM AND NO OTHER PURPOSE | | 1997 SMC 505.9.1 | | 2) FAN SHUT DOWN REQUIRED FOR SYSTEMS W/ | | LESS THAN 2000 CFM BUT SERVING AN AREA | | USED FOR EGRESS. 1997 SMC 406.2 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
12 |
Status |
P |
Date |
2000-10-07 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-10-07 |
Time |
08:16 |
Rev Time |
1.00 |
Received By |
tlarge |
Date |
2000-10-07 |
Time |
08:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
11 |
Status |
F |
Date |
2000-06-12 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-06-12 |
Time |
19:44 |
Rev Time |
1.25 |
Received By |
tlarge |
Date |
2000-06-12 |
Time |
19:44 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SHT.P-2-CONDENSATE DRAINS SHALL NOT BE | | DIRECTLY CONNECTED TO THE STORM DRAINAGE | | SYSTEM PER SPC SEC.804.3. | | | | SHT.P-2-NOTES BAR SINKS/LAVS CONNECTED | | TO SANITARY SYSTEM.FIXTURES IN KITCHEN | | AREA EXCEPT DISHWASHER SHALL DISCHARGE | | INTO THE GREASY WASTE SYSTEM.SPC SEC. | | 804.1.,1004.4. | | | | TWO WAY CLEANOUTS ARE REQD.ON THE INLET | | AND OUTLET OF THE GREASE INTERCEPTORS. | | SPC SEC.710.4. | | | | BRANCH LINES SHALL BE VALVED PER SPC | | 610.4.2.(SEE NOTED AREAS ON PLANS.) | | | | SHT.P-4-NOTE #1-STATES DISHWASHER TO | | DISCHARGE INTO SANITARY.REVISE NOTE. | | DISHWASHER SHALL DISCHARGE TO SANITARY | | PER CITY OF WEST PALM BEACH ORDINANCE. | | | | CHECK DIMENSIONS AND CORRESPONDING | | CAPACITIES OF GREASE TRAPS.CAPACITY IN | | GALS.AND DIMENSIONS DON'T CORRELATE. | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
10 |
Status |
P |
Date |
2000-03-14 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-03-14 |
Time |
11:45 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
2000-03-14 |
Time |
11:45 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REVISE GREASY WASTE AND CONDENSATE. | | SHTS.P-1,P-2. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
9 |
Status |
P |
Date |
2000-03-14 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-03-14 |
Time |
11:41 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
2000-03-14 |
Time |
11:41 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REVISE CONDENSATE AND RWL.SHT.P-1,P-5. | | ******************NOTE****************** | | CONDENSATE CONNECTION TO STORM SHALL BE | | BY INDIRECT CONNECTION PER SPC 804.3. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
8 |
Status |
P |
Date |
2000-03-14 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-03-14 |
Time |
10:41 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
2000-03-14 |
Time |
10:41 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REVISE SHT.P-1.ADD 2-WAY CLEANOUT AT | | GREASE INTERCEPTORS AND FLOOR DRAIN. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
7 |
Status |
F |
Date |
2000-03-11 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-03-11 |
Time |
09:55 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
2000-03-11 |
Time |
09:55 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | COMPLY W/PREVIOUS COMMENTS DATED 2/23/00 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
F |
Date |
2000-02-23 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-02-23 |
Time |
19:34 |
Rev Time |
1.75 |
Received By |
tlarge |
Date |
2000-02-23 |
Time |
19:34 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | DESIGN OF GREASE TRAP SHALL COMPLY W/ | | FLA.ADMIN.CODE RULE 64E-6.013(5). | | A.)DELETE TEE FITTING FROM INLET TO | | GREASE TRAP.INLET INVERT SHALL DISCHARGE | | A MIN.OF 2 1/2" ABOVE LIQUID LEVEL LINE. | | | | B.)THE OUTLET SHALL EXTEND TO WITHIN 8" | | OF THE BOTTOM OF THE TANK. | | | | C.)GREASE INTERCEPTORS SHALL BE EQUAL | | CAPACITY WHEN INSTALLED IN SERIES. | | | | D.)APPROVAL FROM CITY OF WEST PALM BEACH | | UTILITIES IS REQUIRED FOR THE CHANGES TO | | THE GREASE INTERCEPTOR.CONTACT RODNEY | | COMPO AT(561)835-7423 FOR INFORMATION. | | | | IF YOU HAVE ANY QUESTIONS I CAN BE | | REACHED AT (561)659-8096,EXT.8377. | | TIMOTHY K.LARGE, PLANS EXAMINER. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2000-02-11 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-02-11 |
Time |
12:21 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
2000-02-11 |
Time |
12:20 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SHOP DRAWINGS FOR PLUMBING EQUIP. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2000-01-10 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-01-10 |
Time |
07:24 |
Rev Time |
1.50 |
Received By |
tlarge |
Date |
2000-01-10 |
Time |
06:51 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ****************PROVISO***************** | | OUTLET TEE FROM GREASE TRAP SHALL EXTEND | | TO WITHIN 8" OF BOTTOM OF TANK.DOH RULE | | 64E-6.013(5). | | | | SHTS.P-1,P-2-BAR SINKS CANNOT DISCHARGE | | INTO SANITARY SYSTEM.MUST DISCHARGE THRU | | GREASE INTERCEPTOR PER SPC SEC.1004.3. | | | | CHECK DIMENSIONS FOR GREASE TRAPS AS | | LISTED ON SHT.P-2,NOTE #4. | | (5X10X6=300 CU.FT.X 7.5 GALS PER CU.FT.= | | 2250 GALS.) | | | | ________________________________________ | | SHTS.P-1,P-2,P-3,-REVISE SANITARY AND | | PIPE SIZES,REVISE CONDENSATE SYSTEM, | | REVISE WATER PIPING LAYOUT AND SIZES. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
1999-11-30 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-11-30 |
Time |
17:23 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
1999-11-30 |
Time |
17:23 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | FOUNTAIN MECHANICAL ROOM : | | ******************PROVISO*************** | | | | CHECK AND GATE VALVE SHALL BE LOCATED | | OUTSIDE OF PIT PER SPC SEC.717.2. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
1999-11-17 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-11-17 |
Time |
11:27 |
Rev Time |
1.50 |
Received By |
tlarge |
Date |
1999-11-17 |
Time |
11:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2000-01-08 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-10-04 |
Time |
12:41 |
Rev Time |
4.75 |
Received By |
tlarge |
Date |
1999-10-04 |
Time |
12:41 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SHT.P-1 NOTES BAR SINKS CONNECTED TO | | SANITARY SYSTEM.SINKS SHALL CONNECT TO | | GREASY WASTE SYSTEM PER SPC SEC.1004.4. | | | | FLOOR DRAINS ARE NOT PROPERLY VENTED. | | COMPLY W/SPC SEC.901.2. | | | | CONTACT RODNEY COMPO AT CITY OF WEST | | PALM BEACH REGIONAL WASTEWATER TREATMENT | | PLANT FOR PROPER SIZINGOF GREASE TRAP. | | (PHONE # 835-7423. | | | | CLEARLY SHOW LOCATION OF G/T ON PLANS. | | AND DISTANCE FROM BUILDING.EXCAVATION | | SHALL COMPLY W/SBC SEC.1803. | | | | SHT.P-2.NOTE #10-TYPE"M" COPPER NOT | | PERMITTED U/G PER COUNTYWIDE AMENDMENTS | | TO BUILDING SEC.611.2. | | | | HOSE BIBBS SHALL BE VALVED PER SPC SEC. | | 610.4.1. | | | | SHT.G-1.-GAS PIPE SHALL NOT BE INSTALLED | | UNDER BLDG.PER STD.GAS CODE SEC.308.3 |
|
|