Plan Review Details - Permit 99090704
Plan Review Stops For Permit 99090704
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-08-28 Cont ID  
Sent By drunnels Date 2000-08-28 Time 15:24 Rev Time 1.00
Received By drunnels Date 2000-08-28 Time 15:24 Sent To  
Notes
2001-01-08 00:00:00AS BUILT O7-28-00"A" BLOCK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-12-03 Cont ID  
Sent By bstaples Date 1999-10-26 Time 14:15 Rev Time 20.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. PLANS MUST BE SPLIT INTO THREE
 SEPARATE SETS OF THREE SIGNED AND SEALED
 DOCUMENTS.
 2. IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.
 3. PROJECT IS A FLORIDA THRESHOLD
 BUILDING.PROVIDE APPLICATION
 AND INSPECTION PLAN TO DON NEELY ABO,
 FOR REVIEW AND APPROVAL. SEE SHEET S-1
 NOTE 3.
 4. LANDINGS MUST MEET 1997 SBC SECTION
 1007.4.2, SEE SHEET A-21, REFERENCE NOTE
 A-4 BRIDGE NOTE.
 5. FIRE SEPARATION RATING, DETAILS AND
 OPENINGPROTECTION INFORMATION FOR
 RESIDENTIALTO COMMERCIAL SPACE SEE
 SHEET A-11AND SHEET A-12 REQUIRE
 SECTIONS AND FIRE RATINGS.
 6. CERTIFICATION OF PLANS AS COMPLYING
 WITH FLORIDA STATUTE 553.79 AND FEDERAL
 FAIR HOUSING ACT, AUGUST 1996 AS REVISED
 APRIL 1998.
 7. SHEET A-17 INDICATES THAT A SLOPE
 STARTS AT THE DOOR, A LANDING IS
 REQUIRED AT ALL DOORS PRIOR TO STARTING
 A SLOPE 1997 SBC SECTION 1012.1.3.
 8. PRODUCT APPROVAL FOR ALL WINDOWS AND
 DOORS SBC 1997, 110 MPH WIND LOADS.
 9. PRODUCT APPROVAL FOR GLAZING TO
 SHOW COMPLIANCEWITH IMPACT PROTECTION
 REQUIREMENTS.
 10. FIRE RATING DOORS, DOOR 15, 16, 17,
 AND 22 REQUIRE B LABEL SHEET A-26
 INDICATES C LABEL.
 11. DOOR 20 TO EXCERISE ROOM TO BE 20
 MINUTE RATED AND DOOR 21 TO OFFICE TO BE
 3/4 HR. C LABELED DOOR.
 12. SHEET A-27 IF HURRICANE SHUTTERS ARE
 TO BE USED PROVIDE. A) THE STORAGE
 LOCATION FOR ALL PANELSREQUIRED AND
 THE INSTALLATION PLAN FOR REVIEW AND
 APPROVAL. CHANGE REFERENCE IN NOTE 2
 TO 1997 EDITION OF THE SBC AND SSTD
 10-97, REFERENCE IS TO THE 1994 CODE AND
 STANDARD.
 13. TRUSS DIAGRAMSFOR THE PROJECT.
 14. SHEET A-44 MEET 1997 FLORIDA
 HANDICAPPED CODE FIGURE 19 FOR STAIR
 HANDRAILS, PAGE 99.
 15. SHEET A-48 CHANGE NOTE TO REFERENCE
 1997 SBC FOR ROOFING.
 16. POOLS, SUBMIT TO HEALTH DEPT. FOR
 REVIEW AND APPROVAL, PROVIDE INFORMATION
 ON FENCING AND GATES AS REQUIRED BY CITY
 W.P.B. POOL CODE. SHEET A-54
 17. SHEET S-2 ETC. INDICATE SLUMP OF
 GROUT.
  
 18. ADDITIONAL PERMIT FEES DUE.
 19. CODE REFERENCES
 1997 STANDARD BUILDING MECHANICAL AND
 GAS CODES
 1996 NATIONAL ELECTRICAL CODE
 1994 STANDARD PLUMBING CODE
 1997 FLORIDA HANDICAPPED CODE
 1997 FLORIDA ENERGY CODE
 1996 FEDERAL FAIR HOUSING ACT AS AMENDED
 CITY OF WEST PALM BEACH AMENDMENTS TO
 THE CODES EFFECTIVE JULY 1, 1999.
  
 20. CODE REVIEW IS FOR 630, 720 AND 780
 SAPODILLA.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-10-24 Cont ID  
Sent By dpalmer Date 2000-10-24 Time 20:56 Rev Time 0.00
Received By dpalmer Date 2000-10-24 Time 20:56 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE REVISION SUBMITTED!!!
 THIS REV IS SHOWN AS REV #5 THIS REVIS-
 -ION WAS ALREADY SUBMITTED,
 THE PLAN DOES NOT REFLECT THE COMMENTS
 THAT WERE HAND WRITTEN ON THE PREVIOUS
 REVIEW. THE J-BOX SHOWN MUST REMAIN
 ACCCESSIBLE PER NATIONAL ELECTRIC CODE.
 PLEASE DO NOT SUBMIT THE SAME REVISION
 AGAIN. THE CONCEALED J-BOX IS NOT PER-
 -MITTED.
  
 PLEASE SUBMIT THE ABOVE ONLY WHEN THE
 PLANS NOTE THAT THE J-BOX IS ACCESSIBLE.
 IF THERE ARE ANY QUESTIONS ON THE ABOVE
 REVIEW. PLEASE CALL,!!
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-09-29 Cont ID  
Sent By jleahy Date 1999-09-28 Time 13:31 Rev Time 0.00
Received By jleahy Date 1999-09-29 Time 10:45 Sent To  
Notes
2001-01-08 00:00:001- PG. E-2 SHOWS PANEL HA AS HAVING 60
 SPACES IT SHOULD BE NOTED THAT THIS
 IS TWO 30 CIRCUIT PANELS. 384-16
 2- PG. E-2,E-5,AND E-11 HAVE NO AIC
 RATING SHOWN FOR BRANCH CIRCUITS.
 MAIN AIC RATING IS SHOWN BUT NOT
 THE BRANCH CIRCUIT RATINGS. 110-9
 3- PG. E-4,E-7, AND E-10 SHOW OUTLETS
 FOR SERVICING THE A/C EQUIPMENT ON
 ROOFS.NOTE IT IS A LOCAL AMENDMENT
 THAT THESE OUTLETS ARE FURTHER THAN
 25' AWAY!!210-63
 4- PG.E-5 ELECTRIC ROOM ON 1ST SHOWS NO
 OUTLET FOR SERVICING THE EQUIP.
 5- SUBMIT ALL INFORMATION REQUESTED
 BEFORE 1ST ROUGH INSPECTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-12-15 Cont ID  
Sent By bstaples Date 1999-10-22 Time 11:20 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2000-10-21 Cont ID  
Sent By ndenmark Date 2000-10-21 Time 06:55 Rev Time 0.25
Received By ndenmark Date 2000-10-21 Time 06:52 Sent To  
Notes
2001-01-08 00:00:00RAISED SEAL FRESH AIR ADDITION REVISION

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2000-08-23 Cont ID  
Sent By ndenmark Date 2000-08-23 Time 14:02 Rev Time 0.33
Received By ndenmark Date 2000-08-23 Time 14:02 Sent To  
Notes
2001-01-08 00:00:00REVISION FOR ADDITION OF FUTURE O/A

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2000-06-26 Cont ID  
Sent By cthirben Date 2000-06-26 Time 10:50 Rev Time 1.00
Received By cthirben Date 2000-06-26 Time 10:46 Sent To  
Notes
2001-01-08 00:00:00NOTE:********************************
 CALLED MELISSA AT 833 2306 REQUESTING A
 RAISED SEAL ON REVISIONS ON 6.13.00
 CALLED ON 6.26.00 FOR SAME.WILL PICK UP
 REVISION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-12-09 Cont ID  
Sent By ndenmark Date 1999-12-09 Time 07:55 Rev Time 0.33
Received By ndenmark Date 1999-12-09 Time 07:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-09 Cont ID  
Sent By ndenmark Date 1999-10-05 Time 15:33 Rev Time 0.33
Received By ndenmark Date 1999-10-05 Time 15:33 Sent To  
Notes
2001-01-08 00:00:00************CORRECTED*******************
 1) DRYER VENT EXHAUST DUCT TO BE RUN
 FULL LENGTH, SUBDUCT METHOD NOT APPROVED
 2)RISERS WHICH ARE SUBJECT TO MOISTURE
 SHALL BE LINED WITH A SUITABLE MATERIAL
 TO PREVENT DETERIORATION OF DRYWALL
 ENCLOSURE (LOCAL AMENDMENTS)
 3)OVERFLOW PROTECTION REQUIRED FOR AHU'S

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-07-12 Cont ID  
Sent By tlarge Date 2000-07-12 Time 17:56 Rev Time 1.00
Received By tlarge Date 2000-07-12 Time 17:06 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
 A 60"TURNING DIAMETER IS REQD.AT THE
 BASE OF THE RANGE PER 24 CFR 100.205
 (C)(3)(IV).

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-12-04 Cont ID  
Sent By tlarge Date 1999-12-04 Time 07:20 Rev Time 1.50
Received By tlarge Date 1999-12-04 Time 07:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 1999-12-09 Cont ID  
Sent By tlarge Date 1999-11-22 Time 15:40 Rev Time 6.50
Received By tlarge Date 1999-11-22 Time 15:40 Sent To  
Notes
2001-01-08 00:00:00SHT.A-15-UNIT"C"-A MIN.60" DIAMETER
 TURNING SPACE MUST BE PROVIDED IN A "U"
 SHAPED KITCHEN W/A RANGE AT THE BASE PER
 FAIR HOUSING ACT 24 CFR 100.205 (3)(C)
 (IV)
  
 SHT.A-10 AND A-48-SCUPPER SIZES DON'T
 MATCH.SUBMIT CALCULATIONS FOR SCUPPERS
 TO COMPLY W/APPENDIX "A" OF SPC.SHOW
 SQ.FOOTAGE DRAINED BY EACH SCUPPER.
  
 DRINKING FOUNTAINS ARE REQD.IN THE
 LEASING OFFICE AND THE FITNESS CENTER
 PER SPC TABLE 407.
  
 SHT.A-52-H.C.URINAL SHALL BE SET AT 17"
 A.F.F.TO THE RIM PER FACBC SEC.4.18.
  
 A MIN. OF 29" IS REQD.UNDER H.C.LAV.FROM
 FINISH FLOOR TO BOTTOM OF APRON PER
 FACBC SEC.4.19.2.
  
 SHT.P-5-MIN.SIZE OF WTR.SUPPLY TO URINAL
 SHALL BE 3/4" PER TABLE 607 0F SPC.
  
 SHT.P-14-STACK #45-FIXTURE BRANCHES AND
 WATER CLOSETS NOT PERMITTED ON WET VENTS
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 911.1.1.
  
 SHT.P-14-MIN.SIZE OF LOWEST WET VENT
 SHALL COMPLY W/SPC 911.3 AND TABLE 911.3
 (SEE STACKS #45,49,79.)
  
 SHT.P-15-SHOWS PAN DRAINS AS 3/4" AND AS
 1".CLARIFY.
  
 SHT.P-7-50% OF THE AREA OF THE VERTICAL
 WALL SHALL BE ADDED INTO THE PROJECTED
 ROOF AREA FOR INCLUSION INCALCULATING
 SIZE OF STORM DRAINAGE SYSTEM PER SPC
 SEC.1108.3.
  
 3" FLOOR DRAIN IN TRASH ROOM ON P-2 NOT
 SHOWN ON SANITARY RISER DIAGRAM.
  
 *******************NOTE*****************
 THE PRECEDING COMMENTS ARE TYPICAL FOR
 ALL BUILDING TYPES.

Review Stop P PLUMBING
Rev No 1 Status N Date 1999-12-09 Cont ID  
Sent By tlarge Date 1999-09-27 Time 15:43 Rev Time 7.00
Received By tlarge Date 1999-09-27 Time 15:43 Sent To  
Notes
2001-01-08 00:00:00SUPPLY DETAILS FOR SECONDARY ROOF
 DRAINAGE PER SBC SEC.1517.6.4.3.,1604.6.
 SPC 1109.(DETAILS FOR SCUPPERS NOT
 PROVIDED.)
  
 SUBMIT ISOMETRIC FOR STORM DRAINAGE
 SYSTEM.NOTE AREA DRAINED BY EACH R.D.
 COMPLY W/SPC SEC.1108.1,TABLES 1108.1,
 1108.2.AND SLOPE OF PIPE.
  
 CLEARLY SHOW THAT BASE CABINET IN KIT.
 IS OF A REMOVABLE TYPE OR SHOW KNEE
 SPACE IN COMPLIANCE W/FEDERAL FAIR
 HOUSING ACT REQ..# 7.(FOR U-SHAPED
 KITCHENS)
  
 SUBMIT DETAIL OF WATER FILL LINE FOR
 FOUNTAINS.SUPPLY TO BE PROTECTED AGAINST
 BACKFLOW PER SPC SEC.606.
  
 FLOOR PLAN SHOWS 1 1/2" DP DRAIN AND
 RISER SHOWS 1 1/4".COMPLY W/COUNTYWIDE
 AMENDMENTS TO SPC SEC.507.8.3.(SEE
 ATTACHED.)REFER TO SHTS.P-2,P-5,P-11.
  
 3" FLOOR DRAIN TO TRASH ROOM ON P-2 NOT
 ON RISER ON P-3.SPC 104.2.1.
  
 SHT.P-12-UNITS "B"AND "D2"-OVER 4
 FIXTURES ARE CONNECTED TO A 1/2" H.W.
 LINE.COMPLY W/ COUNTYWIDE AMENDMENTS TO
 SPC SEC.607.7.
  
 SHT.P-12-UNIT "C"-OVER 2 FIXTURES ARE
 CONNECTED TO A 1/2" C.W.LINE.COMPLY W/
 COUNTYWIDE AMENDMENTS TO SPC SEC.607.7
  
 SHT.P-13-UNIT F-OVER 4 FIXTURES ARE
 CONNECTED TO 1/2" H.W.
  
 SHT.P-14-STACK #19-SHALL BE 4"PER SPC
 SEC.911.4 & TABLE 911.4.(BRANCH SHALL
 REMAIN FULL SIZE BEGINNING AT HOUSE
 DRAIN.)
  
 SHT.P-14-STACKS # 7,8,38,34-LAV.CANNOT
 CONNECT TO MAIN STACK AND DRY VENT NOT
 PERMITTED PER SPC 911.3(3),911.1.
  
 SIZE OF VENT STACKS FOR MULTI-STORY
 BATHROOM GROUPS SHALL COMPLY W/SPC SEC.
 911.3 AND TABLE 911.3.
  
 CLEARLY SHOW TERMINATION/CONNECTION PT.
 OF ELEVATOR SUMP TO DRAINAGE SYSTEM.
 SPC 104.2.1.
  
 SHT.P-15.-DELETE NOTES REFERRING TO
 SFBC.SPC 101.1
  
 CONTACT CITY OF WEST PALM BEACH REGIONAL
 SEWER TREATMENT FACILITY FOR SPECIFIC
 REQS.OF GREASE AND OIL INTERCEPTORS.
 ATTENTION:RODNEY COMPO.
  
 CLEARLY SHOW LOCATION OF GREASE TRAP ON
 PLANS AND ALL ASSOCIATED PIPING.SPC
 104.2.1.
  
 *****************NOTE*******************
 THE PRECEEDING COMMENTS ARE TYPICAL FOR
 ALL BUILDING TYPES.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-22 Cont ID  
Sent By bstaples Date 1999-10-22 Time 11:25 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
***NONE***