Plan Review Details - Permit 99090559
Plan Review Stops For Permit 99090559
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-06 Cont ID  
Sent By dpalmer Date 1999-10-06 Time 19:16 Rev Time 0.00
Received By dpalmer Date 1999-10-06 Time 19:16 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO******************
  
 1)NOTE:AS PER ARTS;110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT AND
 MAIN BRKRS.FIGURED FROM FALUT CURRENT
 CALCULATIONS.
 2)NOTE:AS PER ART 250-81 GROUNDING
 ELECTRODE CONDUCTOR TO GO TO BLDG,STEEL
 ALSO.
 3)NOTE:AS PER ART;210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE:AS PER 1996/1993 NFPA-72 1996 NEC
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS IN NEW CON-
 -STRUCTION OF RES.DWELLINGS. 2-2.1.1.1
 5)NOTE:SMOKE DETECTORS ARE TO BE 5`
 FROM RETURN AIR.
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 TO BE APPROVED BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-29 Cont ID  
Sent By jleech Date 1999-09-29 Time 11:22 Rev Time 0.50
Received By jleech Date 1999-09-29 Time 11:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-07 Cont ID  
Sent By tlarge Date 1999-10-07 Time 08:58 Rev Time 0.33
Received By tlarge Date 1999-10-07 Time 08:57 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-10-29 Cont ID  
Sent By jcaloger Date 1999-10-13 Time 15:17 Rev Time 2.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-09-21 Cont ID  
Sent By gjoyce Date 1999-09-21 Time 13:58 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***