Plan Review Details - Permit 99090547
Plan Review Stops For Permit 99090547
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-10-05 Cont ID  
Sent By hpiskura Date 1999-10-05 Time 14:16 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 PROVIDE UPDATED CODE SUMMARY (1997)

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-09-28 Cont ID  
Sent By jleahy Date 1999-09-28 Time 12:24 Rev Time 1.00
Received By jleahy Date 1999-09-28 Time 12:24 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 1999-12-22 Cont ID  
Sent By dlauderm Date 1999-12-22 Time 11:22 Rev Time 0.25
Received By dlauderm Date 1999-12-22 Time 11:21 Sent To  
Notes
2001-01-08 00:00:00NO REVIEW REQUIRED BY WATER, STORM, OR
 SANITARY, SANITATION, STREETS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-09-27 Cont ID  
Sent By tlarge Date 1999-12-22 Time 15:30 Rev Time 0.00
Received By tlarge Date 1999-12-22 Time 15:30 Sent To  
Notes
2001-01-08 00:00:00APPROVED AND SIGNED BY R.TURNQUIST ON
 9/27/99.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-27 Cont ID  
Sent By ndenmark Date 1999-09-27 Time 14:44 Rev Time 0.33
Received By ndenmark Date 1999-09-27 Time 14:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-12-21 Cont ID  
Sent By tlarge Date 1999-12-21 Time 19:07 Rev Time 0.75
Received By tlarge Date 1999-12-21 Time 19:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 1999-12-21 Cont ID  
Sent By tlarge Date 1999-12-03 Time 07:13 Rev Time 0.75
Received By tlarge Date 1999-12-03 Time 07:13 Sent To  
Notes
2001-01-08 00:00:00CLEARLY NOTE TYPE OF WALL FINISH IN
 TOILET ROOMS.WALLS SHALL BE NONABSORBENT
 TO A HT.OF 4' PER SBC 1204.2.
  
 PROVIDE U.L.ASSEMBLY # FOR FIRE SAFING
 DETAILS.
  
 ALL SHEETS SHALL BE SIGNED AND SEALED
 PER SPC 104.2.3.

Review Stop P PLUMBING
Rev No 1 Status N Date 1999-12-21 Cont ID  
Sent By tlarge Date 1999-10-04 Time 15:27 Rev Time 1.50
Received By tlarge Date 1999-10-04 Time 15:27 Sent To  
Notes
2001-01-08 00:00:00SHT.A1.01-HANDICAP TOILET ROOM SHALL
 PROVIDE A CLEAR SPACE FOR TURNING PER
 FACBC SEC.4.2.3.AND CLEAR FLOOR SPACE AT
 FIXTURES SHALL COMPLY W/FACBC FIG.28.
  
 A FLOOR DRAIN IS REQD.IN THE TOILET
 ROOM PER SPC SEC.409.4.1.1.
  
 WALLS AND FLOOR IN TOILET ROOM SHALL
 COMPLY W/SBC SEC.1204.
  
 PROVIDE FIRE SAFING DETAIL FOR PIPE
 PENETRATIONS THRU RATED WALLS PER SPC
 104.2.4.
  
 ALL SHEETS SHALL BE SIGNED AND SEALED
 PER SPC SEC.104.2.3.
  
 PLANS SHALL BE APPROVED BY AHCA PRIOR TO
 APPROVAL BY THIS DEPT.SPC 101.4.7.
  
 SUBMIT SANITARY AND WATER ISOMETRIC FOR
 ALL CHANGES TO THE PLBG.SYSTEM.SPC 104.2

Review Stop Z ZONING
Rev No 1 Status N Date 1999-12-23 Cont ID  
Sent By gjoyce Date 1999-12-23 Time 08:18 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***