Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-09-30 Cont ID  
Sent By bstaples Date 1999-09-30 Time 11:41 Rev Time 16.00
Received By bstaples Date 1999-09-30 Time 11:41 Sent To  
Notes
2001-01-08 00:00:001 SITE PLAN WITH DEMINSONS TO ADJACENT
 BUILDINGS.
 2. FOAM PLASTIC MATERIALS SHALL COMPLY
 WITH SECTION 707 AND CHAPTER 26 1997 SBC
 3. PRODUCT INFORMATION ON 8" BLOCK TO
 INSURE CODE COMPLIANCE FOR A FOUR HOUR
 FIRE WALL TO PARKING DECK AND RETAIL
 DECK.
 4 ENGINEER TO APPROVE THE DESIGN OF THE
 FIRE WALLS AS INDICATED WITH THE
 RENFORCEMENT INDICATED ON THE PLANS.
 5. PROVIDE INFORMATION ON WALL OPEANINGS
 TO MEET THE REQUIREMENTS OF TABLE 600
 1997 SBC FOR STREET ELEVEATIONS.
 6. PROVIDE FIRE PROTECTION DESIGN FOR
 WALLS FACING STREET.
 7. PERMIT IS FOR FOUNDATION AND FRAME
 ONLY SEPERATE PERMITS ARE REQUIRED FOR
 COMPLETION OF THE BUILDING.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-09-30 Cont ID  
Sent By dpalmer Date 1999-09-20 Time 09:06 Rev Time 0.00
Received By bstaples Date 1999-09-20 Time 09:06 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*********************
  
 1)NEED TO SHOW ALL UNDERGROUND CONDUITS
 AND SIZES.
 SHOW ELECTRICAL RISER DIAGRAM AND
 LOCATION.
 2)SHOW CONDUIT FOR ALL OTHER UNDERGROUND
 FEEDS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-09-30 Cont ID  
Sent By bstaples Date 1999-09-30 Time 11:40 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-30 Cont ID  
Sent By ndenmark Date 1999-09-20 Time 11:58 Rev Time 0.33
Received By ndenmark Date 1999-09-20 Time 11:58 Sent To  
Notes
2001-01-08 00:00:00PROVISO
 PROVIDE DETAIL FOR EXHAUST FAN TERM-
 INATION
 PLUMBING VENT THRU ROOF AND EXHAUST FANS
 SHALL NOT TERMINATE WITHIN 10' OF OUT
 SIDE AIR MAKE UP FOR ROOFTOP A/C EQUIP.
 SHOW LOCATION OF MAKE UP AIR INTAKE ON
 PLAN FOR REVIEW PURPOSES
 PROVIDE REVISED PLANS FOR THIS WORK
 PRIOR TO COMENSING THIS PORTION OF BLDG

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-01 Cont ID  
Sent By tlarge Date 1999-09-11 Time 11:30 Rev Time 3.50
Received By tlarge Date 1999-09-11 Time 11:30 Sent To  
Notes
2001-01-08 00:00:00SUBMIT OCCUPANT LOAD FOR EACH LEVEL AND
 TOTAL OCCUPANT LOAD TO ENSURE COMPLIANCE
 W/TABLE 407 AND FLA.STATUTE 553.141
 (POTTY PARITY)FOR M,IN.FIXTURE REQS.
  
 DRINKING FOUNTAINS ARE REQD.PER TABLE
 407 OF SPC.DRINKING FOUNTAINS SHALL
 COMPLY W/FACBC SECS.4.1.3(10)(A),4.15.
  
 TOILET STALLS SHALL COMPLY W/FACBC SECS.
 4.17,4.17.3(SEE EXCEPTION:NEW
 CONSTRUCTION)A LAVATORY IS REQD.IN THE
 ACCESSIBLE STALL.
  
 SUBMIT COMPLETE DETAILS FOR HANDICAP
 FIXTURES AND ACCESSORIES.COMPLY W/FACBC
 REQS.
  
 SUBMIT A WATER,SANITARY,STORM AND COND.
 ISOMETRIC FOR REVIEW.SPC 104.2.1.
  
 PLBG.SHEETS REFER TO CIVIL DRWGS.FOR
 CONTINUATION OF PLBG.LINES.SUBMIT CIVIL
 DRWGS.FOR REVIEW.104.2.1.
  
 PLANS SHALL BE REVIEWED AND APPROVED BY
 PALM BEACH COUNTY HEALTH DEPT.PRIOR TO
 REVIEW BY THIS DEPT.SPC SEC.101.4.7.
  
 A BACKFLOW DEVICE IS REQD.ON THE
 DOMESTIC WATER SERVICE PER SPCSEC.606.
  
 WALLS AND FLOORS IN RESTROOMS AND TOILET
 ROOMS SHALL COMPLY W/SBC SEC.1204.2.
  
 FLOOR DRAINS ARE REQD.IN RESTROOMS AND
 TOILET ROOMS PER SPC SEC.409.4.4.1.
  
 PROVISIONS FOR DRAINAGE OF OVERFLOW
 WATER FROM THE ROOF STRUCTURE SHALL BE
 PROVIDED PER SBC SEC.1517.6.4.1.THRU
 1517.6.4.3.,1604.6.2.SUBMIT SIZE AND
 DETAILS OF SCUPPERS/OVERFLOW DRAINAGE.
  
 CONTACT RODNEY COMPO FOR INFORMATION
 REGARDING GREASE INTERCEPTOR AT CITY OF
 W.P.B.REGIONAL SEWER TREATMENT PLANT AT
 835-7423.SHOW DISTANCE OF GREASE INT.
 FROM BLDG.COMPLY W/SBC SEC.1803.1.3.
  
 SUBMIT DETAIL OF GREASE INT.SPC 104.2.1.
 1004.2
  
 NUMBER OF REQD.URINALS SHALL COMPLY
 W/SPC TABLE 407 FOOTNOTE #3.
  
 UNISEX TOILET ROOMS ARE ONLY PERMITTED
 AS ALLOWED IN TABLE 407 FOOTNOTE #6.
  
  
 AN ADDITIONAL TOILET STALL SHALL COMPLY
 W/FACBC SEC.4.22.4.
  
 *********COMMENTS FOR SHELL ONLY*******
 SUBMIT A WATER,SANITARY,STORM AND
 CONDENSATE ISOMETRIC FOR REVIEW.SPC
 SEC.104.2.1.
  
 PLANS REFER TO CIVIL DRWGS.FOR CONTIN-
 UATION OF PLBG. LINES.SUBMIT CIVIL DWGS.
 FOR REVIEW OR LIST PERMIT NUMBER FOR
 THIS WORK.
  
 A BACKFLOW PREVENTION DEVICE IS REQD.ON
 THE DOMESTIC WATER SERVICE PER SPC SEC.
 606.
  
 PROVISIONS FOR DRAINAGE OF OVERFLOW
 WATER FROM THE ROOF STRUCTURE SHALL BE
 PROVIDED PER SBC SEC.1517.6.4.1 THRU
 1517.6.4.3.,1604.6.2. SUBMIT SIZE AND
 DETAILS OF SCUPPERS/OVERFLOW DRAINAGE.
  
 CONTACT RODNEY COMPO FOR INFORMATION
 REGARDING GREASE INTERCEPTOR SIZE AT
 CITY OF W.P.B. REGIONAL SEWER TREATMENT
 PLANT AT (561)835-7423.SHOW DISTANCE OF
 GREASE INTERCEPTOR FROM BLDG.COMPLY W/
 SBC SEC.1803.1.3.
  
 SUBMIT DETAIL OF GREASE INTERCEPTOR.
 SPC SEC.104.2.1.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-09-09 Cont ID  
Sent By gjoyce Date 1999-09-09 Time 09:18 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***