Plan Review Details - Permit 99090087
Plan Review Stops For Permit 99090087
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-09-21 Cont ID  
Sent By dpalmer Date 1999-09-21 Time 08:01 Rev Time 0.00
Received By dpalmer Date 1999-09-21 Time 08:00 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO********************
  
 1)NOTE:NO EQUIPMENT GROUND FROM METER
 THE FIRST MEANS OF DISC.
 2)NOTE:AS PER ART;250-81 GROUNDING
 ELECTRODE CONDUCTOR TO BLDG.STEEL ALSO.
 3)NOTE:PANEL SCHEDULE TO SHOW BATH
 CIRCUT.
 4)NOTE:AS PER ART;210-63 RECEPT.REQ`D
 FOR A/C COND.UNIT.
 5)NOTE:NEED TO HAVE AIC RATING LISTED ON
 PANELSCHED/RISER DIAGRAM AS PER ART;
 110-9, 215-5
  
  
 NEED TO SUBMIT THE ABOVE BEFORE THE
 FIRST ROUGH ELECTRICAL INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-07 Cont ID  
Sent By jleech Date 1999-09-07 Time 11:08 Rev Time 0.50
Received By jleech Date 1999-09-07 Time 11:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-09-11 Cont ID  
Sent By tlarge Date 1999-10-13 Time 09:01 Rev Time 0.50
Received By tlarge Date 1999-10-13 Time 09:01 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 1999-11-20 Cont ID  
Sent By jgomez Date 1999-11-20 Time 16:44 Rev Time 1.50
Received By jgomez Date 1999-11-20 Time 16:44 Sent To  
Notes
2001-01-08 00:00:00REVISION:
 ROYAL WALL SYSTEM INSTEAD OF MASONRY:
  
 CHECKLIST:
 1-ROYAL WALL SYSTEM PRODUCT APPROVAL IS
 APPROVED FOR PANELS UP TO 15'6" HIGH.
 ENTRY TOWER IS 20'-8". PROVIDE A
 COMPLETE SITE SPECIFIC ENGINEERING
 ANALYSIS WITH COMPLETE CALCULATIONS,
 SPECIFICATIONS AND DETAILS.
 2-FIRE RATED WALL DOESN'T MEET THE
 REQUIREMENTS FOR SECTIONS 709.2.1.4.4
 AND 709.2.1.4.5 SBC 1997.
 CALCULATIONS ARE INCORRECT.
 3-WHEN WALL FINISHES CONTRIBUTE TO GET
 THE TOTAL FIRE RESISTANCE OF THE WALL,
 THEN, THEY SHALL BE INSTALLED AS PER
 SECTION 709.3.1.6 SBC 1997. PROVIDE
 SUCH SPECIFICATIONS.
 4-PROVIDE COMPLETE DETAILS AND SPECS FOR
 CONCRETE PANELS WITH ROUND AND ARCHED
 OPENINGS. SECTION 104.2.2 CITY
 AMENDMENTS TO SBC 1997.
 5-PROVIDE INFORMATION SHOWING THE R
 VALUE (12.9) CALCULATED IN THE ENERGY
 CALCULATIONS. SEC 104.2.2 AMENDMENTS.
 6-PROVIDE COPIES OF APPROVED DRAWINGS
 REFERENCED IN THE PRODUCT APPROVAL.
 7-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM. THE
 MEAN ROOF HEIGHT IS 23'-6" MORE OR
 LESS.
  
 FROM PREVIOUS PROVISO:
 1-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE.
 -PROVIDE DETAIL FOR INSTALLATION OF
 STORM PANEL AT FRONT WINDOW. SEE SILL
 DETAIL.
 2-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS, WINDOW AT DINING AREA AND
 ARCHED WINDOW.
 3-UPDATE ALL ENGINEERED DRAWINGS. CUT
 AND PASTE IS NOT ACCEPTABLE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-10-12 Cont ID  
Sent By jgomez Date 1999-10-12 Time 18:09 Rev Time 2.00
Received By jgomez Date 1999-10-12 Time 18:09 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PLEASE REVISE ALL ORIGINAL DRAWINGS
 SHOWING ALL CORRECTIONS/CLARIFICATIONS
 AS REQUESTED ON PLANS.
 2-PROVIDE 32" MINIMUM CLEAR OPENING AT
 ENTRY DOOR. TABLE 1004 SBC 1997.
 3-REVISE DESIGN CERTIFICATION FOR WIND
 LOAD COMPLIANCE FORM. MEAN ROOF HEIGHT
 IS 23'-6" PLUS O MINUS. SEE COMMENTS
 ON PLANS.
 4-PROVIDE ATTIC ACCESSS AT ENTRY TOWER
 AND AT GUEST SUITE/GOLFCART AREA AS
 PER SEC. 2309.6 SBC 1997.
 5-PROVIDE SIZES OF CEILING FANS AS PER
 TABLE 6-6 OF FLORIDA ENERGY CODE, 1997
 6-CLARIFY IF FIXED WINDOW AT GRAND ROOM
 HAS TRUE MULLIONS OR NOT IN ORDER TO
 VERIFY ACTUAL SIZE OF WINDOW.
 7-STORM PANELS: PROVIDE A COMPLETE
 INSTALLATION SCHEDULE AS PER CITY
 SAMPLE AND KEY PLAN.
 8-PROVIDE TWO COPIES OF ENGINEERED ROOF
 TRUSSES SIGNED AND SEALED AND REVIEWED
 BY DESIGNER OF RECORD.
 9-PROVIDE PRODUCT APPROVAL FOR WINDOW AT
 DINING AREA.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-09-03 Cont ID  
Sent By gjoyce Date 1999-09-03 Time 15:32 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***