Plan Review Details - Permit 99090086
Plan Review Stops For Permit 99090086
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-05 Cont ID  
Sent By dpalmer Date 1999-10-05 Time 12:44 Rev Time 0.00
Received By dpalmer Date 1999-10-05 Time 12:43 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO**************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 ALL EQUIPMENT AND MAINS AS PER ARTS;
 110-9/215-5 FIGURED FROM FAULT CURRENT
 CALCULATIONS.
 2)NOTE; EQUIPMENT GROUNDING CONDUCTOR IS
 ONLY TO BE INSTALLED AFTER FIRST MEANS
 OF DISC.
 3)NOTE:AS PER ART;250-81 GROUNDING
 ELECTRODE CONDUCTOR IS REQ`D TO GO TO
 BLDG.STEEL ALSO.
 4)NOTE: AS PER ART;210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 5)NOTE:MASTER BEDROOM HALLWAY AS PER ART
 210-52H
  
 NEED TO SUBMIT ALL THE ABOVE INFORMATION
 FOR APPROVAL BEFORE FIRST ELECTRICAL
 INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-07 Cont ID  
Sent By jleech Date 1999-09-07 Time 10:41 Rev Time 0.50
Received By jleech Date 1999-09-07 Time 10:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-09-11 Cont ID  
Sent By tlarge Date 1999-10-13 Time 15:20 Rev Time 0.50
Received By tlarge Date 1999-10-13 Time 15:20 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 1999-11-18 Cont ID  
Sent By jgomez Date 1999-11-18 Time 14:35 Rev Time 3.00
Received By jgomez Date 1999-11-18 Time 14:35 Sent To  
Notes
2001-01-08 00:00:00REVISION: ROYAL WALL SYSTEM IN LIEU OF
 MASONRY CONSTRUCTION.
  
 CHECKLIST:
 1-FIRE RATED WALL AT ZERO LOT LINE DOES
 NOT MEET THE REQUIREMENTS FOR SECTION
 709.2.1.4.4 AND SECTION 709.2.1.4.5
 SBC 1997.(CALCS ARE INCORRECT).
 2-WHEN FINISHES ON CONCRETE WALLS ARE
 ASSUMED TO CONTRIBUTE TO THE TOTAL
 FIRE RESISTANCE OF THE WALL, THEN THE
 INSTALLATION REQUIREMENTS SHALL BE AS
 PER SECTION 709.3.1.6 SBC 1997.
 SECTION 709.2.1.4.6 SBC 1997.
 3-PROVIDE COMPLETE DETAILS AND SPECS FOR
 CONCRETE PANELS WITH ROUND AND ARCHED
 OPENINGS. SEC. 104.2.2 CITY AMENDMENTS
 4-PROVIDE INFORMATION SHOWING THE R
 VALUE (12.9) FOR THE INSULATION SHOWN.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 5-DETERMINE WHICH ROYAL WALL SYSTEM
 PRODUCT APPROVAL IS GOING TO BE USED.
 DADE COUNTY OR SBCCI. AND PROVIDE
 COPIES OF THE APPROVED DRAWINGS.
 6-PROVIDE COMPLETE DETAILS AND SPECS FOR
 COLUMN AT COVERED PORCH.
 SECTION 104.2.2 CITY AMENDMENTS.
  
 FROM PREVIOUS PROVISO, DATED 10/13/99:
 1-PROVIDE PRODUCT APPROVAL FOR:
 FIXED WINDOW AT LIVING AREA, ENTRY
 DOORS, ROUND AND ARCHED WINDOWS.
 2-STORM PANELS:
 -PROVIDE COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE (ATTACHED)
 -PROVIDE DETAIL FOR INSTALLATION OF
 STORM PANELS AT FRONT WINDOWS. SEE
 EXTERIOR SILL DETAIL AND INSTALLATION
 SCHEDULE.
 3-TRUSS DRAWINGS:
 -UPDATE ALL DETAILS AND ENGINEERED ROOF
 TRUSSES. ENGINEERED TRUSSES SHOW CUT
 AND PASTE INFORMATION SHOWING THE
 DESIGN CRITERIA TO BE SBC 1997.
 THIS IS NOT ACCEPTABLE.
 -CLARIFY/REVISE IF TRUSS FGT4 IS ONE
 PLY OR TWO PLYS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-10-13 Cont ID  
Sent By jgomez Date 1999-10-13 Time 14:15 Rev Time 2.00
Received By jgomez Date 1999-10-13 Time 14:15 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PLEASE REVISE ALL ORIGINAL DRAWINGS
 SHOWING ALL CLARIFICATIONS/CORRECTIONS
 AS REQUESTED ON PLANS.
 2-PROVIDE 32" MINIMUM CLEAR OPENING AT
 ENTRY DOOR. TABLE 1004 SBC 1997.
 3*PROVIDE PRODUCT APPROVAL FOR FIXED
 WINDOW AT LIVING AREA. CLARIFY IF
 WINDOW IS TO HAVE MULLIONS OR MUNTINS.
 *SAME CLARIFICATION IS REQUIRED FOR
 FIXED WINDOW AT FAMILY AREA.
 4-PROVIDE DESIGN PRESSURES FOR ALL
 EXTERIOR OPENINGS. SEC 1606 SBC 1997.
 5-SPECIFY SIZES OF CEILING FANS AS PER
 TABLE 6-6 FLORIDA ENERGY CODE, 1997.
 SEE ENERGY CALCULATIONS FOR CREDIT
 TAKEN FOR CEILING FANS.
 6-PROVIDE ATTIC ACCESS AT MAIN ROOF.
 SEC. 2309.6 SBC 1997.
 7-PROVIDE TWO COPIES OF ENGINEERED
 TRUSSES, SIGNED AND SEALED AND REVIEWED
 BY DESIGNER OF RECORD.
 8-PROVIDE KNEEWALL DETAIL AT LOCATION
 MARKED ON DRAWING #7. SEE PLANS.
 9-PROVIDE A COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE AND KEY
 PLAN FOR STORM PANELS.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-09-03 Cont ID  
Sent By gjoyce Date 1999-09-03 Time 15:33 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***