Plan Review Details - Permit 99090050
Plan Review Stops For Permit 99090050 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2000-02-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-02-22 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-02-22 |
Time |
11:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
1999-10-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
1999-09-22 |
Time |
17:43 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
1999-09-22 |
Time |
17:43 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ***************UNSAT******************** | | | | 1)NOTE:NEED TO SHOW LOCATION OF PROPOSED | | PANEL'B' ART;215-5 | | 2)NOTE;NEED TO SHOW ON PANEL SCHED. AND | | LOAD CALCULATIONS TWO SMALL PER KITCHEN. | | ART;215-5 | | 3)NOTE;BATH CIRCUT/S ARE NOT SHOWN ON | | PANEL 'A' AND REQ`S DEDICATED CIRCUT | | AS PER ART;210-52D | | 4)NOTE;QUESTION AS TO 6-2/0 CONDUCTORS | | TO PANEL 'A'??? | | 5)NOTE;IF PROPOSED PANEL'B' IS TO FEED | | SEPARATE BLDG. THEN MAINS MUST BE | | GROUPED AS PER ART; 230-72 | | 6)NOTE;AS PER ART;210-8-A-6 ALL RECEPTS. | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | GFI/GFI PROTECTED. | | 7)NOTE;AS PER ART;210-52E WP GFI RECEPTS | | ARE REQ`D FRONT AND BACK OF DWELLINGS. | | 8)NOTE;AS PER ART;210-63 A RECEPT. IS | | REQ`D FOR THE A/C COND. UNIT. | | 9)NOTE; PLEASE SHOW DISC.S FOR A/C COND. | | UNITS AS PER ART;440-11 | | 10)NOTE;POWDER ROOM BY FRONT DOOR REQ`S | | GFI RECEPT. AND TO BE ON BATH CIRCUT. | | AS PER ART;210-52D | | 11)NOTE;RECEPT.AND LIGHT REQ`D FOR AHU | | IN ATTIC.210-70/210-63 | | 12)NOTE;THERE ARE NUMEROUS LOCATIONS | | FOR OUTLETS REQ`D BY ART;210-52 | | NOTE THE 2`6`12` RULE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | AND RESUBMIT. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2000-02-26 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-02-26 |
Time |
09:43 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2000-02-26 |
Time |
09:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
1999-10-04 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
1999-09-22 |
Time |
13:31 |
Rev Time |
0.00 |
Received By |
cthirben |
Date |
2000-02-24 |
Time |
11:04 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | NEED MODEL NUMBER OF CONDENSOR AND AIR | | HANDLER AND SEER FOR BOTH FLOORS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2000-02-23 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-02-23 |
Time |
17:45 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
2000-02-23 |
Time |
17:45 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | WATER CLOSETS,SHOWERS AND TUBS ON 2ND.FL | | ARE NOT PROPERLY VENTED.COMPLY W/SPC | | SEC.901.2 | | | | 2ND.FLR.PLUMBING CANNOT DRAIN INTO VENT | | FOR 1ST.FLR.FIXTURES.SPC.SEC.904.1. | | | | MAX.2 WATER CLOSETS PERMITTED ON 3" | | BUILDING DRAIN PER SPC TABLE 714.1 | | FOOTNOTE #3. | | | | ONLY FIXTURE DRAINS PERMITTED ON HORIZ. | | WET VENTS PER COUNTYWIDE AMENDMENTS TO | | SPC SEC.911.1.1. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
1999-10-04 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-09-22 |
Time |
10:02 |
Rev Time |
0.65 |
Received By |
fknapp |
Date |
1999-09-22 |
Time |
10:02 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | WATER CLOSETS,SHOWERS AND TUBS ON 2ND.FL | | ARE NOT PROPERLY VENTED.COMPLY W/SPC SEC | | 901.2 | | | | 2ND FLR.PLBG.CANNOT DRAIN INTO VENT FOR | | 1ST.FLR.FIXTURES.SPC SEC.904.1. | | | | MAX.2 WATER CLOSETS PERMITTED ON 3"BLDG. | | DRAIN PER SPC TABLE 714.1,FOOTNOTE #3 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
1999-10-04 |
|
|
Cont ID |
|
Sent By |
fknapp |
Date |
1999-10-04 |
Time |
12:56 |
Rev Time |
4.00 |
Received By |
fknapp |
Date |
1999-10-04 |
Time |
09:01 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO: | | | | 1)PROVIDE 2 CURRENT COPIES OF PRODUCT | | APPROVAL FOR NEW EXTERIOR DOORS AND | | WINDOWS. | | | | 2)PROVIDE STORM PANEL INSTALLATION | | SCHEDULE & KEY PLAN WITH SPECIFIC | | MOUNTING & ANCHORS TO BE USED,UNDER | | SEPERATE PERMIT. | | | | 3)PROVIDE 2 CURRENT COPIES OF PRODUCT | | APPROVAL FOR ROOF COVERING UNDER | | SEPERATE PERMIT. | | | | SUBMIT PRIOR TO INSTALLATION. | | | | NOTE:TRADES TO BE UNDER SEPERATE PERMITS |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
1999-09-03 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
1999-09-03 |
Time |
11:43 |
Rev Time |
0.25 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|