Plan Review Details - Permit 99090050
Plan Review Stops For Permit 99090050
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-22 Cont ID  
Sent By dpalmer Date 2000-02-22 Time 11:23 Rev Time 0.00
Received By dpalmer Date 2000-02-22 Time 11:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-10-04 Cont ID  
Sent By dpalmer Date 1999-09-22 Time 17:43 Rev Time 0.00
Received By dpalmer Date 1999-09-22 Time 17:43 Sent To  
Notes
2001-01-08 00:00:00***************UNSAT********************
  
 1)NOTE:NEED TO SHOW LOCATION OF PROPOSED
 PANEL'B' ART;215-5
 2)NOTE;NEED TO SHOW ON PANEL SCHED. AND
 LOAD CALCULATIONS TWO SMALL PER KITCHEN.
 ART;215-5
 3)NOTE;BATH CIRCUT/S ARE NOT SHOWN ON
 PANEL 'A' AND REQ`S DEDICATED CIRCUT
 AS PER ART;210-52D
 4)NOTE;QUESTION AS TO 6-2/0 CONDUCTORS
 TO PANEL 'A'???
 5)NOTE;IF PROPOSED PANEL'B' IS TO FEED
 SEPARATE BLDG. THEN MAINS MUST BE
 GROUPED AS PER ART; 230-72
 6)NOTE;AS PER ART;210-8-A-6 ALL RECEPTS.
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 7)NOTE;AS PER ART;210-52E WP GFI RECEPTS
 ARE REQ`D FRONT AND BACK OF DWELLINGS.
 8)NOTE;AS PER ART;210-63 A RECEPT. IS
 REQ`D FOR THE A/C COND. UNIT.
 9)NOTE; PLEASE SHOW DISC.S FOR A/C COND.
 UNITS AS PER ART;440-11
 10)NOTE;POWDER ROOM BY FRONT DOOR REQ`S
 GFI RECEPT. AND TO BE ON BATH CIRCUT.
 AS PER ART;210-52D
 11)NOTE;RECEPT.AND LIGHT REQ`D FOR AHU
 IN ATTIC.210-70/210-63
 12)NOTE;THERE ARE NUMEROUS LOCATIONS
 FOR OUTLETS REQ`D BY ART;210-52
 NOTE THE 2`6`12` RULE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 AND RESUBMIT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-02-26 Cont ID  
Sent By jleech Date 2000-02-26 Time 09:43 Rev Time 0.50
Received By jleech Date 2000-02-26 Time 09:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 1999-10-04 Cont ID  
Sent By jleech Date 1999-09-22 Time 13:31 Rev Time 0.00
Received By cthirben Date 2000-02-24 Time 11:04 Sent To  
Notes
2001-01-08 00:00:00NEED MODEL NUMBER OF CONDENSOR AND AIR
 HANDLER AND SEER FOR BOTH FLOORS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-02-23 Cont ID  
Sent By tlarge Date 2000-02-23 Time 17:45 Rev Time 0.50
Received By tlarge Date 2000-02-23 Time 17:45 Sent To  
Notes
2001-01-08 00:00:00WATER CLOSETS,SHOWERS AND TUBS ON 2ND.FL
 ARE NOT PROPERLY VENTED.COMPLY W/SPC
 SEC.901.2
  
 2ND.FLR.PLUMBING CANNOT DRAIN INTO VENT
 FOR 1ST.FLR.FIXTURES.SPC.SEC.904.1.
  
 MAX.2 WATER CLOSETS PERMITTED ON 3"
 BUILDING DRAIN PER SPC TABLE 714.1
 FOOTNOTE #3.
  
 ONLY FIXTURE DRAINS PERMITTED ON HORIZ.
 WET VENTS PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.911.1.1.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-10-04 Cont ID  
Sent By tlarge Date 1999-09-22 Time 10:02 Rev Time 0.65
Received By fknapp Date 1999-09-22 Time 10:02 Sent To  
Notes
2001-01-08 00:00:00WATER CLOSETS,SHOWERS AND TUBS ON 2ND.FL
 ARE NOT PROPERLY VENTED.COMPLY W/SPC SEC
 901.2
  
 2ND FLR.PLBG.CANNOT DRAIN INTO VENT FOR
 1ST.FLR.FIXTURES.SPC SEC.904.1.
  
 MAX.2 WATER CLOSETS PERMITTED ON 3"BLDG.
 DRAIN PER SPC TABLE 714.1,FOOTNOTE #3

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-10-04 Cont ID  
Sent By fknapp Date 1999-10-04 Time 12:56 Rev Time 4.00
Received By fknapp Date 1999-10-04 Time 09:01 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
  
 1)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVAL FOR NEW EXTERIOR DOORS AND
 WINDOWS.
  
 2)PROVIDE STORM PANEL INSTALLATION
 SCHEDULE & KEY PLAN WITH SPECIFIC
 MOUNTING & ANCHORS TO BE USED,UNDER
 SEPERATE PERMIT.
  
 3)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVAL FOR ROOF COVERING UNDER
 SEPERATE PERMIT.
  
 SUBMIT PRIOR TO INSTALLATION.
  
 NOTE:TRADES TO BE UNDER SEPERATE PERMITS

Review Stop Z ZONING
Rev No 1 Status P Date 1999-09-03 Cont ID  
Sent By gjoyce Date 1999-09-03 Time 11:43 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***