Plan Review Details - Permit 99090010
Plan Review Stops For Permit 99090010
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-04 Cont ID  
Sent By dpalmer Date 1999-10-04 Time 13:06 Rev Time 0.00
Received By dpalmer Date 1999-10-04 Time 13:06 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO*****************
  
 1)NOTE:SUBMIT AIC RATING FIGURED FROM
 FAULT CURRENT CALCULATIONS,ART;110-9/
 215-5
 2)NOTE:AS PER ART;250-81 GROUNDING
 ELECTRODE CONDUCTOR TO GOT TO BLDG.STEEL
 ALSO.
 3)NOTE:AS PER ART;210-8-A-6 ALL RECEPTS.
 SERVING KITCHEN COUNTER SPACE.
 4) NOTE;AS PER ART;210-52 NOTE 2`6`12
 RULE FOR OUTLET SPACING.
 5)NOTE;AS PER 1996 NFPA-72
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS IN NEW
 CONTRUCTION OF DWELLING UNITS.
 NEED TO HAVE THE ABOVE SUBMITTED AND
 APPROVED BEFORE ROUGH ELECTRICAL
 INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-07 Cont ID  
Sent By jleech Date 1999-09-07 Time 09:36 Rev Time 0.50
Received By jleech Date 1999-09-07 Time 09:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-11-18 Cont ID  
Sent By tlarge Date 1999-11-18 Time 20:37 Rev Time 0.50
Received By tlarge Date 1999-11-18 Time 20:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-09-11 Cont ID  
Sent By tlarge Date 1999-09-11 Time 06:27 Rev Time 0.50
Received By tlarge Date 1999-09-11 Time 06:27 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-06 Cont ID  
Sent By jcaloger Date 1999-10-12 Time 11:41 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-09-03 Cont ID  
Sent By gjoyce Date 1999-09-03 Time 11:35 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***