Plan Review Details - Permit 99081314
Plan Review Stops For Permit 99081314
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 1999-12-01 Cont ID  
Sent By fknapp Date 1999-12-01 Time 09:20 Rev Time 2.00
Received By fknapp Date 1999-12-01 Time 05:58 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE STORM PANEL INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC
 MOUNTING AND ANCHORS TO BE USED UNDER
 SEPERATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 1999-11-18 Cont ID  
Sent By fknapp Date 1999-11-18 Time 08:30 Rev Time 2.00
Received By fknapp Date 1999-11-18 Time 08:30 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR DOUBLE OUTSWING DOORS.
  
 2)PROVIDE STORM PANEL INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC
 MOUNTING AND ANCHORS TO BE USED.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE PINK RECIEPT ATTACHED TO
 THE PERMIT APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 1999-12-01 Cont ID  
Sent By fknapp Date 1999-10-05 Time 15:41 Rev Time 5.00
Received By fknapp Date 1999-10-05 Time 09:05 Sent To  
Notes
2001-01-08 00:00:00DENIED SEE CHECKLIST

Review Stop E ELECTRICAL
Rev No 3 Status P Date 1999-11-18 Cont ID  
Sent By jleahy Date 1999-11-18 Time 15:00 Rev Time 0.45
Received By dpalmer Date 1999-11-18 Time 14:59 Sent To  
Notes
2001-01-08 00:00:001- NEED TO KNOW HOW PANELS ARE FED
  
 2- HOW MANY CKTS TO CABANA
  
 3- WHERE ARE THE MAINS?

Review Stop E ELECTRICAL
Rev No 2 Status N Date 1999-12-01 Cont ID  
Sent By dpalmer Date 1999-11-03 Time 06:46 Rev Time 0.00
Received By dpalmer Date 1999-11-03 Time 06:46 Sent To  
Notes
2001-01-08 00:00:00************DENIED**********************
  
 1)NOTE:SERVICE ENTRANCE CONDUCTORS NEED
 TO BE SIZED FOR ATLEAST THE LOAD OF THE
 SERVICE!!!!!!
 2)NOTE:PLEASE REVISE LOAD CALCULATION
 COMBINING BOTH PANELS FOR SERVICE
 CALCULATION.
 3)NOTE:RISER ONLY SHOWS 4/0 WHICH IS
 RATED FOR 230 AMPS AND CAN BE PROTECTED
 AT 250A BUT THE LOAD EXCEEDS THAT RATING
 OF THE WIRE.AS PER 310-16!!!!!
 SIZE SERVICE ENTRANCE CONDUCTORS ACCORD.
 4)NOTE:PLANS SHOW 2 WATER HEATERS AND
 2 DRYERS???? PANEL SCHEDULES AND LOAD
 CALCULATIONS ONLY SHOW ONE OF EACH
 BEING FIGURED???? PLEASE VERIFY!!!
 5)NOTE: PLEASE ADD CIRCUT(S) ON PANEL
 SCHD.THAT ARE REQ`D BY 210-52D FOR BATHS
 6)NOTE:NEED TO HAVE GROUNDING ELECTRODE
 CONDUCTOR GOING TO STEEL OF NEW
 STRUCTURES.AS PER 250-81
 7)NOTE:AT DETACHED STRUCTURE BACK YARD,,
 IF FED BY MORE THAN ONE BRANCH CIRCUT
 THEN MUST MEET CODE AS TO PROPER GROUND-
 -ING. AS PER 250-24 C-3
 8)NOTE:ON PLANS,,,SHEET 5 OF 15 SHOW
 4 A/C COND. UNITS AND 9 OF 15 SHOW ONLY
 2 A/C COND. UNITS??? ALSO PLANS 3 AHU`S
 ??WHAT ARE THE CORRECT AMOUNT OF UNITS??
 9)NOTE:AS REQ`D BY ART;210-8-A-6 ALL
 OUTLETS SERVING KITCHEN COUNTERSPACE ARE
 TO BE GFI/GFI PROTECTED. PLEASE LABEL.
 10)NOTE:PLEASE NOTE SOME MISSING OUTLETS
 THAT ARE REQ`D BY 210-52
 11)NOTE:NEED TO SUBMIT THE AIC RATING OF
 EQUIPMENT MAINS AND BRKRS.AIC RATING IS
 IGURED FROM FAULT CURRENT CALCULATIONS.
 AS REQ`D BY 110-9/10 AND 215-5
 NOTE ALL THE ABOVE SERVICE INFORMATION
 REQ`D BY 215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORNATION
 REQ`STED FOR REVIEW AND APPROVAL!!
 ELEC WILL NOT PRINT

Review Stop E ELECTRICAL
Rev No 1 Status N Date 1999-12-01 Cont ID  
Sent By dpalmer Date 1999-10-05 Time 07:13 Rev Time 0.00
Received By jwitmer Date 1999-10-05 Time 07:13 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
  
 1)NOTE:AS PER ART210-8-A-6 ALL RECEPTS.
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED, TO INCLUDE KITCHEN
 AREA.
 2)NOTE;IF DETACHED CABANA HAS NORE THAN
 ONE CIRCUT TO THAT STUCTURE,THEN IT REQ`
 S A MEANS OF DISC. ST THAT STRUCTURE.
 3)AS PER 310-16 SERVICE ENTRANCE CONDS.
 ARE NOT OF SUFFICENT SIZE.LOAD CALCS.
 SHOW LOAD ON PANEL'A' AT 186.22 AND LOAD
 ON PANEL'B'AT 80.54 THATS 266.76 ON 4/0
 WIRE WHICH IS ONLY RATED FOR 230AMPS!!!
 SIZE CONDUCTORS AS PER 310-16 TO GUTTER
 TAPS MAY BE SIZED TO PANEL RATING.
 4)NOTE:AS PER ARTS;110-9/215-5 NEED TO
 SUBMIT AIC RATING OF ALL EQUIPMENT
 BEING USED TO INCLUDE AIC RATING OF
 MAINS,
 5)NOTE;SIZE GUTTER TO NEW SERVICE
 CONDUCTORS
 6)NOTE;SIZE GROUNDING ELECTRODE COND-
 -UCTOR TO NEW SERVICE ENTRANCE CONDUCTOR
 7)NOTE;AS PER ART 250-81,GROUNDING ELEC-
 -TRODE CONDUCTOR TO GOT TO TO BLDG.
 STEEL OF NEW ADDITIONS.
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 FOR APPROVAL.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-12-01 Cont ID  
Sent By jwitmer Date 1999-12-01 Time 13:11 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00JHL:PROVISO 11/13/99

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 1999-12-01 Cont ID  
Sent By jleech Date 1999-10-04 Time 15:27 Rev Time 0.35
Received By jwitmer Date 1999-10-04 Time 15:27 Sent To  
Notes
2001-01-08 00:00:00NO A/C PLANS.

Review Stop P PLUMBING
Rev No 5 Status P Date 1999-11-30 Cont ID  
Sent By tlarge Date 1999-11-30 Time 12:58 Rev Time 0.50
Received By tlarge Date 1999-11-30 Time 12:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status N Date 1999-12-01 Cont ID  
Sent By tlarge Date 1999-11-23 Time 15:29 Rev Time 0.33
Received By jwitmer Date 1999-11-23 Time 15:28 Sent To  
Notes
2001-01-08 00:00:00PLUMBING RISER SHALL MATCH FLOOR PLAN AS
 TO LOCATION OF FIXTURES.COUNTYWIDE
 AMENDMENTS TO STD.PLBG.CODE SEC.104.2.2
  
 FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC SEC.913.2.

Review Stop P PLUMBING
Rev No 3 Status N Date 1999-12-01 Cont ID  
Sent By tlarge Date 1999-11-05 Time 09:45 Rev Time 0.65
Received By jwitmer Date 1999-11-05 Time 09:45 Sent To  
Notes
2001-01-08 00:00:00PLUMBING RISER SHALL MATCH THE FLOOR
 PLAN AS TO LOCATION OF FIXTURES.
  
 FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED.SPC 913.2
  
 SIZE ALL SECTIONS OF THE PLUMBING RISER.
  
 TUB AND SHOWER ON 2ND FLR.NOT PROPERLY
 VENTED.SPC 901.2.

Review Stop P PLUMBING
Rev No 2 Status N Date 1999-12-01 Cont ID  
Sent By tlarge Date 1999-09-22 Time 07:50 Rev Time 1.00
Received By jwitmer Date 1999-09-22 Time 07:50 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SANITARY ISOMETRICS FOR PLBG.WORK
 TO BE DONE IN EACH STRUCTURE.SPC SEC.
 104.2.1.
  
 FIXTURES LOCATED DOWNSTREAM OF WATER
 CLOSETS SHALL BE VENTED PER SPC SEC.
 913.2
  
 WASHING MACHINE NOT PERMITTED ON 2"CROSS
 PER SPC SEC.409.12.3.
  
 VEGGIE SINK,BAR SINK,AND 2ND FLR.LAV.ARE
 SHOWN ON THE FLOOR PLAN BUT NOT ON THE
 SANITARY ISOMETRIC.SPC 104.2.1.
  
 SHOW FIXTURE CLEARANCES OF WATER CLOSETS
 COMPLY W/SPC SEC.403.4.
  
 WATER CLOSET AND SHOWER ARE NOT PROPERLY
 VENTED.COMPLY W/SPC SEC.901.2.(SEE TUB
 AND SHOWER ON 2ND.FLR.ALSO.)
  
 SANITARY ISOMETRIC SHALL CORRELATE W/
 THE FLOOR PLAN.SPC 104.2.1.
  
 DIMENSIONS REQD.FOR GARAGE SHOWER.COMPLY
 W/COUNTYWIDE AMENDMENTS SEC.409.8.2.1.

Review Stop P PLUMBING
Rev No 1 Status N Date 1999-12-01 Cont ID  
Sent By tlarge Date 1999-08-30 Time 07:43 Rev Time 0.00
Received By jwitmer Date 1999-12-01 Time 13:37 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SANITARY ISOMETRIC FOR ALL NEW
 PLUMBING BEING INSTALLED.SPC 104.2.1.
  
 SEPARATE PERMITS ARE REQUIRED FOR EACH
 STRUCTURE.104.1.1.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-01 Cont ID  
Sent By pschmitz Date 1999-10-02 Time 09:15 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW UNSAT
 (1) SHT 3 LABEL VEG. & BAR SINK ON PLAN
 DRAWING,ISOMETRIC DOES NOT MATCH.
 (2) WATER CLOSES NOT WET VENTED,
 MAJOR OVER A MINOR. (* TYPICAL)
 (3) VENT TUB & SHOWER.
 (4) GARAGE APT. KITCHEN SINK NOT SHOWN
 ON ISOMETRIC.
 (5) SIZE & LOCATION OF ALL WATER HEATERS
 STD PLBG. CODE 94 SEC 104.2.1
 SEE SHT A-3 END OF COMMENTS

Review Stop Z ZONING
Rev No 2 Status P Date 1999-11-17 Cont ID  
Sent By gjoyce Date 1999-11-17 Time 15:24 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 1999-08-31 Cont ID  
Sent By gjoyce Date 1999-08-31 Time 08:48 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00CONS SIGNED PERMIT OUT