Plan Review Details - Permit 99081085
Plan Review Stops For Permit 99081085
Review Stop P PLUMBING
Rev No 3 Status P Date 1999-12-01 Cont ID  
Sent By tlarge Date 1999-12-01 Time 11:24 Rev Time 0.30
Received By tlarge Date 1999-12-01 Time 11:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-11-30 Cont ID  
Sent By tlarge Date 1999-11-30 Time 08:20 Rev Time 0.50
Received By tlarge Date 1999-11-30 Time 08:20 Sent To  
Notes
2001-01-08 00:00:00SUBMIT PROPER EHD OF CSST TUBING AND
 COMPLY W/TABLE 305.4F OF SGC.
  
 A UNION SHALL BE INSTALLED DOWNSTREAM OF
 S.O.V.TO PERMIT REMOVAL OF CONTROLS PER
 NFPA 54 SEC.5.5.4.
  
 SIZE THE SUPPLY LINES TO THE RANGE,HOT
 TOP RANGE AND FRYER.COMPLY W/SGC.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-08-26 Cont ID  
Sent By tlarge Date 1999-08-26 Time 14:35 Rev Time 0.30
Received By tlarge Date 1999-08-26 Time 14:35 Sent To  
Notes
***NONE***