Plan Review Details - Permit 99080556
Plan Review Stops For Permit 99080556
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-08-31 Cont ID  
Sent By bstaples Date 1999-08-31 Time 07:50 Rev Time 0.50
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-09-01 Cont ID  
Sent By dpalmer Date 1999-09-01 Time 16:30 Rev Time 0.00
Received By dpalmer Date 1999-09-01 Time 16:30 Sent To  
Notes
2001-01-08 00:00:00************PROVISO*********************
  
 1)NOTE:NEW PANEL AND DISC. ARE SHOWN ON
 RISER DIAGRAM FOR 10TH FLOOR,,PLEASE
 GIVE MORE DETAIL OF DISC.ALSO NEED TO
 SUBMIT AIC RATINGS OF NEW PANEL AND
 DISC.AND BRKRS BEING USED. AS PER ARTS;
 110-9 AND 215-5
 2) NOTE:NEED LOAD CACULATIONS OF 9TH
 FLOOR DISTR.PANEL. TO INCLUDE ALL
 PANELS AND EQUIPMENT BEING SUPPLIED
 BY THAT DISTR. PANEL.ART;215-5
 3)NEED TO SUBMIT LOAD CALCULATIONS OF
 MAIN DISTR.CENTER AT FIRST LEVEL.
  
 ALL THE ABOVE NEEDS TO BE DONE,SUBMITTED
 AND APPROVED BEFORE FIRST ELECTRICAL
 INSPECTION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-08-31 Cont ID  
Sent By bstaples Date 1999-08-31 Time 07:51 Rev Time 0.50
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-01 Cont ID  
Sent By ndenmark Date 1999-09-01 Time 14:47 Rev Time 0.25
Received By ndenmark Date 1999-09-01 Time 14:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-08-28 Cont ID  
Sent By pschmitz Date 1999-08-28 Time 11:22 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***