2001-01-08 00:00:00 | CLEARLY SHOW ON PLANS THAT THE KITCHEN |
| SINK COMPLIES W/FACBC SEC.4.24.1.- |
| 4.24.7. |
| |
| A SERVICE SINK IS REQD.PER SPC TABLE 407 |
| FOOTNOTE #15. |
| |
| SHOWERS SHALL BE PROVIDED PER SPC TABLE |
| 407.(DORMITORIES)AND SHALL BE HANDICAP |
| ACCESSIBLE PER FACBC SEC.4.21. |
| |
| CLEARLY SHOW ON PLANS THAT FLOORS AND |
| WALLS IN COMMON AREA BATHROOMS AND |
| TOILET ROOM COMPLY W/STD.BLDG.CODE SEC. |
| 1204.2. |
| |
| FIXTURE REQS.SHALL BE BASED ON 50 SQ.FT. |
| PER PERSON (SLEEPING AREA ONLY) PER SPC |
| TABLE 407.(SEE DORMITORIES). |
| |
| PLANS SHOW WATER CLOSETS INFRINGING ON |
| WHEELCHAIR TURNING SPACE IN TOILET/BATH |
| ROOMS.COMPLY W/FACBC SEC.4.2.3. |
| |
| SEPARATE FULLY ACCESSIBLE TOILET/BATH |
| FACILITIES SHALL BE PROVIDED FOR MALES |
| & FEMALES (COMMON AREA FACILITIES) PER |
| FACBC SEC.4.1.3.(11), 4.22, 9.2(E). |
| |
| AN APPROVED BFP DEVICE IS REQD.ON THE |
| MAKE-UP WATER LINE TO THE COOLING TOWER. |
| SPC SEC.606.1. |
| |
| A GREASE INTERCEPTOR IS REQD.PER SPC |
| SEC.1004.1, 1004.2, 1004.4.CONTACT ROD |
| COMPO AT CITY OF W.P.B. REGIONAL WASTE- |
| WATER TREATMENT PLANT FOR SIZE REQS. |
| (561) 835-7423. |
| |
| SHT.P-8-WATER HEATER PAN DAIN AND RELIEF |
| LINE SHALL NOT BE COMBINED PER COUNTY- |
| WIDE AMENDMENTS TO STD.PLBG.CODE SECS.. |
| 507.8.3, 507.8.4. |
| |
| OCCUPANCY SHALL BE DETERMINED BY THE |
| BUILDING OFFICIAL PER SBC SEC.301.3. |
| AND THE BUILDING OFFICIAL SHALL RENDER |
| INTERPRETATIONS PER SBC SEC.103.1(RE: |
| IS OCCUPANCY A DWELLING OR DORMITORY?) |
| |
| ALL ADDENDUMS TO PLANS SHALL BE ATTACHED |
| TO THE PLANS |