Plan Review Details - Permit 99080039
Plan Review Stops For Permit 99080039
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-01-05 Cont ID  
Sent By lmartine Date 2000-01-05 Time 16:06 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-09-08 Cont ID  
Sent By hpiskura Date 1999-09-08 Time 15:55 Rev Time 9.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-05 Cont ID  
Sent By dlauderm Date 1999-11-10 Time 10:54 Rev Time 0.50
Received By lmartine Date 1999-11-10 Time 10:54 Sent To  
Notes
2001-01-08 00:00:00FAILED FOR WATER AND SANITARY REVIEW,
 DSL, 11-10-99. WATER:THE PLAN SHOWS
 A TIE-IN TO THE FIRE LINE FOR A
 SEPARATE PROPERTY OWNER AND A DOMESTIC
 WATER LINE RUN ACROSS PRIVATE PROPERTY
 WITHOUT AN EASEMENT SHOWN.A DEP
 PERMIT IS REQUIRED FOR THE WATER
 SYSTEM, SUBMIT PLANS ACCORDANTLY TO
 THE PUBLIC UTILITIES DEPARTMENT.
 SANITARY: THE GRAVITY SYSTEM IS SHOWN
 BEING TIED TO A PRIVATE GRAVITY SYSTEM
 THAT IS SERVED BY A PRIVATE LIFT
 STATION.A DEP PERMIT IS REQUIRED FOR
 A SEPARATE GRAVITY SEWER SYSTEM WITH
 IT'S OWN PRIVATE LIFT STATION, SUBMIT
 PLANS ACCORDANTLY TO THE PUBLIC
 UTILITIES DEPARTMENT.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2000-01-05 Cont ID  
Sent By lmartine Date 2000-01-05 Time 16:05 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-01-05 Cont ID  
Sent By lmartine Date 2000-01-05 Time 16:05 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-11-01 Cont ID  
Sent By ndenmark Date 1999-11-01 Time 07:20 Rev Time 0.33
Received By ndenmark Date 1999-11-01 Time 07:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-01 Cont ID  
Sent By ndenmark Date 1999-08-30 Time 12:40 Rev Time 0.50
Received By ndenmark Date 1999-08-30 Time 12:40 Sent To  
Notes
2001-01-08 00:00:00NOTES CORRECTED ON REVISION
 1)PROVIDE BACKDRAFT DAMPERS AT EACH
 EXHAUST FAN RUNOUT TO PREVENT CARRYOVER
 INTO ROOMS WITHOUT CEILING MOUNTED EXHAU
 ST FANS FROM ROOMS WITH CEILING MOUNTED
 EXHAUST FANS WHEN ROOF MOUNTED EXHAUST
 FANS ARE NOT RUNNING 1997 SMC 501.4
 2) IF HP-F IS USING ABOVE CEILING FOR
 RETURN AIR PLENUM, AIR ADMITTANCE VALVES
 'SHALL NOT BE USED IN SAME SPACE. SMC
 609.1.3
 3)ANY A/C UNITS SERVING AREA USED FOR
 EGRESS SHALL BE SHUT DOWN BY DUCT SMOKE
 DETECTOR 1997 SMC 406.2
 4)EVERY ATTIC IN WHICH MECHANICAL EQUIP-
 MENT IS INSTALLED SHALL BE ACCESSIBLE BY
 AN OPENING AS LARGE AS THE LARGEST PIECE
 OF EQUIPMENT BUT IN NO CASE LESS THAN
 22X36 INCHES. 1997 SMC 304.4.1

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-10-25 Cont ID  
Sent By tlarge Date 1999-10-25 Time 15:12 Rev Time 2.75
Received By tlarge Date 1999-10-25 Time 15:12 Sent To  
Notes
2001-01-08 00:00:00CLEARLY SHOW ON PLANS THAT THE KITCHEN
 SINK COMPLIES W/FACBC SEC.4.24.1.-
 4.24.7.
  
 A SERVICE SINK IS REQD.PER SPC TABLE 407
 FOOTNOTE #15.
  
 SHOWERS SHALL BE PROVIDED PER SPC TABLE
 407.(DORMITORIES)AND SHALL BE HANDICAP
 ACCESSIBLE PER FACBC SEC.4.21.
  
 CLEARLY SHOW ON PLANS THAT FLOORS AND
 WALLS IN COMMON AREA BATHROOMS AND
 TOILET ROOM COMPLY W/STD.BLDG.CODE SEC.
 1204.2.
  
 FIXTURE REQS.SHALL BE BASED ON 50 SQ.FT.
 PER PERSON (SLEEPING AREA ONLY) PER SPC
 TABLE 407.(SEE DORMITORIES).
  
 PLANS SHOW WATER CLOSETS INFRINGING ON
 WHEELCHAIR TURNING SPACE IN TOILET/BATH
 ROOMS.COMPLY W/FACBC SEC.4.2.3.
  
 SEPARATE FULLY ACCESSIBLE TOILET/BATH
 FACILITIES SHALL BE PROVIDED FOR MALES
 & FEMALES (COMMON AREA FACILITIES) PER
 FACBC SEC.4.1.3.(11), 4.22, 9.2(E).
  
 AN APPROVED BFP DEVICE IS REQD.ON THE
 MAKE-UP WATER LINE TO THE COOLING TOWER.
 SPC SEC.606.1.
  
 A GREASE INTERCEPTOR IS REQD.PER SPC
 SEC.1004.1, 1004.2, 1004.4.CONTACT ROD
 COMPO AT CITY OF W.P.B. REGIONAL WASTE-
 WATER TREATMENT PLANT FOR SIZE REQS.
 (561) 835-7423.
  
 SHT.P-8-WATER HEATER PAN DAIN AND RELIEF
 LINE SHALL NOT BE COMBINED PER COUNTY-
 WIDE AMENDMENTS TO STD.PLBG.CODE SECS..
 507.8.3, 507.8.4.
  
 OCCUPANCY SHALL BE DETERMINED BY THE
 BUILDING OFFICIAL PER SBC SEC.301.3.
 AND THE BUILDING OFFICIAL SHALL RENDER
 INTERPRETATIONS PER SBC SEC.103.1(RE:
 IS OCCUPANCY A DWELLING OR DORMITORY?)
  
 ALL ADDENDUMS TO PLANS SHALL BE ATTACHED
 TO THE PLANS

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-08-28 Cont ID  
Sent By tlarge Date 1999-08-28 Time   Rev Time 2.75
Received By tlarge Date 1999-08-28 Time 08:48 Sent To  
Notes
2001-01-08 00:00:00LAUNDRY ROOM SHALL COMPLY W/F.A.C.B.C.
 SEC.9.5.1.
  
 KITCHEN AREA SHALL COMPLY W/F.A.C.B.C.
 SEC.4.24.1-4.24.7.,9.22(7).
  
 WALLS AND FLOORS OF COMMON AREA TOILET
 ROOMS SHALL COMPLY W/SBC SEC.1204.2.
  
 A SERVICE SINK IS REQD.PER TABLE 407
 FOOTNOTE # 15 OF SPC.
  
 TOILET ROOMS SHALL BE ACCESSIBLE PER
 F.A.C.B.C.SEC.4.1.3.(11),4.22.(SEPARATE
 FULLY ACCESSIBLE TOILET FACILITIES SHALL
 BE PROVIDED FOR MALES & FEMALES).TABLE
 407(DORMITORIES)OF SPC.
  
 CLEARLY SHOW WHEELCHAIR TURNING SPACE
 IN ACCESSIBLE TOILET ROOMS PER F.A.C.B.C
 SEC.4.2.3.
  
 AN APPROVED BFP DEVICE IS REQD.ON THE
 MAKEUP WATER LINE TO THE COOLING TOWER.
 SPC 606.1
  
 A SHOWER SHALL BE PROVIDED PER SPC SEC.
 TABLE 407(DORMITORIES) AND SHALL BE
 HANDICAP ACCESSIBLE PER F.A.C.B.C.SEC.
 4.21.

Review Stop Z ZONING
Rev No 1 Status F Date 1999-08-09 Cont ID  
Sent By gjoyce Date 1999-08-09 Time 15:13 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***