Plan Review Details - Permit 99080038
Plan Review Stops For Permit 99080038
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-01-05 Cont ID  
Sent By lmartine Date 2000-01-05 Time 15:54 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-09-08 Cont ID  
Sent By hpiskura Date 1999-09-08 Time 16:03 Rev Time 9.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-01-04 Cont ID  
Sent By dlauderm Date 1999-11-10 Time 10:51 Rev Time 0.50
Received By lmartine Date 1999-11-10 Time 10:45 Sent To  
Notes
2001-01-08 00:00:00FAILED FOR WATER AND SANITARY REVIEW,
 DSL, 11-10-99. WATER:THE PLAN SHOWS
 A TIE-IN TO THE FIRE LINE FOR A
 SEPARATE PROPERTY OWNER AND A DOMESTIC
 WATER LINE RUN ACROSS PRIVATE PROPERTY
 WITHOUT AN EASEMENT SHOWN.A DEP
 PERMIT IS REQUIRED FOR THE WATER
 SYSTEM, SUBMIT PLANS ACCORDANTLY TO
 THE PUBLIC UTILITIES DEPARTMENT.
 SANITARY: THE GRAVITY SYSTEM IS SHOWN
 BEING TIED TO A PRIVATE GRAVITY SYSTEM
 THAT IS SERVED BY A PRIVATE LIFT
 STATION.A DEP PERMIT IS REQUIRED FOR
 A SEPARATE GRAVITY SEWER SYSTEM WITH
 IT'S OWN PRIVATE LIFT STATION, SUBMIT
 PLANS ACCORDANTLY TO THE PUBLIC
 UTILITIES DEPARTMENT.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 1999-11-10 Cont ID  
Sent By lmartine Date 1999-11-10 Time 13:30 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-08-25 Cont ID  
Sent By lmartine Date 1999-08-25 Time 13:31 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 1999-08-30 Cont ID  
Sent By ndenmark Date 1999-08-30 Time 10:51 Rev Time 0.50
Received By ndenmark Date 1999-08-30 Time 10:51 Sent To  
Notes
2001-01-08 00:00:00DENIED
 1) PROVIDE BACKDRAFT DAMPERS AT EACH
 EXHAUST FAN RUNOUT TO PREVENT CARRYOVER
 INTO ROOMS WITHOUT CEILING MOUNTED EXHAU
 ST FANS FROM ROOMS WITH CEILING MOUNTED
 EXHAUST FANS WHEN ROOF MOUNTED EXHAUST
 FANS ARE NOT RUNNING 1997 SMC 501.4
 2) IF HP-F IS USING ABOVE CEILING FOR
 RETURN AIR PLENUM, AIR ADMITTANCE VALVES
 SHALL NOT BE USED IN SAME SPACE
 3) ANY A/C UNITS SERVING AREA USED FOR
 EGRESS SHALL BE SHUT DOWN BY DUCT SMOKE
 DETECTOR 1997 SMC 406.2
 4) EVERY ATTIC IN WHICH MECHANICAL EQUIP
 MENT IS INSTALLED SHALL BE ACCESSIBLE BY
 AN OPENING AS LARGE AS THE LARGEST PIECE
 OF EQUIPMENT BUT IN NO CASE LESS THAN
 22X36 INCHES.

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-10-25 Cont ID  
Sent By tlarge Date 1999-10-25 Time 11:10 Rev Time 2.75
Received By tlarge Date 1999-10-25 Time 11:09 Sent To  
Notes
2001-01-08 00:00:00CLEARLY SHOW ON PLANS THAT KITCHEN SINK
 COMPLIES W/FACBC SEC.4.24.1- 4.24.7.
  
 A SERVICE SINK IS REQD.PER SPC TABLE 407
 FOOTNOTE #15.
  
 SHOWERS SHALL BE PROVIDED PER SPC TABLE
 407 (DORMITORIES) AND SHALL BE HANDICAP
 ACCESSIBLE PER FACBC SEC.4.21.
  
 CLEARLY SHOW WALLS AND FLOORS IN COMMON
 AREA BATHROOMS AND TOILET ROOM COMPLY W/
 STD.BLDG.CODE SEC.1204.2.
  
 FIXTURE REQS.SHALL BE BASED ON 50 SQ.FT.
 PER PERSON (SLEEPING AREA ONLY)PER
 TABLE 407 OF SPC.
  
 PLANS SHOW WATER CLOSETS INFRINGING ON
 WHEELCHAIR TURNING SPACE IN TOILET/BATH
 ROOMS.COMPLY W/FACBC SEC.4.2.3.
  
 SEPARATE FULLY ACCESSIBLE TOILET/BATH
 FACILITIES SHALL BE PROVIDED FOR MALES
 & FEMALES(COMMON AREA FACILITIES) PER
 FACBC SEC.4.1.3(11), 4.22, 9.2(E).
  
 AN APPROVED BFP DEVICE IS REQD.ON THE
 MAKE-UP WATER LINE TO THE COOLING TOWER.
 SPC SEC.606.1.
  
 A GREASE INTERCEPTOR IS REQD.PER SPC
 SEC.1004.1,1004.2,1004.4.CONTACT RODNEY
 COMPO AT CITY OF W.P.B. REGIONAL WASTE-
 WATER TREATMENT PLANT FOR SIZE REQS.
 (561)835-7423.
  
 SHT.P-8-WATER HEATER DRAIN PAN AND
 RELIEF LINE SHALL NOT BE COMBINED PER
 COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE
 SECS.507.8.3, 507.8.4.
  
 OCCUPANCY SHALL BE DETERMINED BY THE
 BUILDING OFFICIAL PER SBC SEC.301.3 AND
 THE BUILDING OFFICIAL SHALL RENDER
 INTERPRETATIONS PER SBC SEC.103.1(RE:
 IS OCCUPANCY TO BE CLASSED AS A DWELLING
 OR A DORMITORY?)
  
 ALL SUBMITTED ADDENDUMS SHALL BE
 ATTACHED TO THE PLANS.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-08-27 Cont ID  
Sent By tlarge Date 1999-08-27 Time 17:54 Rev Time 3.00
Received By tlarge Date 1999-08-27 Time 17:54 Sent To  
Notes
2001-01-08 00:00:00LAUNDRY ROOM SHALL COMPLY W/F.A.C.B.C.
 SEC.9.5.1.
  
 KITCHEN AREA SHALL COMPLY W/F.A.C.B.C.
 SECS.4.24.1- 4.24.7, 9.22(7).
  
 WALLS AND FLOORS OF TOILET ROOMS SHALL
 COMPLY W/SBC SEC.1204.2.
  
 A SERVICE SINK IS REQ'D.PER TABLE 407 OF
 SPC,FOOTNOTE # 15.
  
 TOILET ROOMS SHALL BE ACCESSIBLE PER
 F.A.C.B.C.SEC.4.1.3(11).4.22.(SEPARATE
 FULLY ACCESSIBLE TOILET FACILITIES SHALL
 BE PROVIDED FOR MALES & FEMALES.)SEE
 TABLE 407(DORMITORIES) FOR FIXTURE REQS.
  
 CLEARLY SHOW WHEELCHAIR TURNING SPACE
 IN ACCESSIBLE TOILET ROOMS PER F.A.C.B.C
 SEC.4.2.3.
  
 AN APPROVED BFP DEVICE IS REQD.ON THE
 MAKEUP WATER LINE TO THE COOLING TOWER.
 SPC 606.1 .
  
 A SHOWER SHALL BE PROVIDED PER SPC TABLE
 407(DORMITORIES) AND SHALL BE HANDICAP
 ACCESSIBLE PER F.A.C.B.C. SEC.4.21.

Review Stop Z ZONING
Rev No 1 Status F Date 1999-08-09 Cont ID  
Sent By gjoyce Date 1999-08-09 Time 15:13 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***