2001-01-08 00:00:00 | CLEARLY SHOW ON PLANS THAT KITCHEN SINK |
| COMPLIES W/FACBC SEC.4.24.1- 4.24.7. |
| |
| A SERVICE SINK IS REQD.PER SPC TABLE 407 |
| FOOTNOTE #15. |
| |
| SHOWERS SHALL BE PROVIDED PER SPC TABLE |
| 407 (DORMITORIES) AND SHALL BE HANDICAP |
| ACCESSIBLE PER FACBC SEC.4.21. |
| |
| CLEARLY SHOW WALLS AND FLOORS IN COMMON |
| AREA BATHROOMS AND TOILET ROOM COMPLY W/ |
| STD.BLDG.CODE SEC.1204.2. |
| |
| FIXTURE REQS.SHALL BE BASED ON 50 SQ.FT. |
| PER PERSON (SLEEPING AREA ONLY)PER |
| TABLE 407 OF SPC. |
| |
| PLANS SHOW WATER CLOSETS INFRINGING ON |
| WHEELCHAIR TURNING SPACE IN TOILET/BATH |
| ROOMS.COMPLY W/FACBC SEC.4.2.3. |
| |
| SEPARATE FULLY ACCESSIBLE TOILET/BATH |
| FACILITIES SHALL BE PROVIDED FOR MALES |
| & FEMALES(COMMON AREA FACILITIES) PER |
| FACBC SEC.4.1.3(11), 4.22, 9.2(E). |
| |
| AN APPROVED BFP DEVICE IS REQD.ON THE |
| MAKE-UP WATER LINE TO THE COOLING TOWER. |
| SPC SEC.606.1. |
| |
| A GREASE INTERCEPTOR IS REQD.PER SPC |
| SEC.1004.1,1004.2,1004.4.CONTACT RODNEY |
| COMPO AT CITY OF W.P.B. REGIONAL WASTE- |
| WATER TREATMENT PLANT FOR SIZE REQS. |
| (561)835-7423. |
| |
| SHT.P-8-WATER HEATER DRAIN PAN AND |
| RELIEF LINE SHALL NOT BE COMBINED PER |
| COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE |
| SECS.507.8.3, 507.8.4. |
| |
| OCCUPANCY SHALL BE DETERMINED BY THE |
| BUILDING OFFICIAL PER SBC SEC.301.3 AND |
| THE BUILDING OFFICIAL SHALL RENDER |
| INTERPRETATIONS PER SBC SEC.103.1(RE: |
| IS OCCUPANCY TO BE CLASSED AS A DWELLING |
| OR A DORMITORY?) |
| |
| ALL SUBMITTED ADDENDUMS SHALL BE |
| ATTACHED TO THE PLANS. |