Plan Review Details - Permit 99080036
Plan Review Stops For Permit 99080036
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-04-16 Cont ID  
Sent By jwitmer Date 2001-04-16 Time 10:06 Rev Time 0.55
Received By jwitmer Date   Time   Sent To  
Notes
2001-04-16 00:00:00RAILING DETAIL ENGINEER CALC'S

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2000-12-18 Cont ID  
Sent By jwitmer Date 2000-12-18 Time 15:18 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISION:10/17/2000
 SHEET A-1 DOOR SCH. REVISIONS OK
 SHEET A-3 CHANGE OF ROOF
 1). 1707.5 CONCRETE & CLAY ROOF TILE
 PROOF OF OVERTURNING RESISTANCE.
 A SBCCI OR DADE COUNTY PRODUCT
 APPROVAL REPORT(CURRENT).
 2).MECHANICAL EQUIPMENT CURB : DETAILS
 FOR STRAPPING WERE NOT GIVEN.
  
 JIM WITMER BUILD. PLAN REVIEW
 (561) 659-8096 EX.8412
 THANK YOU!

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-01-24 Cont ID  
Sent By hpiskura Date 2000-01-24 Time 10:48 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO:CONTRACTOR MUST SUBMIT TEST
 DATA - PRODUCT APPROVAL FOR DOORS,
 WINDOWS AND ROOF COVERING, BEFORE
 CONSTRUCTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-01-06 Cont ID  
Sent By lmartine Date 2000-01-06 Time 13:16 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-09-09 Cont ID  
Sent By hpiskura Date 1999-09-09 Time 13:58 Rev Time 6.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-12-13 Cont ID  
Sent By dpalmer Date 2000-12-13 Time 22:51 Rev Time 0.00
Received By dpalmer Date 2000-12-13 Time 22:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-02-12 Cont ID  
Sent By dpalmer Date 2000-02-12 Time 20:59 Rev Time 0.00
Received By dpalmer Date 2000-02-12 Time 20:57 Sent To  
Notes
2001-01-08 00:00:00***************** OK *******************
  
 1)NOTE: NEW REVISED PLANS FOR E-4
 PLANS WERE OK`D BY J.LEAHY

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-01-24 Cont ID  
Sent By hpiskura Date 2000-01-24 Time 09:02 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00JAKE OK ON PLANS

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-02-11 Cont ID  
Sent By dlauderm Date 1999-11-10 Time 10:57 Rev Time 0.50
Received By dlauderm Date 1999-11-10 Time 10:56 Sent To  
Notes
2001-01-08 00:00:00FAILED FOR WATER AND SANITARY REVIEW,
 DSL, 11-10-99. WATER:THE PLAN SHOWS
 A TIE-IN TO THE FIRE LINE FOR A
 SEPARATE PROPERTY OWNER AND A DOMESTIC
 WATER LINE RUN ACROSS PRIVATE PROPERTY
 WITHOUT AN EASEMENT SHOWN.A DEP
 PERMIT IS REQUIRED FOR THE WATER
 SYSTEM, SUBMIT PLANS ACCORDANTLY TO
 THE PUBLIC UTILITIES DEPARTMENT.
 SANITARY: THE GRAVITY SYSTEM IS SHOWN
 BEING TIED TO A PRIVATE GRAVITY SYSTEM
 THAT IS SERVED BY A PRIVATE LIFT
 STATION.A DEP PERMIT IS REQUIRED FOR
 A SEPARATE GRAVITY SEWER SYSTEM WITH
 IT'S OWN PRIVATE LIFT STATION, SUBMIT
 PLANS ACCORDANTLY TO THE PUBLIC
 UTILITIES DEPARTMENT.
  
 THIS REVIEW WAS CHANGED TO PASSED WITH
 PROVISOS, SEE ENG #2 REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2001-03-15 Cont ID  
Sent By mamini Date 2001-03-15 Time 13:08 Rev Time 2.00
Received By mamini Date 2001-03-15 Time 13:07 Sent To  
Notes
2001-03-15 00:00:00PASSED:
 1.REVISION AS SUBMITTED FOR CONSTRUCTION
 OF RAMP TO THE NEW PARKING AND BUILDING
 IS APPROVED.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2000-12-12 Cont ID  
Sent By mgonzale Date 2000-12-12 Time 07:48 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED
 NEW FIRE HYDRANT REVISION ACKNOWLEDGED
 PLEASE PROVIDE AS-BUILTS WHEN JOB IS
 COMPLETED TO
 MANUEL GONZALEZ
 1000 45H STREET SUITE 15
 WPB FL 33407
 561 659 8040 EXT 2306
 2 MYLER COPIES WILL ALSO BE REQUIRED.
 THANK YOU.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-02-11 Cont ID  
Sent By dlauderm Date 2000-02-11 Time 11:47 Rev Time 1.00
Received By dlauderm Date 2000-02-11 Time 11:46 Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISOS:
  
 1. STORMWATER CALCULATIONS ARE STILL
 REQUIRED, SUPPLY PRIOR TO START OF
 CONSTRUCTION. USE THE FOLLOWING AS A
 GUIDE LINE:
 BUILDING AREA
 +PAVED AREA
 TOTAL IMPERVIOUS AREA
 +TOTAL GREEN AREA
 TOTAL SITE AREA
 TOTAL IMPERVIOUS AREA (IN SF):
 DIVIDED BY 1,573 SF (1 ERU EQUALS THE
 ERU'S TO BE CHARGED
 TOTAL IMPERVIOUS AREA NEEDS TO BE IN
 ERU'S.
 43,560 SQUARE FEET IN AN ACRE
 1,573SQUARE FEET 1 ERU
 27.692308 ERU'S PER ACRE.
 ERU (EQUIVALENT RESIDENTIAL UNIT)IS AN
 INPURMEATABLE SURFACES, SUCH AS ROOFS,
 SIDEWALKS, PARKING LOTS.
  
  
 2. PLANS ARE STILL WRONG ON WATER
 SERVICE.IT MUST BE A TAPPING VALVE AND
 SLEEVE, 4" WATER SERVICE WITH BYPASS, 3"
 METER THEN THE REDUCED PRESSURE
 PRINCIPLE BACKFLOW PREVENTERS.THE
 DRAWING DOES NOT STATE IT BUT IT IS
 SUGGESTED THAT TWO DEVICES BE INSTALLED
 IN PARALLEL SO THE BUILDINGS ARE NEVER
 WITHOUT SERVICE.
  
 3. SHEET SP-1 DOES NOT SHOW THE OPENING
 BETWEEN THE DUMPSTER GATES.THE OPENING
 BETWEEN THE GATES MUST BE 12' - 6".

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-02-11 Cont ID  
Sent By lmartine Date 1999-11-10 Time 11:16 Rev Time 0.00
Received By dlauderm Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE DEANS NOTES UNDER ELECTRIC.REVIEW
 WAS CHANGED TO PASSED WITH PROVISOS, SEE
 ENG #2 REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-11-27 Cont ID  
Sent By mcarsill Date 2000-11-27 Time 09:04 Rev Time 0.00
Received By mcarsill Date 2000-11-27 Time 09:04 Sent To  
Notes
2001-01-08 00:00:001) THE NEW ENTRY DRIVE IS TO BE AT LEAST
 20 FEET IN CLEAR WIDTH.
 2) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 3) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT
 SHOWN ON PLANS. CUT SHEETS, WIRING
 DIAGRAM AND FLOOR PLANS ARE TO BE
 SUBMITTED.
  
 ON NOVEMBER 27,2000, WRITER SPOKE TO
 KEVIN NORTH OF THE WEITZ COMPANY.
 PER MR. NORTH, THE BUILDING WILL BE
 COMPLETELY FIRE SPRINKLER PROTECTED AND
 THE FP PLANS WERE PREVIOUSLY SUBMITTED
 TO THE CITY. MR. NORTH WAS ADVISED THAT
 THE FIRE SPRINKLER SYSTEM CONNECTION IS
 TO BE WITHIN 150 FEET OF THE FIRE
 HYDRANT. PLANS WERE PREVIOUSLY APPROVED
 BY FIRE RESCUE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-08-25 Cont ID  
Sent By lmartine Date 1999-08-25 Time 11:17 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-12-14 Cont ID  
Sent By ndenmark Date 2000-12-14 Time 12:14 Rev Time 0.50
Received By ndenmark Date 2000-12-14 Time 12:14 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 CONDENSATE DRAIN TO TERMINATE IN A PERM-
 IABLE LOCATION OR TO STORM DRAIN.
 OVERFLOW PROTECTION REQUIRED FOR AHU PER
 1997 SMC 304.8.6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-17 Cont ID  
Sent By ndenmark Date 1999-08-30 Time 13:57 Rev Time 0.50
Received By ndenmark Date 1999-08-30 Time 13:57 Sent To  
Notes
2001-01-08 00:00:00APPROVED 11/17/99 NCD
 1)AIR ADMITTANCE VALVES NOT PERMITTED IN
 RETURN AIR PLENUM AREA PER 1997 SMC 609.
 1.3
 2)ANY A/C UNITS SERVING AREA USED FOR
 EGRESS SHALL BE SHUT DOWN BY DUCT SMOKE
 DETECTOR 1997 SMC 406.2
 3) EVERY ATTIC IN WHICH MECHANICAL EQUIP
 MENT IS INSTALLED SHALL BE ACCESSIBLE BY
 AN OPENING AS LARGE AS THE LARGEST PIECE
 OF EQUIPMENT BUT IN NO CASE LESS THAN
 22X36 INCHES 1997 SMC 304.4.1
 4)PROVIDE BACKDRAFT DAMPER AT EACH
 EXHAUST AIR OPENING NOT EQUIPPED WITH
 CEILING MOUNTED EXHAUST FAN WITH DAMPER
 TO PREVENT CARRYOVER INTO ROOM IF ROOF
 MOUNTED EXHAUST FAN IS NOT RUNNING SMC
 501.4

Review Stop P PLUMBING
Rev No 6 Status P Date 2000-12-04 Cont ID  
Sent By jleech Date 2000-12-04 Time 11:40 Rev Time 1.50
Received By jleech Date 2000-12-04 Time 11:40 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
  
 CONDENSATE DRAINS TO BE ROUTED PER NOTE
 # 4. SUBMIT NEW DRAWINGS SHOWING NEW
 L0CATIONS OF CONDENSATE DRAINS, BEFORE
 ROUGH A/C INSPECTION.

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-02-22 Cont ID  
Sent By tlarge Date 2000-02-22 Time 12:36 Rev Time 1.50
Received By tlarge Date 2000-02-22 Time 12:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status N Date 2000-02-22 Cont ID  
Sent By tlarge Date 2000-02-21 Time 09:05 Rev Time 2.25
Received By tlarge Date 2000-02-21 Time 08:09 Sent To  
Notes
2001-01-08 00:00:00SHOWERS SHALL BE PROVIDED PER SPC TABLE
 407.(SEE REQS.FOR DORMITORIES.)
  
 CLEARLY SHOW ON PLANS THAT FLOORS AND
 WALLS IN COMMON AREA BATHROOMS AND
 TOILET ROOMS COMPLY W/SBC SEC.1204.2.
  
 SIZE REQUIREMENT AND DESIGN OF GREASE
 TRAP SHALL COMPLY W/HEALTH DEPT.REQS.
 AND CITY OF WEST PALM BEACH UTILITIES.
 CONTACT RODNEY COMPO AT CITY OF WPB
 REGIONAL WASTEWATER TREATMENT FACILITY.
 SEEFLA.ADMIN.CODE SEC.64E-6.013(5)(A).
  
 CLEARLY SHOW ON PLAN THAT GREASE TRAP
 WILL NOT BE LOCATED WITHIN ANGLE OF
 REPOSE.
  
 MINIMUM INLET AND OUTLET TO GREASE TRAP
 SHALL BE 4" AND INLET SHALL DISCHARGE A
 MIN.OF 2 1/2" ABOVE LIQUID LEVEL LINE.

Review Stop P PLUMBING
Rev No 3 Status N Date 2000-02-22 Cont ID  
Sent By tlarge Date 2000-01-27 Time 15:04 Rev Time 5.50
Received By tlarge Date 2000-01-27 Time 15:04 Sent To  
Notes
2001-01-08 00:00:00CLEARLY SHOW ON THE PLANS THAT THE
 KITCHEN SINK COMPLIES W/FACBC SEC.4.24.1
 THRU 4.24.7.(IF THIS AREA IS A
 DESIGNATED WORK AREA AND NOT TO BE
 UTILIZED BY THE GUESTSFOR COOKING OR
 WARMING FOOD IT IS NOT REQD.TO BE FULLY
 ACCESSIBLE.CLARIFY ON THE PLANS.
  
 SHOWERS SHALL BE PROVIDED PER SPC TABLE
 407(DORMITORIES).
  
 CLEARLY SHOW ON THE PLANS THAT FLOORS
 AND WALLS IN COMMON AREA BATHROOMS AND
 TOILET ROOMS COMPLY W/SBC SEC.1204.2
  
 SIZE REQS.AND DESIGN OF GREASE TRAP
 SHALL COMPLY W/HEALTH DEPT.REQS.AND
 CITY OF WPB UTILITIES.CONTACT RODNEY
 COMPO AT CITY OF WPB REGIONAL WASTEWATER
 TREATMENT FACILITY.(561)835-7423.
  
 DISHWASHER SHALL DRAIN TO SANITARY,NOT
 TO GREASE PER WPB UTILITIES.
  
 SIZE OF DRYWELL SHALL COMPLY W/SMC SEC.
 304.8.5.
  
 LOCATION OF GREASE TRAP SHALL NOT BE
 WITHIN ANGLE OF REPOSE.SBC 1803.1.3.

Review Stop P PLUMBING
Rev No 2 Status N Date 2000-02-22 Cont ID  
Sent By tlarge Date 1999-10-26 Time 10:37 Rev Time 3.50
Received By tlarge Date 1999-10-26 Time 10:37 Sent To  
Notes
2001-01-08 00:00:00THE OCCUPANCY OF THE STRUCTURE SHALL BE
 DETERMINED BY THE BUILDING OFFICIAL PER
 SBC SEC.301.3 AND THE BUILDING OFFICIAL
 SHALL RENDER INTERPRETATIONS PER SBC
 SEC.103.1.(RE:IS OCCUPANCY TO BE CLASSED
 AS A DWELLING OR A DORMITORY.?)
  
 CLEARLY SHOW ON THE PLANS THAT THE
 KITCHEN SINK COMPLIES W/FACBC SEC.4.24.1
 THRU 4.24.7.
  
 SHOWERS SHALL BE PROVIDED PER SPC TABLE
 407(DORMITORIES) AND SHALL BE HANDICAP
 ACCESSIBLE PER SBC 4.21.
  
 CLEARLY SHOW ON THE PLANS THAT FLOORS
 AND WALLS IN COMMON AREA BATHROOMS AND
 TOILET ROOMS COMPLY W/SBC SEC.1204.2
  
 FIXTURE REQS.SHALL BE BASED ON 50 SQ.FT.
 PER PERSON (SLEEPING AREA ONLY) PER
 TABLE 407 OF SPC.
  
 SHT.M-5-AN APPROVED BACKFLOW PREVENTION
 DEVICE SHALL BE INSTALLED IN THE MAKE-UP
 WATER LINE TO THE COOLING TOWER PER SBC
 SEC.606.1-606.5
  
 A GREASE INTERCEPTOR IS REQD.PER SPC SEC
 1004.1, 1004.2.,1004.4.CONTACT RODNEY
 COMPO AT CITY OF W.P.B. REGIONAL WASTE-
 WATER TREATMENT FACILITY FOR SIZE
 REQS.
  
 SHT.P-8-WATER HEATER PAN DRAIN AND
 RELIEF LINE SHALL NOT BE COMBINED PER
 COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE
 SEC.507.8.3,507.8.4.
  
 SUBMIT COPY OF COMPLETED APPLICATION OF
 WATER USE PERMIT FROM SO.FLA.WTR.MNGMT.
 (MUST HAVE AGENCY'S STAMP OF RECEIPT ON
 APPLICATION.)SPC 101.4.7,FLA.STATUTE
 373.62.
  
 CORRECTIONS TO PLANS TO BE MADE ON LARGE
 SHEETS AND ADDENDUMS SHALL BE ATTACHED
 TO THE PLANS.

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-02-22 Cont ID  
Sent By tlarge Date 1999-08-26 Time 16:00 Rev Time 5.75
Received By tlarge Date 1999-08-26 Time 16:00 Sent To  
Notes
2001-01-08 00:00:00INDICATE NUMBER OF STAFF TO BE PRESENT
 AT ANY ONE TIME.SPC 104.2.1,TABLE 407.
  
 A GREASE INTERCEPTOR SHALL BE REQUIRED
 PER SPC SEC.1004.1,1004.4.
 CONTACT RODNEY COMPO AT CITY OF WEST
 PALM BEACH REGIONAL SEWER TREATMENT
 PLANT AT 835-7423 FOR MIN.SIZE REQS.
  
 SHT.A-5-SHOW ALL DIMENSIONS AND HEIGHT
 REQ'S.FOR THE HANDICAP FIXTURES.COMPLY
 W/FLA.ACCESS.CODE FOR BLDG.CONST.10/97
 EDITION.
  
 SHT.M-5-AN APPROVED BACKFLOW PREVENTION
 DEVICE SHALL BE INSTALLED ON THE MAKE-UP
 WATER LINE T0 THE COOLING TOWER PER SPC
 SEC.606.1-606.5(WHERE APPLICABLE).
  
 WET VENTS SHALL RECEIVE THE DISCHARGE
 FROM FIXTURE DRAINS ONLY PER COUNTYWIDE
 AMENDMENTS SEC.911.1.1.(RMS.123A & 132A)
  
 SHT.P-3-RMS.#125,127,128,130. SINK S-1
 IS NOT SHOWN ON WATER RISER.SPC 104.2.1.
  
 SHT.P-8.DETAIL #1-PAN DRAIN & RELIEF
 LINES SHALL BE RUN SEPARATELY TO POINT
 OF DISCHARGE.SPC SEC.507.8.3,507.8.4.
  
 A WATER USE PERMIT IS REQ'D.FOR THE
 IRRIGATION SYSTEM PER FLA.STATUTE 373.62
  
 SHT.C-1.CLEANOUTS ON SANITARY SEWER
 SHALL COMPLY W/SPC SEC.710.2.4(2).
  
 AN APPROVED BFP DEVICE IS REQ'D.ON THE
 DOMESTIC WATER SERVICE TO THE BLDG.PER
 SPC 606.1.
  
 IRRIGATION PLANS SHALL BE SIGNED AND
 SEALED BY DESIGN PROFESSIONAL.
  
 TOILET ROOM FLOORS AND WALLS SHALL
 COMPLY W/SBC SEC.1204.2.
  
 KIT.AREA SHALL COMPLY W/F.A.C.B.C.SECS.
 4.24.1- 4.24.7,9.22(7).
  
 LAUNDRY AREA SHALL COMPLY W/F.A.C.B.C.
 SEC.9.5.1.
  
 WATER AND SANITARY LINES AT DUMPSTER
 AREA SHALL BE SHOWN ON THE APPROPRIATE
 RISER DIAGRAMS.SPC 104.2.1.
  
 DRAIN FROM DUMPSTER AND CAN WASH SHALL
 DISCHARGE THROUGH GREASE INTERCEPTOR.
 SPC 1004.1,1004.4.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-01-12 Cont ID  
Sent By gjoyce Date 1999-08-09 Time 15:12 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00LANDSCAPING PLANS NEEDED