Plan Review Stops For Permit 99080036 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2001-04-16 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-04-16 |
Time |
10:06 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-04-16 00:00:00 | RAILING DETAIL ENGINEER CALC'S |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2000-12-18 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2000-12-18 |
Time |
15:18 |
Rev Time |
1.50 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REVISION:10/17/2000 | | SHEET A-1 DOOR SCH. REVISIONS OK | | SHEET A-3 CHANGE OF ROOF | | 1). 1707.5 CONCRETE & CLAY ROOF TILE | | PROOF OF OVERTURNING RESISTANCE. | | A SBCCI OR DADE COUNTY PRODUCT | | APPROVAL REPORT(CURRENT). | | 2).MECHANICAL EQUIPMENT CURB : DETAILS | | FOR STRAPPING WERE NOT GIVEN. | | | | JIM WITMER BUILD. PLAN REVIEW | | (561) 659-8096 EX.8412 | | THANK YOU! |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2000-01-24 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2000-01-24 |
Time |
10:48 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO:CONTRACTOR MUST SUBMIT TEST | | DATA - PRODUCT APPROVAL FOR DOORS, | | WINDOWS AND ROOF COVERING, BEFORE | | CONSTRUCTION. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2000-01-06 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2000-01-06 |
Time |
13:16 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
1999-09-09 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
1999-09-09 |
Time |
13:58 |
Rev Time |
6.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2000-12-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-12-13 |
Time |
22:51 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-12-13 |
Time |
22:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2000-02-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-02-12 |
Time |
20:59 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-02-12 |
Time |
20:57 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ***************** OK ******************* | | | | 1)NOTE: NEW REVISED PLANS FOR E-4 | | PLANS WERE OK`D BY J.LEAHY |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2000-01-24 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2000-01-24 |
Time |
09:02 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | JAKE OK ON PLANS |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2000-02-11 |
|
|
Cont ID |
|
Sent By |
dlauderm |
Date |
1999-11-10 |
Time |
10:57 |
Rev Time |
0.50 |
Received By |
dlauderm |
Date |
1999-11-10 |
Time |
10:56 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | FAILED FOR WATER AND SANITARY REVIEW, | | DSL, 11-10-99. WATER:THE PLAN SHOWS | | A TIE-IN TO THE FIRE LINE FOR A | | SEPARATE PROPERTY OWNER AND A DOMESTIC | | WATER LINE RUN ACROSS PRIVATE PROPERTY | | WITHOUT AN EASEMENT SHOWN.A DEP | | PERMIT IS REQUIRED FOR THE WATER | | SYSTEM, SUBMIT PLANS ACCORDANTLY TO | | THE PUBLIC UTILITIES DEPARTMENT. | | SANITARY: THE GRAVITY SYSTEM IS SHOWN | | BEING TIED TO A PRIVATE GRAVITY SYSTEM | | THAT IS SERVED BY A PRIVATE LIFT | | STATION.A DEP PERMIT IS REQUIRED FOR | | A SEPARATE GRAVITY SEWER SYSTEM WITH | | IT'S OWN PRIVATE LIFT STATION, SUBMIT | | PLANS ACCORDANTLY TO THE PUBLIC | | UTILITIES DEPARTMENT. | | | | THIS REVIEW WAS CHANGED TO PASSED WITH | | PROVISOS, SEE ENG #2 REVIEW. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
4 |
Status |
P |
Date |
2001-03-15 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-03-15 |
Time |
13:08 |
Rev Time |
2.00 |
Received By |
mamini |
Date |
2001-03-15 |
Time |
13:07 |
Sent To |
|
|
Notes |
2001-03-15 00:00:00 | PASSED: | | 1.REVISION AS SUBMITTED FOR CONSTRUCTION | | OF RAMP TO THE NEW PARKING AND BUILDING | | IS APPROVED. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
3 |
Status |
P |
Date |
2000-12-12 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2000-12-12 |
Time |
07:48 |
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PASSED | | NEW FIRE HYDRANT REVISION ACKNOWLEDGED | | PLEASE PROVIDE AS-BUILTS WHEN JOB IS | | COMPLETED TO | | MANUEL GONZALEZ | | 1000 45H STREET SUITE 15 | | WPB FL 33407 | | 561 659 8040 EXT 2306 | | 2 MYLER COPIES WILL ALSO BE REQUIRED. | | THANK YOU. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2000-02-11 |
|
|
Cont ID |
|
Sent By |
dlauderm |
Date |
2000-02-11 |
Time |
11:47 |
Rev Time |
1.00 |
Received By |
dlauderm |
Date |
2000-02-11 |
Time |
11:46 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PASSED WITH PROVISOS: | | | | 1. STORMWATER CALCULATIONS ARE STILL | | REQUIRED, SUPPLY PRIOR TO START OF | | CONSTRUCTION. USE THE FOLLOWING AS A | | GUIDE LINE: | | BUILDING AREA | | +PAVED AREA | | TOTAL IMPERVIOUS AREA | | +TOTAL GREEN AREA | | TOTAL SITE AREA | | TOTAL IMPERVIOUS AREA (IN SF): | | DIVIDED BY 1,573 SF (1 ERU EQUALS THE | | ERU'S TO BE CHARGED | | TOTAL IMPERVIOUS AREA NEEDS TO BE IN | | ERU'S. | | 43,560 SQUARE FEET IN AN ACRE | | 1,573SQUARE FEET 1 ERU | | 27.692308 ERU'S PER ACRE. | | ERU (EQUIVALENT RESIDENTIAL UNIT)IS AN | | INPURMEATABLE SURFACES, SUCH AS ROOFS, | | SIDEWALKS, PARKING LOTS. | | | | | | 2. PLANS ARE STILL WRONG ON WATER | | SERVICE.IT MUST BE A TAPPING VALVE AND | | SLEEVE, 4" WATER SERVICE WITH BYPASS, 3" | | METER THEN THE REDUCED PRESSURE | | PRINCIPLE BACKFLOW PREVENTERS.THE | | DRAWING DOES NOT STATE IT BUT IT IS | | SUGGESTED THAT TWO DEVICES BE INSTALLED | | IN PARALLEL SO THE BUILDINGS ARE NEVER | | WITHOUT SERVICE. | | | | 3. SHEET SP-1 DOES NOT SHOW THE OPENING | | BETWEEN THE DUMPSTER GATES.THE OPENING | | BETWEEN THE GATES MUST BE 12' - 6". |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2000-02-11 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
1999-11-10 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
dlauderm |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SEE DEANS NOTES UNDER ELECTRIC.REVIEW | | WAS CHANGED TO PASSED WITH PROVISOS, SEE | | ENG #2 REVIEW. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2000-11-27 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-11-27 |
Time |
09:04 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-11-27 |
Time |
09:04 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) THE NEW ENTRY DRIVE IS TO BE AT LEAST | | 20 FEET IN CLEAR WIDTH. | | 2) BUILDING ADDRESS NOT SHOWN ON | | ELEVATION DRAWINGS. BUILDING ADDRESS TO | | COMPLY WITH CITY CODE REQUIREMENTS. | | 3) PROVIDE COMPLETE FIRE ALARM SYSTEM | | SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT | | SHOWN ON PLANS. CUT SHEETS, WIRING | | DIAGRAM AND FLOOR PLANS ARE TO BE | | SUBMITTED. | | | | ON NOVEMBER 27,2000, WRITER SPOKE TO | | KEVIN NORTH OF THE WEITZ COMPANY. | | PER MR. NORTH, THE BUILDING WILL BE | | COMPLETELY FIRE SPRINKLER PROTECTED AND | | THE FP PLANS WERE PREVIOUSLY SUBMITTED | | TO THE CITY. MR. NORTH WAS ADVISED THAT | | THE FIRE SPRINKLER SYSTEM CONNECTION IS | | TO BE WITHIN 150 FEET OF THE FIRE | | HYDRANT. PLANS WERE PREVIOUSLY APPROVED | | BY FIRE RESCUE. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
1999-08-25 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
1999-08-25 |
Time |
11:17 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2000-12-14 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-12-14 |
Time |
12:14 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
2000-12-14 |
Time |
12:14 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO: | | CONDENSATE DRAIN TO TERMINATE IN A PERM- | | IABLE LOCATION OR TO STORM DRAIN. | | OVERFLOW PROTECTION REQUIRED FOR AHU PER | | 1997 SMC 304.8.6 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
1999-11-17 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
1999-08-30 |
Time |
13:57 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
1999-08-30 |
Time |
13:57 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | APPROVED 11/17/99 NCD | | 1)AIR ADMITTANCE VALVES NOT PERMITTED IN | | RETURN AIR PLENUM AREA PER 1997 SMC 609. | | 1.3 | | 2)ANY A/C UNITS SERVING AREA USED FOR | | EGRESS SHALL BE SHUT DOWN BY DUCT SMOKE | | DETECTOR 1997 SMC 406.2 | | 3) EVERY ATTIC IN WHICH MECHANICAL EQUIP | | MENT IS INSTALLED SHALL BE ACCESSIBLE BY | | AN OPENING AS LARGE AS THE LARGEST PIECE | | OF EQUIPMENT BUT IN NO CASE LESS THAN | | 22X36 INCHES 1997 SMC 304.4.1 | | 4)PROVIDE BACKDRAFT DAMPER AT EACH | | EXHAUST AIR OPENING NOT EQUIPPED WITH | | CEILING MOUNTED EXHAUST FAN WITH DAMPER | | TO PREVENT CARRYOVER INTO ROOM IF ROOF | | MOUNTED EXHAUST FAN IS NOT RUNNING SMC | | 501.4 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
P |
Date |
2000-12-04 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-12-04 |
Time |
11:40 |
Rev Time |
1.50 |
Received By |
jleech |
Date |
2000-12-04 |
Time |
11:40 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO; | | | | CONDENSATE DRAINS TO BE ROUTED PER NOTE | | # 4. SUBMIT NEW DRAWINGS SHOWING NEW | | L0CATIONS OF CONDENSATE DRAINS, BEFORE | | ROUGH A/C INSPECTION. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2000-02-22 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-02-22 |
Time |
12:36 |
Rev Time |
1.50 |
Received By |
tlarge |
Date |
2000-02-22 |
Time |
12:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
N |
Date |
2000-02-22 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-02-21 |
Time |
09:05 |
Rev Time |
2.25 |
Received By |
tlarge |
Date |
2000-02-21 |
Time |
08:09 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SHOWERS SHALL BE PROVIDED PER SPC TABLE | | 407.(SEE REQS.FOR DORMITORIES.) | | | | CLEARLY SHOW ON PLANS THAT FLOORS AND | | WALLS IN COMMON AREA BATHROOMS AND | | TOILET ROOMS COMPLY W/SBC SEC.1204.2. | | | | SIZE REQUIREMENT AND DESIGN OF GREASE | | TRAP SHALL COMPLY W/HEALTH DEPT.REQS. | | AND CITY OF WEST PALM BEACH UTILITIES. | | CONTACT RODNEY COMPO AT CITY OF WPB | | REGIONAL WASTEWATER TREATMENT FACILITY. | | SEEFLA.ADMIN.CODE SEC.64E-6.013(5)(A). | | | | CLEARLY SHOW ON PLAN THAT GREASE TRAP | | WILL NOT BE LOCATED WITHIN ANGLE OF | | REPOSE. | | | | MINIMUM INLET AND OUTLET TO GREASE TRAP | | SHALL BE 4" AND INLET SHALL DISCHARGE A | | MIN.OF 2 1/2" ABOVE LIQUID LEVEL LINE. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
N |
Date |
2000-02-22 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-01-27 |
Time |
15:04 |
Rev Time |
5.50 |
Received By |
tlarge |
Date |
2000-01-27 |
Time |
15:04 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | CLEARLY SHOW ON THE PLANS THAT THE | | KITCHEN SINK COMPLIES W/FACBC SEC.4.24.1 | | THRU 4.24.7.(IF THIS AREA IS A | | DESIGNATED WORK AREA AND NOT TO BE | | UTILIZED BY THE GUESTSFOR COOKING OR | | WARMING FOOD IT IS NOT REQD.TO BE FULLY | | ACCESSIBLE.CLARIFY ON THE PLANS. | | | | SHOWERS SHALL BE PROVIDED PER SPC TABLE | | 407(DORMITORIES). | | | | CLEARLY SHOW ON THE PLANS THAT FLOORS | | AND WALLS IN COMMON AREA BATHROOMS AND | | TOILET ROOMS COMPLY W/SBC SEC.1204.2 | | | | SIZE REQS.AND DESIGN OF GREASE TRAP | | SHALL COMPLY W/HEALTH DEPT.REQS.AND | | CITY OF WPB UTILITIES.CONTACT RODNEY | | COMPO AT CITY OF WPB REGIONAL WASTEWATER | | TREATMENT FACILITY.(561)835-7423. | | | | DISHWASHER SHALL DRAIN TO SANITARY,NOT | | TO GREASE PER WPB UTILITIES. | | | | SIZE OF DRYWELL SHALL COMPLY W/SMC SEC. | | 304.8.5. | | | | LOCATION OF GREASE TRAP SHALL NOT BE | | WITHIN ANGLE OF REPOSE.SBC 1803.1.3. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2000-02-22 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-10-26 |
Time |
10:37 |
Rev Time |
3.50 |
Received By |
tlarge |
Date |
1999-10-26 |
Time |
10:37 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | THE OCCUPANCY OF THE STRUCTURE SHALL BE | | DETERMINED BY THE BUILDING OFFICIAL PER | | SBC SEC.301.3 AND THE BUILDING OFFICIAL | | SHALL RENDER INTERPRETATIONS PER SBC | | SEC.103.1.(RE:IS OCCUPANCY TO BE CLASSED | | AS A DWELLING OR A DORMITORY.?) | | | | CLEARLY SHOW ON THE PLANS THAT THE | | KITCHEN SINK COMPLIES W/FACBC SEC.4.24.1 | | THRU 4.24.7. | | | | SHOWERS SHALL BE PROVIDED PER SPC TABLE | | 407(DORMITORIES) AND SHALL BE HANDICAP | | ACCESSIBLE PER SBC 4.21. | | | | CLEARLY SHOW ON THE PLANS THAT FLOORS | | AND WALLS IN COMMON AREA BATHROOMS AND | | TOILET ROOMS COMPLY W/SBC SEC.1204.2 | | | | FIXTURE REQS.SHALL BE BASED ON 50 SQ.FT. | | PER PERSON (SLEEPING AREA ONLY) PER | | TABLE 407 OF SPC. | | | | SHT.M-5-AN APPROVED BACKFLOW PREVENTION | | DEVICE SHALL BE INSTALLED IN THE MAKE-UP | | WATER LINE TO THE COOLING TOWER PER SBC | | SEC.606.1-606.5 | | | | A GREASE INTERCEPTOR IS REQD.PER SPC SEC | | 1004.1, 1004.2.,1004.4.CONTACT RODNEY | | COMPO AT CITY OF W.P.B. REGIONAL WASTE- | | WATER TREATMENT FACILITY FOR SIZE | | REQS. | | | | SHT.P-8-WATER HEATER PAN DRAIN AND | | RELIEF LINE SHALL NOT BE COMBINED PER | | COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE | | SEC.507.8.3,507.8.4. | | | | SUBMIT COPY OF COMPLETED APPLICATION OF | | WATER USE PERMIT FROM SO.FLA.WTR.MNGMT. | | (MUST HAVE AGENCY'S STAMP OF RECEIPT ON | | APPLICATION.)SPC 101.4.7,FLA.STATUTE | | 373.62. | | | | CORRECTIONS TO PLANS TO BE MADE ON LARGE | | SHEETS AND ADDENDUMS SHALL BE ATTACHED | | TO THE PLANS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2000-02-22 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-08-26 |
Time |
16:00 |
Rev Time |
5.75 |
Received By |
tlarge |
Date |
1999-08-26 |
Time |
16:00 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | INDICATE NUMBER OF STAFF TO BE PRESENT | | AT ANY ONE TIME.SPC 104.2.1,TABLE 407. | | | | A GREASE INTERCEPTOR SHALL BE REQUIRED | | PER SPC SEC.1004.1,1004.4. | | CONTACT RODNEY COMPO AT CITY OF WEST | | PALM BEACH REGIONAL SEWER TREATMENT | | PLANT AT 835-7423 FOR MIN.SIZE REQS. | | | | SHT.A-5-SHOW ALL DIMENSIONS AND HEIGHT | | REQ'S.FOR THE HANDICAP FIXTURES.COMPLY | | W/FLA.ACCESS.CODE FOR BLDG.CONST.10/97 | | EDITION. | | | | SHT.M-5-AN APPROVED BACKFLOW PREVENTION | | DEVICE SHALL BE INSTALLED ON THE MAKE-UP | | WATER LINE T0 THE COOLING TOWER PER SPC | | SEC.606.1-606.5(WHERE APPLICABLE). | | | | WET VENTS SHALL RECEIVE THE DISCHARGE | | FROM FIXTURE DRAINS ONLY PER COUNTYWIDE | | AMENDMENTS SEC.911.1.1.(RMS.123A & 132A) | | | | SHT.P-3-RMS.#125,127,128,130. SINK S-1 | | IS NOT SHOWN ON WATER RISER.SPC 104.2.1. | | | | SHT.P-8.DETAIL #1-PAN DRAIN & RELIEF | | LINES SHALL BE RUN SEPARATELY TO POINT | | OF DISCHARGE.SPC SEC.507.8.3,507.8.4. | | | | A WATER USE PERMIT IS REQ'D.FOR THE | | IRRIGATION SYSTEM PER FLA.STATUTE 373.62 | | | | SHT.C-1.CLEANOUTS ON SANITARY SEWER | | SHALL COMPLY W/SPC SEC.710.2.4(2). | | | | AN APPROVED BFP DEVICE IS REQ'D.ON THE | | DOMESTIC WATER SERVICE TO THE BLDG.PER | | SPC 606.1. | | | | IRRIGATION PLANS SHALL BE SIGNED AND | | SEALED BY DESIGN PROFESSIONAL. | | | | TOILET ROOM FLOORS AND WALLS SHALL | | COMPLY W/SBC SEC.1204.2. | | | | KIT.AREA SHALL COMPLY W/F.A.C.B.C.SECS. | | 4.24.1- 4.24.7,9.22(7). | | | | LAUNDRY AREA SHALL COMPLY W/F.A.C.B.C. | | SEC.9.5.1. | | | | WATER AND SANITARY LINES AT DUMPSTER | | AREA SHALL BE SHOWN ON THE APPROPRIATE | | RISER DIAGRAMS.SPC 104.2.1. | | | | DRAIN FROM DUMPSTER AND CAN WASH SHALL | | DISCHARGE THROUGH GREASE INTERCEPTOR. | | SPC 1004.1,1004.4. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-01-12 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
1999-08-09 |
Time |
15:12 |
Rev Time |
0.50 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | LANDSCAPING PLANS NEEDED |
|
|