Plan Review Details - Permit 99071517
Plan Review Stops For Permit 99071517
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-08-10 Cont ID  
Sent By dpalmer Date 1999-08-10 Time 13:02 Rev Time 0.00
Received By dpalmer Date 1999-08-10 Time 13:01 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO*****************
  
 1)NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT FROM FAULT CURRENT CALCU-
 -LATIONS.
 2)NOET:ART,210-52D BATH RECEPTS. ARE TO
 BE ON 20AMP BRANCH CIRCUTS.
 3)NOTE:NFPA-72 SMOKE DETECTORS REQ`D
 INSIDE AND OUTSIDE BEDROOMS.
  
 PLEASE HAVE SUBMITTED AND APPROVED
 BEFORE ROUGH ELEC.INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-08-07 Cont ID  
Sent By jleech Date 1999-08-07 Time 11:42 Rev Time 0.50
Received By jleech Date 1999-08-07 Time 11:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-27 Cont ID  
Sent By tlarge Date 1999-07-27 Time 17:44 Rev Time 0.33
Received By tlarge Date 1999-07-27 Time 17:44 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-08-16 Cont ID  
Sent By jcaloger Date 1999-08-16 Time 10:44 Rev Time 2.50
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-07-23 Cont ID  
Sent By gjoyce Date 1999-07-23 Time 16:10 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***