Plan Review Details - Permit 99071429
Plan Review Stops For Permit 99071429
Review Stop P PLUMBING
Rev No 2 Status P Date 1999-07-22 Cont ID  
Sent By tlarge Date 1999-07-22 Time 14:43 Rev Time 0.30
Received By tlarge Date 1999-07-22 Time 14:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-22 Cont ID  
Sent By tlarge Date 1999-07-22 Time 07:04 Rev Time 0.50
Received By tlarge Date 1999-07-22 Time 07:04 Sent To  
Notes
2001-01-08 00:00:00INDICATE TYPE OF PIPING TO BE INSTALLED.
 STD.GAS CODE SEC.306.
  
 SHOW DISTANCE FROM POINT OF DELIVERY TO
 MOST REMOTE OUTLET IN BLDG.STD.GAS CODE
 SEC.305.4.
  
 TOTAL BTU LOAD ON SYSTEM REQ'D.STD.GAS
 CODE SEC.302, 305.3.
  
 INDICATE SUPPLY PRESSURE AND NOTE
 LOCATION OF METER ON PLANS.(DISTANCE
 FROM BLDG.EXTERIOR.).STD.GAS CODE SEC.
 305.2.
  
 2 COPIES OF PLANS REQ'D.STD.GAS CODE
 SEC.104.2.1.