Plan Review Stops For Permit 99071025 |
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
1999-07-21 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
1999-07-21 |
Time |
13:17 |
Rev Time |
0.25 |
Received By |
ndenmark |
Date |
1999-07-21 |
Time |
13:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
1999-07-15 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
1999-07-15 |
Time |
08:57 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
1999-07-15 |
Time |
08:57 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ************** PROVISO ***************** | | 1) FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | REQUIRED PER 1994 SMC 406.1 AND 406.2 | | 2) NOTIFICATION OF FAN SHUT DOWN TO BE | | PER 1996 NFPA 4-4.4.2 OR 4-4.4.3 TIED TO | | BLDG FIRE ALARM SYSTEM OR IF NO BLDG | | SYSTEM, TIED TO HORN AND STROBE | | 3) BATH EXHAUST TO MEET 1994 SMC 503.3.2 |
|
|
|