Plan Review Details - Permit 99071025
Plan Review Stops For Permit 99071025
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-07-21 Cont ID  
Sent By ndenmark Date 1999-07-21 Time 13:17 Rev Time 0.25
Received By ndenmark Date 1999-07-21 Time 13:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-15 Cont ID  
Sent By ndenmark Date 1999-07-15 Time 08:57 Rev Time 0.33
Received By ndenmark Date 1999-07-15 Time 08:57 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO *****************
 1) FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED PER 1994 SMC 406.1 AND 406.2
 2) NOTIFICATION OF FAN SHUT DOWN TO BE
 PER 1996 NFPA 4-4.4.2 OR 4-4.4.3 TIED TO
 BLDG FIRE ALARM SYSTEM OR IF NO BLDG
 SYSTEM, TIED TO HORN AND STROBE
 3) BATH EXHAUST TO MEET 1994 SMC 503.3.2