Plan Review Details - Permit 99061775
Plan Review Stops For Permit 99061775
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-06 Cont ID  
Sent By dpalmer Date 2001-02-06 Time 12:46 Rev Time 0.00
Received By dpalmer Date 2001-02-06 Time 12:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-07-30 Cont ID  
Sent By dpalmer Date 1999-07-30 Time 08:53 Rev Time 0.00
Received By dpalmer Date 1999-07-30 Time 08:53 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
  
 NOTE:NEED TO SUBMIT PLANS WITH AIC
 RATING FIGURED FROM FAULT CURRENT
 CALCULATIONS.PLEASE DRAW ON PANEL SCHED.
 ART:110-9/215-5
 NOTE:RECEPTS.SERVING KITCHEN COUNTER
 SPACE ARE TO BE GFI/GFI PROTECTED.ART:
 210-8-A-6
 NOTE: SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.NFPA-72
 NOTE:EQUIPMENT GROUNDING CONDUCTOR REQ`D
 FROM MAIN DISC.TO PANEL.
 ART: 250-95/250-92
 NOTE:RECEPTS.REQ`D FRONT AND BACK OF
 DWELLING UNITS ART:210-52E
 NOTE:GROUNDING ELECTRODE CONDUCTOR TO GO
 TOBLDG.STEEL AND CWP.
 NOTE:5 ROOMS SHOW CEILING BOXES IN THE
 CENTER OF THE ROOM.WHERE ARE THEY
 CONTROLLED FROM?? SWITCHED?
  
 NEED TO HAVE THE ABOVE INFORMATION
 SUBMITTED AND APPROVED BEFORE ROUGH
 INSPECTION IS CALLED IN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-11-30 Cont ID  
Sent By jleech Date 1999-11-30 Time 12:21 Rev Time 0.35
Received By jleech Date 1999-11-30 Time 12:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 1999-07-31 Cont ID  
Sent By jleech Date 1999-07-31 Time 11:43 Rev Time 0.50
Received By jleech Date 1999-07-31 Time 11:43 Sent To  
Notes
2001-01-08 00:00:00NO ENERGY CALKS.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-24 Cont ID  
Sent By tlarge Date 1999-07-24 Time 09:56 Rev Time 0.33
Received By tlarge Date 1999-07-24 Time 09:56 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 1999-11-24 Cont ID  
Sent By jgomez Date 1999-11-24 Time 16:50 Rev Time 1.50
Received By jgomez Date 1999-11-24 Time 16:50 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
  
 1-EGRESS WINDOWS MUST HAVE A MINIMUM OF
 22" CLEAR HEIGHT OPENING. SECTION
 1005.4 SBC 1994.
 2-PROVIDE PRODUCT APPROVAL FOR WINDOW
 MULLIONS.
 3-STORM PANELS UNDER A SEPARATE PERMIT.
 -PROVIDE COMPLETE INSTALLATION
 SCHEDULE, AS PER CITY SAMPLE, AND KEY
 PLAN.
 -HIGHLIGHT SPECIFIC MOUNTING CONDITIONS
 AND ANCHORS SCHEDULE TO BE USED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 1999-08-30 Cont ID  
Sent By jgomez Date 1999-08-30 Time 13:55 Rev Time 1.00
Received By jgomez Date   Time   Sent To D
Notes
2001-01-08 00:00:00PLANS WERE NOT CORRECTED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 1999-08-16 Cont ID  
Sent By jgomez Date 1999-08-16 Time 17:19 Rev Time 2.00
Received By jgomez Date   Time   Sent To D
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PROVIDE ENERGY CALCULATIONS (USE FORM
 600A-97) AND MANUAL "J" CALCULATIONS.
 2-PROVIDE SOIL TEST REPORT AS PER SEC.
 1804.2.2 AND TABLE 1804.2.7.3 OF CITY
 AMENDMENTS.
 3-DRAWINGS TO HAVE THE NAME AND ADDRESS
 OF THE DESIGNER ENGINEER. SEC 104.2.1
 CITY AMENDMENTS.
 4-PAY THE IMPACT FEES TO THE COUNTY.
 5-PROVIDE SAFETY GLASS WHERE REQUIRED.
 SEE PLANS FOR COMMENTS. SEC. 2405.2
 SBC 1997.
 6-PROVIDE THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS. SEC. 1606 SBC 1997.
 7-STORM PANELS:*PROVIDE A COMPLETE
 INSTALLATION SCHEDULE (SEE ATTACHED)
 AND KEY PLAN. *HIGHLIGHT SPECIFIC
 ANCHORS AND SPACING TO BE USED.
 NOTE:THIS INFORMATION MAY BE FURNISHED
 AT A LATER TIME, BUT, UNDER A SEPARATE
 PERMIT.
 8-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR AND REAR DOOR.
 9-FOOTING F1 TO BE 16" DEEP MIN. SEC.
 1804.1.3 SBC/97 AND SEC. 1804.1.9
 CITY AMENDMENTS.
 10-REVISE NOTE #1 OF FOUNDATION NOTES.
 PROVIDE MIN. 6 MIL VAPOR BARRIER.
 SEC. 1909.2 SBC 1997.
 11-MEAN ROOF HEIGHT SPECIFIED IN THE
 DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM IS WRONG. REVISE AS
 REQUIRED.
 NOTE: IT IS RECOMMENDED TO WRITE THIS
 INFORMATION ON THE PLANS INSTEAD OF
 FILLING A SEPARATE FORM.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-07-21 Cont ID  
Sent By gjoyce Date 1999-07-01 Time 12:05 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS CITY CONCURRENCY