Plan Review Details - Permit 99061773
Plan Review Stops For Permit 99061773
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-01-10 Cont ID  
Sent By dpalmer Date 2001-01-10 Time 11:58 Rev Time 0.00
Received By dpalmer Date 2001-01-10 Time 11:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 1999-12-14 Cont ID  
Sent By dpalmer Date 1999-12-14 Time 06:10 Rev Time 0.00
Received By dpalmer Date 1999-12-14 Time 06:10 Sent To  
Notes
2001-01-08 00:00:00****************************************
  
 *************PROVISO*******************
  
 NOTES SAME AS BEFORE!!!!!!!
 SUBMIT FOR REVIEW AND APPROVAL BEFORE
 FIRST ROUGH ELECTRICAL INSPECTION IS
 CALLED IN.!!!!!!!!!!!!

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-07-29 Cont ID  
Sent By dpalmer Date 1999-07-29 Time 18:12 Rev Time 0.00
Received By dpalmer Date 1999-07-29 Time 18:12 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
  
 NOTE:NEED TO SUBMIT PLANS WITH AIC
 RATING FIGURED FROM FAULT CURRENT
 CALCULATIONS.PLEASE DRAW ON PANEL SCHED.
 ART:110-9/215-5
 NOTE:RECEPTS.SERVING KITCHEN COUNTER
 ARE TO GFI/GFI PROTCTED,ART:210-8-A-6.
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS AS PER NFPA-72
 NOTE:EQUIPMENT GROUNDING CONDUCTOR
 REQ`D FROM MAIN DISC.TO PANEL.250-92
 250-95.
 NOTE:ART:210-52E RECEPTS.REQ`D BACK AND
 FRONT OF DWELLING.
 NOTE:GROUNDING ELECTRODE CONDUCTOR
 REQ`D TO GO TO CWP BLDG.STEEL.
 NOTE:5 ROOMS SHOW CEILING BOXES.HOW ARE
 THEY CONTROLLED OR SWITCH?
  
 NEED TO HAVE THE ABOVE INFORMATION
 SUBMITTED AND APPROVED BEFORE ROUGH
 INSPECTION IS CALLED IN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-14 Cont ID  
Sent By jleech Date 1999-07-31 Time 11:50 Rev Time 1.00
Received By cthirben Date 1999-12-14 Time 11:10 Sent To  
Notes
2001-01-08 00:00:00NO ENERGY CALKS.
 REVISED ENERGY CALC. ISSUED OK.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-24 Cont ID  
Sent By tlarge Date 1999-07-24 Time 09:57 Rev Time 0.33
Received By tlarge Date 1999-07-24 Time 09:57 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 1999-12-23 Cont ID  
Sent By jgomez Date 1999-12-23 Time 16:13 Rev Time 1.50
Received By jgomez Date 1999-12-23 Time 16:12 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE SURVEY ISSUED FOR BUILDING
 PERMIT. SEE SURVEYOR'S STATEMENT.
 2-PROVIDE SAFETY GLAZING IN BEDROOM #1
 WINDOW. SEC 2405.2 SBC 1994.
 3-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION
 SCHEDULE. FILL IN ALL THE REQUESTED
 INFORMATION.
 -HIGHLIGHT SPECIFIC MOUNTING
 CONDITIONS. TOP AND BOTTOM. AND ANCHOR
 AND SPACING TO BE USED.
 -STORM PANELS TO BE UNDER A SEPARATE
 PERMIT.
 4-EGRESS WINDOWS MUST HAVE A CLEAR
 HEIGHT OPENING OF 22". SEC 1005.4
 SBC 1994.
 5-PROVIDE PRODUCT APPROVAL FOR WINDOW
 MULLIONS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 1999-08-30 Cont ID  
Sent By jgomez Date 1999-08-30 Time 13:58 Rev Time 1.00
Received By jgomez Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLANS WERE NOT CORRECTED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 1999-08-17 Cont ID  
Sent By jgomez Date 1999-08-17 Time 14:51 Rev Time 1.00
Received By jgomez Date   Time   Sent To D
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PROVIDE ENERGY CALCULATIONS (USE FORM
 600A-97) AND MANUAL "J" CALCULATIONS.
 2-PROVIDE SOIL TEST REPORT AS PER SEC.
 1804.2.2 AND TABLE 1804.2.7.3 OF CITY
 AMENDMENTS.
 3-DRAWINGS TO HAVE THE NAME AND ADDRESS
 OF THE DESIGNER ENGINEER. SEC 104.2.1
 CITY AMENDMENTS.
 4-PAY THE IMPACT FEES TO THE COUNTY.
 5-PROVIDE SAFETY GLASS WHERE REQUIRED.
 SEE PLANS FOR COMMENTS. SEC. 2405.2
 SBC 1997.
 6-PROVIDE THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS. SEC 1606 SBC 1997.
 7-STORM PANELS: * PROVIDE A COMPLETE
 INSTALLATION SCHEDULE AND KEY PLAN.
 *HIGHLIGHT SPECIFIC MOUNTING CONDITION
 AND ANCHORS AND SPACING TO BE USED.
 NOTE:THIS INFORMATION MAY BE FURNISHED
 AT A LATER TIME, BUT, UNDER A SEPARATE
 PERMIT.
 8-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR AND REAR DOOR.
 9-FOOTING F1 TO BE 16" DEEP MIN. SEC.
 1804.1.3 SBC 1997 AND SEC. 1804.1.9
 CITY AMENDMENTS.
 10-REVISE NOTE #1 OF FOUNDATION NOTES.
 PROVIDE MIN. 6 MIL VAPOR BARRIER.
 SEC. 1909.2 SBC 1997.
 11-MEAN ROOF HEIGHT SPECIFIED IN THE
 DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM IS WRONG. REVISE AS
 REQUIRED.
 NOTE: IT IS RECOMMENDED TO WRITE THIS
 INFORMATION ON THE PLANS, INSTEAD OF
 FILLING A SEPARATE FORM.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-07-21 Cont ID  
Sent By gjoyce Date 1999-07-01 Time 12:06 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS CITY CONCURRENCY