Plan Review Stops For Permit 99061677 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2000-05-22 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-05-22 |
Time |
09:52 |
Rev Time |
2.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO: REVISION | | 1. ALL EXTERIOR GLAZED OPENINGS PROVIDE | | PRODUCT APPROVAL INFORMATION FOR WIND | | AND IMPACT PROTECTION ACCORDING TO THE | | 1997 STANDARD BUILDING CODE AS AMENDED | | BY THE CITY OF WEST PALM BEACH. | | 2. SHEET A-11 SHUTTER INSTALLATION AND | | STORAGE. SUBMIT A WRITTEN PLAN TO THE | | BUILDING OFFICIAL SHOW STORAGE LOCATIONS | | AND LISST PERSONEL WHO WILL INSTALL THE | | GLAZING PROTECTION. SEE CITY OF WEST | | PALM BEACH POLICY ON GLAZING PROTEDTION | | FOR ADDITIONAL INFORMATION. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
1999-08-02 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
1999-07-07 |
Time |
11:30 |
Rev Time |
32.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | CHECK LIST | | E |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2000-12-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-12-11 |
Time |
09:50 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-12-11 |
Time |
09:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
P |
Date |
2000-12-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-12-04 |
Time |
09:47 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-12-04 |
Time |
09:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2000-11-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-11-21 |
Time |
08:39 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-11-21 |
Time |
08:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2000-11-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-11-14 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-11-14 |
Time |
15:03 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: PLEASE SEE NOTES ATTACHED FROM | | REVIEW DONE 6/19/00 BY JAKE LEAHY. | | NOT ALL NOTES WERE ADDRESSED ON E-4. | | | | 2)NOTE: PLEASE SEE E-4 WHERE IS MAIN FOR | | PANEL "X" NO MAIN IS SHOWN FOR THIS SER- | | VICE.?PLEASE SEE NOTE FROM JAKE LEAHY | | PER 230-72B NEC AND NFPA. | | | | 3)NOTE: SEE NOTES FORM PREVIOUS REVIEW | | FOR FIXTURE HEIGHT OF 74". SEE LIFE- | | -SAFETY 101 FOR MIN. OF 6'8" | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW.IF THERE ARE ANY QUESTIONS PLEASE | | CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 659-8096 EXT 8372 | | | | JAKE LEAHY | | CHIEF ELECTRICAL INSPECTOR | | 659-8096 EXT 8451 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2000-08-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-08-28 |
Time |
07:31 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-08-28 |
Time |
07:31 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SHEET E-2 ONLY FOR REV #9 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2000-05-23 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2000-05-23 |
Time |
09:26 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2000-06-19 |
Time |
13:17 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1- PG. E-1SHOWS A REFERENCE TO THE | | HEIGHT OF FIXTURES IN THE STAIRWELLS | | AND CORIDOORS AT 74" LIFE SAFTEY 101 | | HAS A MINIMUM OF 6'8" ABOVE FINISHED | | FLOOR UNLESS IT IS FLUSH WITH THE WAL | | | | 2- PG. E-3 HAS A REFERENCE TO THE | | LOCATION AND NUMBER OF SMOKE DETECTOR | | IN THE UNITS NFPA 72 REQUIRES THEM TO | | BE INSIDE AND OUTSIDE OF EACH BDRM. | | THE NOTE REFERENCES THE FIRE DEPT. | | THEY DONT DO ROUGH INSPECTIONS!! | | DETECTORS WILL BE PER PLAN AND CODE. | | 1996 NFPA 70 ADOPTED NFPA 72 WHICH | | CALLS FOR THE DETECTORS AS STATED | | ABOVE. | | | | PG. E-4 PANELS X, XR, AND HR SHOW NO | | AIC RATINGS FOR THE PANEL AND BREAKER | | PLEASE LIST IN THE DESCRIPTION OF THE | | PANEL AS SHOWN ON OTHER PANELS | | | | PG E-4 GNEERATOR SHOWS THE MAIN ON THE | | SECOND FLOOR!230-72(B) REQUIRES IT | | TO BE WITH THE NORMAL MAINS BUT NOT | | RIGHT NEXT TO THEM, REMOTE WHICH CAN | | BE AS LITTLE AS 10'!!!! PER NFPA | | | | PG E-42500 AMP FEED TO SECOND FLOOR FOR | | APT. MAINS NEEDS TO BE ENCASED IN | | 2" OF CONCRETE, BRICK, OR TILE!!!!! | | | | PR E-4 SAME FOR THE FIRE PUMP!!!!!!!!! | | | | PG E-4 THERE IS ALSO NO REFERENCE TO THE | | PLAQUES THAT ARE REQUIRED AT EACH OF | | THE THREE SERVICES SHOWING THE | | LOCATIONS OF THE OTHER SERVICES. | | 230-2(E) |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
1999-07-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
1999-07-26 |
Time |
14:19 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2000-05-23 |
Time |
08:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
1999-08-10 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
1999-08-10 |
Time |
11:07 |
Rev Time |
3.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | MEC WPBFD APPROVED WITH COMMENTS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
P |
Date |
2001-02-13 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-02-13 |
Time |
13:21 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2001-02-13 |
Time |
13:21 |
Sent To |
|
|
Notes |
2001-02-13 00:00:00 | AS BUILT DRAWINGS REVIEWED 2/13/01, | | APPROVED. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2000-07-13 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-07-13 |
Time |
08:32 |
Rev Time |
0.00 |
Received By |
cthirben |
Date |
2000-07-13 |
Time |
09:57 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | NOTES::::::::::::::::::::::::::::::::::: | | LETTER FOR APPROVED MASTIC TO BE INCLUD- | | ED TO PLANS. | | REVISION: | | RECIEVED SEALED LETTER FOR SUPPLY OR | | EXHAUST RISER SUPPORT TO BE FILED IN | | PLANS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
1.00 |
Received By |
cthirben |
Date |
2000-06-26 |
Time |
10:57 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | NOTE:******************************** | | CALLED ON 6.13.00 REQUESTING A RASIED | | SEAL ON REVISION | | CALLED ON 6.26.00 CUST WILL PICK UP REVI | | SIONS |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2000-03-30 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-03-30 |
Time |
11:41 |
Rev Time |
1.00 |
Received By |
ndenmark |
Date |
2000-03-30 |
Time |
11:41 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO: OVERFLOW PROTECTION REQUIRED |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
1999-07-27 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
1999-07-27 |
Time |
10:46 |
Rev Time |
2.00 |
Received By |
ndenmark |
Date |
1999-07-27 |
Time |
10:46 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO COMMENTS RESPONSE BY ARCHITECT | | #1 DRYER VENTS TO BE ADDRESSED BY LETTER | | SEE ATTACHED FAX COPY, HARD COPY TO | | FOLLOW, PLANS TO BE REVISED PRIOR TO ANY | | MECHANICAL WORK | | #2 THE SCREEN IS WHAT IS NOT TO CODE, | | NOT THE BACKDRAFT DAMPER. SCREEN TO BE | | REMOVED | | #3 OK | | #4 OK | | #5 OK | | #6 OK | | #7 OK |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
1999-07-27 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
1999-07-10 |
Time |
06:49 |
Rev Time |
1.00 |
Received By |
ndenmark |
Date |
1999-07-10 |
Time |
06:49 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | *************PROVISO******************* | | | | 1) DRYER VENT DUCTS TO RUN TO OUTSIDE OF | | THE BUILDING. 1994 SMC 509.1 (1) DUCTS | | SHALL NOT BE CONNECTED TO A VENT | | CONNECTOR, GAS VENT, CHIMNEY, CRAWL | | SPACE OR OTHER SIMILIAR CONCEALED SPACE. | | THE EXCEPTION 1994 SMC 610.1.3(2) WHERE | | BRANCH DUCTS CONNECT TO RETURN RISERS | | IN WHICH THE AIR IS UPWARD AND SUBDUCTS | | AT LEAST 22 INCHES LONG ARE CARRIED UP | | INSIDE THE RISER AT EACH INLET.,DOES NOT | | APPLY TO DRYER VENTS | | 2) THE EXHAUST FAN FOR THE DRYER VENT | | CHASE DOES NOT COMPLY WITH THE REQUIR- | | MENTS OF 1994 SMC 509.3 THE WALL OR ROOF | | CAP SHALL BE NONSCREENED WITH BACKDRAFT | | DAMPER. | | 3)OVERFLOW PROTECTION REQUIRED ON AHU'S | | 4) EXHAUST FROM GENERATOR TO TERMINATE | | MIN. 10 FT FROM PARKING AREAS, WINDOWS, | | DOOR OR AIR INTAKE OPENINGS AND AT LEAST | | 10 FT. ABOVE ADJOINING ABOVE ADJOINING | | GRADE LEVEL, PER 1994 SMC 506.1 | | 5) 1994 SMC 406.2 REQUIRES SYSTEMS SERV- | | ING AREAS USED FOR EGRESS TO HAVE AUTO- | | MATIC FAN SHUT DOWN. PROVIDE AUTOMATIC | | FAN SHUT DOWN FOR AHU 4. | | 6)1994 SMC 406.5 SPECIAL PROVISIONS FOR | | HIGH RISE GROUP R BLDGS REQUIRES A SMOKE | | DETECTOR INSTALLED IN THE DUCT AT EACH | | CONNECTION TO A VERTICAL DUCT OR RISER | | SERVING A RECIRCULATING AIR SYSTEM OF | | MORE THAN ONE STORY. PROVIDE DETAIL OF | | LOCATON AND TYPE DETECTOR.1994SBC412.2.1 | | 7)PROVIDE INFORMATION ON SMOKE CONTROL | | SHOWING COMPLIANCE WITH 1994 SBC 412.5 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2000-07-12 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-07-12 |
Time |
17:00 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
2000-07-12 |
Time |
17:00 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | FLIP DW & KIT.SINK IN "D" UNIT,CHANGE | | SHOWER TO TUB IN "E"UNIT. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2000-03-30 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-03-30 |
Time |
17:14 |
Rev Time |
2.75 |
Received By |
tlarge |
Date |
2000-03-30 |
Time |
17:14 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ALL BATHROOMS IN THE DWELLING UNITS | | SHALL COMPLY W/FEDERAL FAIR HOUSING ACT | | 24 CFR 100.205(C)(3)(IV),REQ.#7(2), | | PARAGRAPH (A) OR (B).CLEAR FLOOR SPACE | | SHALL BE SHOWN ON THE PLANS AND | | DESIGNATE WHICH DESIGN SPECIFICATION | | ("A" OR "B")OF THE FAIR HOUSING ACT IS | | BEING USED. | | ******NOTE:IF YOU CHOOSE SPECIFICATION | | "A"IT APPLIES TO ALL BATHROOMS IN THE | | DWELLING UNIT AND CLEAR FLOOR SPACE FOR | | FIXTURES SHALL COMPLY W/FIG.7(A),(B),(C) | | (D).IN SPECIFICATION"B"ONLY ONE BATHROOM | | IS REQD.TO COMPLY W/THE PROVISIONS OF | | THE ACT FOR MANEUVERING AND CLEAR FLOOR | | SPACE REQUIREMENTS AT FIXTURES. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
1999-07-27 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-07-27 |
Time |
11:20 |
Rev Time |
1.25 |
Received By |
tlarge |
Date |
1999-07-27 |
Time |
11:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
1999-07-27 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-07-08 |
Time |
16:20 |
Rev Time |
11.00 |
Received By |
tlarge |
Date |
1999-07-08 |
Time |
16:20 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SHT.P-5.-UNITS"A","B" & "C" CORRECTLY | | SIZE WATER LINES TO BATHROOM GROUPS. | | OMPLY W/COUNTYWIDE AMENDMENTS TO SPC | | SEC.607.7. | | | | SHT.P-6.-4" F.D. IN EMERG.GEN.ROOM | | REQUIRES VENT.COMPLY W/SPC TABLE 908.1. | | | | SHT.P-6.-FLOOR DRAIN IN TRASH ROOM | | REQUIRES VENT.COMPLY W/SPC TABLE 908.1. | | | | SHT.P-6.-STACKS #9,10,13,14,15,16,21,22, | | 23,24,27,28.SIZE OF VERTICAL COMBINATION | | WASTE AND VENT SYSTEM SHALL COMPLY W/SPC | | SEC.911.4 AND TABLE 911.4 (BRANCH BEGINS | | AS 6" AND REDUCES TO 5".NOTE:PIPE SIZE | | TO REMAIN FULL SIZE THRU ROOF.) | | | | SHT.P-7.-WTR.HEATER DETAIL-PAN DRAIN BE | | MIN.OF 1" PER SPC SEC.507.8.2. | | | | NOTE ON PLAN THAT SHOWER VALVES COMPLY | | W/SPC TABLE 613. | | | | SHT.P-5.-SERVICE SINK ON GROUND FLR. | | SHALL BE VALVED PER SPC SEC.610.4.1. | | | | SIZE OF GREASE TRAP AND OIL/SAND | | INTERCEPTOR SHALL BE APPROVED BY CITY | | OF WEST PALM BEACH UTILITIES DEPT. | | CONTACT RODNEY COMPO AT(561)835-7423. | | | | RELIEF VENTS ARE REQ'D.IN THE DRAINAGE | | SYSTEM PER SPC SEC.916. | | | | SHT.A-3.-DISTANCE OF WATER SERVICE FROM | | BLDG.DRAIN OR SEWER SHALL COMPLY W/SPC | | SEC.608.3, 608.4.(NOTE AREAS AT GREASE | | TRAPS AND OIL /SAND INTERCEPTOR. | | | | SUBMIT PIPING ISOMETRIC FOR STORM | | DRAINAGE SYSTEM. SPC 104.2.1. | | | | SUBMIT RISER DIAGRAM FOR SUMP PUMP | | PIPING IN TRASH ROOM.COMPLY W/SPC SEC. | | 717. | | | | SHOW DISTANCE OF INTERCEPTORS FROM | | BLDG.COMPLY W/STANDARD BLDG.CODE SEC. | | 1803.1.3.FOR EXCAVATIONS. | | | | A COMPLETE GAS DRAWING SHALL BE | | SUBMITTED PRIOR TO ISSUANCE OF GAS | | PERMIT PER STANDARD GAS CODE SEC.104.2.1 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
1999-08-02 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
1999-08-02 |
Time |
07:40 |
Rev Time |
1.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|