Plan Review Details - Permit 99061677
Plan Review Stops For Permit 99061677
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-05-22 Cont ID  
Sent By bstaples Date 2000-05-22 Time 09:52 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO: REVISION
 1. ALL EXTERIOR GLAZED OPENINGS PROVIDE
 PRODUCT APPROVAL INFORMATION FOR WIND
 AND IMPACT PROTECTION ACCORDING TO THE
 1997 STANDARD BUILDING CODE AS AMENDED
 BY THE CITY OF WEST PALM BEACH.
 2. SHEET A-11 SHUTTER INSTALLATION AND
 STORAGE. SUBMIT A WRITTEN PLAN TO THE
 BUILDING OFFICIAL SHOW STORAGE LOCATIONS
 AND LISST PERSONEL WHO WILL INSTALL THE
 GLAZING PROTECTION. SEE CITY OF WEST
 PALM BEACH POLICY ON GLAZING PROTEDTION
 FOR ADDITIONAL INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-08-02 Cont ID  
Sent By bstaples Date 1999-07-07 Time 11:30 Rev Time 32.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00CHECK LIST
 E

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2000-12-11 Cont ID  
Sent By dpalmer Date 2000-12-11 Time 09:50 Rev Time 0.00
Received By dpalmer Date 2000-12-11 Time 09:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2000-12-04 Cont ID  
Sent By dpalmer Date 2000-12-04 Time 09:47 Rev Time 0.00
Received By dpalmer Date 2000-12-04 Time 09:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2000-11-21 Cont ID  
Sent By dpalmer Date 2000-11-21 Time 08:39 Rev Time 0.00
Received By dpalmer Date 2000-11-21 Time 08:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2000-11-14 Cont ID  
Sent By dpalmer Date 2000-11-14 Time 15:03 Rev Time 0.00
Received By dpalmer Date 2000-11-14 Time 15:03 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SEE NOTES ATTACHED FROM
 REVIEW DONE 6/19/00 BY JAKE LEAHY.
 NOT ALL NOTES WERE ADDRESSED ON E-4.
  
 2)NOTE: PLEASE SEE E-4 WHERE IS MAIN FOR
 PANEL "X" NO MAIN IS SHOWN FOR THIS SER-
 VICE.?PLEASE SEE NOTE FROM JAKE LEAHY
 PER 230-72B NEC AND NFPA.
  
 3)NOTE: SEE NOTES FORM PREVIOUS REVIEW
 FOR FIXTURE HEIGHT OF 74". SEE LIFE-
 -SAFETY 101 FOR MIN. OF 6'8"
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372
  
 JAKE LEAHY
 CHIEF ELECTRICAL INSPECTOR
 659-8096 EXT 8451

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-08-28 Cont ID  
Sent By dpalmer Date 2000-08-28 Time 07:31 Rev Time 0.00
Received By dpalmer Date 2000-08-28 Time 07:31 Sent To  
Notes
2001-01-08 00:00:00SHEET E-2 ONLY FOR REV #9

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-05-23 Cont ID  
Sent By jleahy Date 2000-05-23 Time 09:26 Rev Time 0.00
Received By jleahy Date 2000-06-19 Time 13:17 Sent To  
Notes
2001-01-08 00:00:001- PG. E-1SHOWS A REFERENCE TO THE
 HEIGHT OF FIXTURES IN THE STAIRWELLS
 AND CORIDOORS AT 74" LIFE SAFTEY 101
 HAS A MINIMUM OF 6'8" ABOVE FINISHED
 FLOOR UNLESS IT IS FLUSH WITH THE WAL
  
 2- PG. E-3 HAS A REFERENCE TO THE
 LOCATION AND NUMBER OF SMOKE DETECTOR
 IN THE UNITS NFPA 72 REQUIRES THEM TO
 BE INSIDE AND OUTSIDE OF EACH BDRM.
 THE NOTE REFERENCES THE FIRE DEPT.
 THEY DONT DO ROUGH INSPECTIONS!!
 DETECTORS WILL BE PER PLAN AND CODE.
 1996 NFPA 70 ADOPTED NFPA 72 WHICH
 CALLS FOR THE DETECTORS AS STATED
 ABOVE.
  
 PG. E-4 PANELS X, XR, AND HR SHOW NO
 AIC RATINGS FOR THE PANEL AND BREAKER
 PLEASE LIST IN THE DESCRIPTION OF THE
 PANEL AS SHOWN ON OTHER PANELS
  
 PG E-4 GNEERATOR SHOWS THE MAIN ON THE
 SECOND FLOOR!230-72(B) REQUIRES IT
 TO BE WITH THE NORMAL MAINS BUT NOT
 RIGHT NEXT TO THEM, REMOTE WHICH CAN
 BE AS LITTLE AS 10'!!!! PER NFPA
  
 PG E-42500 AMP FEED TO SECOND FLOOR FOR
 APT. MAINS NEEDS TO BE ENCASED IN
 2" OF CONCRETE, BRICK, OR TILE!!!!!
  
 PR E-4 SAME FOR THE FIRE PUMP!!!!!!!!!
  
 PG E-4 THERE IS ALSO NO REFERENCE TO THE
 PLAQUES THAT ARE REQUIRED AT EACH OF
 THE THREE SERVICES SHOWING THE
 LOCATIONS OF THE OTHER SERVICES.
 230-2(E)

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-07-26 Cont ID  
Sent By dpalmer Date 1999-07-26 Time 14:19 Rev Time 0.00
Received By jleahy Date 2000-05-23 Time 08:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-08-10 Cont ID  
Sent By bstaples Date 1999-08-10 Time 11:07 Rev Time 3.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00MEC WPBFD APPROVED WITH COMMENTS.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2001-02-13 Cont ID  
Sent By pkrauss Date 2001-02-13 Time 13:21 Rev Time 0.25
Received By pkrauss Date 2001-02-13 Time 13:21 Sent To  
Notes
2001-02-13 00:00:00AS BUILT DRAWINGS REVIEWED 2/13/01,
 APPROVED.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2000-07-13 Cont ID  
Sent By cthirben Date 2000-07-13 Time 08:32 Rev Time 0.00
Received By cthirben Date 2000-07-13 Time 09:57 Sent To  
Notes
2001-01-08 00:00:00NOTES:::::::::::::::::::::::::::::::::::
 LETTER FOR APPROVED MASTIC TO BE INCLUD-
 ED TO PLANS.
 REVISION:
 RECIEVED SEALED LETTER FOR SUPPLY OR
 EXHAUST RISER SUPPORT TO BE FILED IN
 PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 1.00
Received By cthirben Date 2000-06-26 Time 10:57 Sent To  
Notes
2001-01-08 00:00:00NOTE:********************************
 CALLED ON 6.13.00 REQUESTING A RASIED
 SEAL ON REVISION
 CALLED ON 6.26.00 CUST WILL PICK UP REVI
 SIONS

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-03-30 Cont ID  
Sent By ndenmark Date 2000-03-30 Time 11:41 Rev Time 1.00
Received By ndenmark Date 2000-03-30 Time 11:41 Sent To  
Notes
2001-01-08 00:00:00PROVISO: OVERFLOW PROTECTION REQUIRED

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-07-27 Cont ID  
Sent By ndenmark Date 1999-07-27 Time 10:46 Rev Time 2.00
Received By ndenmark Date 1999-07-27 Time 10:46 Sent To  
Notes
2001-01-08 00:00:00PROVISO COMMENTS RESPONSE BY ARCHITECT
 #1 DRYER VENTS TO BE ADDRESSED BY LETTER
 SEE ATTACHED FAX COPY, HARD COPY TO
 FOLLOW, PLANS TO BE REVISED PRIOR TO ANY
 MECHANICAL WORK
 #2 THE SCREEN IS WHAT IS NOT TO CODE,
 NOT THE BACKDRAFT DAMPER. SCREEN TO BE
 REMOVED
 #3 OK
 #4 OK
 #5 OK
 #6 OK
 #7 OK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-27 Cont ID  
Sent By ndenmark Date 1999-07-10 Time 06:49 Rev Time 1.00
Received By ndenmark Date 1999-07-10 Time 06:49 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO*******************
  
 1) DRYER VENT DUCTS TO RUN TO OUTSIDE OF
 THE BUILDING. 1994 SMC 509.1 (1) DUCTS
 SHALL NOT BE CONNECTED TO A VENT
 CONNECTOR, GAS VENT, CHIMNEY, CRAWL
 SPACE OR OTHER SIMILIAR CONCEALED SPACE.
 THE EXCEPTION 1994 SMC 610.1.3(2) WHERE
 BRANCH DUCTS CONNECT TO RETURN RISERS
 IN WHICH THE AIR IS UPWARD AND SUBDUCTS
 AT LEAST 22 INCHES LONG ARE CARRIED UP
 INSIDE THE RISER AT EACH INLET.,DOES NOT
 APPLY TO DRYER VENTS
 2) THE EXHAUST FAN FOR THE DRYER VENT
 CHASE DOES NOT COMPLY WITH THE REQUIR-
 MENTS OF 1994 SMC 509.3 THE WALL OR ROOF
 CAP SHALL BE NONSCREENED WITH BACKDRAFT
 DAMPER.
 3)OVERFLOW PROTECTION REQUIRED ON AHU'S
 4) EXHAUST FROM GENERATOR TO TERMINATE
 MIN. 10 FT FROM PARKING AREAS, WINDOWS,
 DOOR OR AIR INTAKE OPENINGS AND AT LEAST
 10 FT. ABOVE ADJOINING ABOVE ADJOINING
 GRADE LEVEL, PER 1994 SMC 506.1
 5) 1994 SMC 406.2 REQUIRES SYSTEMS SERV-
 ING AREAS USED FOR EGRESS TO HAVE AUTO-
 MATIC FAN SHUT DOWN. PROVIDE AUTOMATIC
 FAN SHUT DOWN FOR AHU 4.
 6)1994 SMC 406.5 SPECIAL PROVISIONS FOR
 HIGH RISE GROUP R BLDGS REQUIRES A SMOKE
 DETECTOR INSTALLED IN THE DUCT AT EACH
 CONNECTION TO A VERTICAL DUCT OR RISER
 SERVING A RECIRCULATING AIR SYSTEM OF
 MORE THAN ONE STORY. PROVIDE DETAIL OF
 LOCATON AND TYPE DETECTOR.1994SBC412.2.1
 7)PROVIDE INFORMATION ON SMOKE CONTROL
 SHOWING COMPLIANCE WITH 1994 SBC 412.5

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-07-12 Cont ID  
Sent By tlarge Date 2000-07-12 Time 17:00 Rev Time 0.50
Received By tlarge Date 2000-07-12 Time 17:00 Sent To  
Notes
2001-01-08 00:00:00FLIP DW & KIT.SINK IN "D" UNIT,CHANGE
 SHOWER TO TUB IN "E"UNIT.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-03-30 Cont ID  
Sent By tlarge Date 2000-03-30 Time 17:14 Rev Time 2.75
Received By tlarge Date 2000-03-30 Time 17:14 Sent To  
Notes
2001-01-08 00:00:00ALL BATHROOMS IN THE DWELLING UNITS
 SHALL COMPLY W/FEDERAL FAIR HOUSING ACT
 24 CFR 100.205(C)(3)(IV),REQ.#7(2),
 PARAGRAPH (A) OR (B).CLEAR FLOOR SPACE
 SHALL BE SHOWN ON THE PLANS AND
 DESIGNATE WHICH DESIGN SPECIFICATION
 ("A" OR "B")OF THE FAIR HOUSING ACT IS
 BEING USED.
 ******NOTE:IF YOU CHOOSE SPECIFICATION
 "A"IT APPLIES TO ALL BATHROOMS IN THE
 DWELLING UNIT AND CLEAR FLOOR SPACE FOR
 FIXTURES SHALL COMPLY W/FIG.7(A),(B),(C)
 (D).IN SPECIFICATION"B"ONLY ONE BATHROOM
 IS REQD.TO COMPLY W/THE PROVISIONS OF
 THE ACT FOR MANEUVERING AND CLEAR FLOOR
 SPACE REQUIREMENTS AT FIXTURES.

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-07-27 Cont ID  
Sent By tlarge Date 1999-07-27 Time 11:20 Rev Time 1.25
Received By tlarge Date 1999-07-27 Time 11:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-27 Cont ID  
Sent By tlarge Date 1999-07-08 Time 16:20 Rev Time 11.00
Received By tlarge Date 1999-07-08 Time 16:20 Sent To  
Notes
2001-01-08 00:00:00SHT.P-5.-UNITS"A","B" & "C" CORRECTLY
 SIZE WATER LINES TO BATHROOM GROUPS.
 OMPLY W/COUNTYWIDE AMENDMENTS TO SPC
 SEC.607.7.
  
 SHT.P-6.-4" F.D. IN EMERG.GEN.ROOM
 REQUIRES VENT.COMPLY W/SPC TABLE 908.1.
  
 SHT.P-6.-FLOOR DRAIN IN TRASH ROOM
 REQUIRES VENT.COMPLY W/SPC TABLE 908.1.
  
 SHT.P-6.-STACKS #9,10,13,14,15,16,21,22,
 23,24,27,28.SIZE OF VERTICAL COMBINATION
 WASTE AND VENT SYSTEM SHALL COMPLY W/SPC
 SEC.911.4 AND TABLE 911.4 (BRANCH BEGINS
 AS 6" AND REDUCES TO 5".NOTE:PIPE SIZE
 TO REMAIN FULL SIZE THRU ROOF.)
  
 SHT.P-7.-WTR.HEATER DETAIL-PAN DRAIN BE
 MIN.OF 1" PER SPC SEC.507.8.2.
  
 NOTE ON PLAN THAT SHOWER VALVES COMPLY
 W/SPC TABLE 613.
  
 SHT.P-5.-SERVICE SINK ON GROUND FLR.
 SHALL BE VALVED PER SPC SEC.610.4.1.
  
 SIZE OF GREASE TRAP AND OIL/SAND
 INTERCEPTOR SHALL BE APPROVED BY CITY
 OF WEST PALM BEACH UTILITIES DEPT.
 CONTACT RODNEY COMPO AT(561)835-7423.
  
 RELIEF VENTS ARE REQ'D.IN THE DRAINAGE
 SYSTEM PER SPC SEC.916.
  
 SHT.A-3.-DISTANCE OF WATER SERVICE FROM
 BLDG.DRAIN OR SEWER SHALL COMPLY W/SPC
 SEC.608.3, 608.4.(NOTE AREAS AT GREASE
 TRAPS AND OIL /SAND INTERCEPTOR.
  
 SUBMIT PIPING ISOMETRIC FOR STORM
 DRAINAGE SYSTEM. SPC 104.2.1.
  
 SUBMIT RISER DIAGRAM FOR SUMP PUMP
 PIPING IN TRASH ROOM.COMPLY W/SPC SEC.
 717.
  
 SHOW DISTANCE OF INTERCEPTORS FROM
 BLDG.COMPLY W/STANDARD BLDG.CODE SEC.
 1803.1.3.FOR EXCAVATIONS.
  
 A COMPLETE GAS DRAWING SHALL BE
 SUBMITTED PRIOR TO ISSUANCE OF GAS
 PERMIT PER STANDARD GAS CODE SEC.104.2.1

Review Stop Z ZONING
Rev No 1 Status P Date 1999-08-02 Cont ID  
Sent By bstaples Date 1999-08-02 Time 07:40 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
***NONE***