Review Stop P PLUMBING
Rev No 1 Status P Date 1999-06-24 Cont ID  
Sent By tlarge Date 1999-06-23 Time 16:18 Rev Time 0.50
Received By tlarge Date 1999-06-23 Time 15:37 Sent To  
Notes
2001-01-08 00:00:00SUBMIT A WATER RISER DIAGRAM FOR REVIEW.
 SPC SEC.104.2.1,
  
 CLEARLY SHOW ON PLAN WHERE AND HOW
 EFFLUENT FROM EMERG.EYEWASH WILL BE
 DISPOSED.SPC 301.4, 301.11.1,& 301.11
 (DRAINAGE TO FLOOR W/O FLOOR DRAIN WILL
 CREATE A HAZARD.
 NOTE:PVC CANNOT BE USED FOR WATER DIST.
 PER SPC 611.2,611.3.