Plan Review Details - Permit 99060864
Plan Review Stops For Permit 99060864
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-01-13 Cont ID  
Sent By hpiskura Date 1999-08-05 Time 10:52 Rev Time 16.00
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2000-08-04 Cont ID  
Sent By jleahy Date 2000-08-04 Time 10:13 Rev Time 0.00
Received By jleahy Date 2000-09-11 Time 14:05 Sent To  
Notes
2001-01-08 00:00:001-PAGE ESP2 FPL SHOWS A 1.25" RACEWAY
 RISER SHOWS 2" RACEWAYWHICH ONE???
  
 2-LIGHTING CONTACTOR TO BE SERVICE RATED
  
 3-NO MAIN SHOWN, IF LIGHTING CONTACTOR
 IS TO BE USED THEN IT SHALL HAVE A
 MANUAL OVERRIDE FOR A DISCONNECT
  
 4-NO METER SHOWN, NOTE 2 STATES METER
 BY OWNER?

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-06-21 Cont ID  
Sent By jleahy Date 2000-06-21 Time 14:03 Rev Time 0.00
Received By jleahy Date 2000-09-11 Time 14:04 Sent To  
Notes
2001-01-08 00:00:001- PG.ESP2 HAS A DETAIL FOR A HOUSE PAN.
 THE DIAGRAM SHOWS NO MAIN OR METER.
 A PANEL SCHEDULE IS ALSO REQUIRED,AND
 THE LIGHTING CONTACTOR HAS TO BE RATE
 FOR USE AS SERVICE EQUIPMENT!!!!!!!!!
  
 2- PG.E-7 AS PER THE ORIGINAL NOTES FOR
 PAGE ME2 AND E-7 ATS1, AND ATS2 NEED
 TO HAVE DISCONNECTS INSTALLED UP ON
 THE MEZZ. LEVEL ON THE EMERGENCY SIDE
 OF THE TRANSFER SWITCHES!
  
 3- TRANSFORMER "TB" HAS A COMBINED LOAD
 OF 195.2 KVA FROM THE TWO PANELS IT
 FEEDS.TRANSFORMER IS ONLY 150 KVA?
 YOU NEED TO SHOW A LOAD CALCULATION
 THAT WILL ALLOW THIS!ALL THE LIGHTS
 ATTACHED TO THESE PANELS IS DONE AT
 100% AND NOT THE REQUIRED 125% THE
 CODE BOOK REQUIRES!!!!!!
  
 4- STILL HAVE NEVER RECEIVED A LOAD CALC
 ON THE GENERATOR AND THE TWO 800A
 MAINS?MDP-A, AND MDP-B!!!!!!!!!!!!
  
 5- ANY ADDITIONAL LOADS ADDED TO THESE
 PANELS AS DIRECTED ON THE DRAWINGS ON
 PG. E-6 WILL HAVE TO BE ADDED TO THE
 LOAD CALCULATION FOR THE BUILDING!!!

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-27 Cont ID  
Sent By jleahy Date 2000-03-27 Time 12:34 Rev Time 0.00
Received By jleahy Date 2000-09-11 Time 14:06 Sent To  
Notes
2001-01-08 00:00:001-NO MAIN SHOWN ON FIRE PUMP ON EMERGENC
 SIDE
 2-HIGH BAY LIGHT FIXTURES SHALL MEET
 410-30(C)

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-25 Cont ID  
Sent By jleahy Date 1999-10-25 Time 12:25 Rev Time 0.00
Received By jleahy Date 2000-09-11 Time 14:06 Sent To  
Notes
2001-01-08 00:00:001)THE 2 ATS'S NEED TO HAVE MEANS OF
 DISCONNECT AT THE TRANSFER SWITCH
 PER 225-8, AND 230-72
 (SUFFICIENTLY REMOTE FROM THE OTHER
 MAINS DOES NOT MEAN OUTSIDE BUILDING
 10'TO 15' IS REMOTE.
  
 2)MAINS ARE ABOVE THE OFFICE AREA.
 HOW ARE MAINS ACCESSED!
  
 3)MAINS ON THE SECOND FLOOR LIMIT YOU
 TOO 8' OF SERVICE ENTRANCE CONDUCTOR
 IN EACH SET, INSIDE THE BUILDING
  
 4)PANEL SCHEDULES R, R1, SB, IS1, AND
 IS2 ARE MISSING FROM THE DRAWINGS.
  
 5)PROVIDE THIS ADDITIONAL INFORMATION
 PRIOR TO FIRST ELECTRICAL INSPECTION

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2000-06-26 Cont ID  
Sent By mgonzale Date 2000-06-26 Time 14:27 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISO (SITE LIGHTING REV)
 WHEN INSTALLING LIGHTING CONDUIT PLEASE
 REFER TO KIMLEY HORN ENGINEERING PLAN
 TO IDENTIFY ALL UTILITIES.
 MUST CALL SUNSHINE LOCATION SERVICE
 48 HOURS PRIOR TO COMMENCEMENT
 LIGHT POLE DETAIL IS NOT SHOWN ON ANY
 SHEETS SUBMITTED BUT CONTRACTOR MUST
 COORDINATE WITH KIMLEY HORN ENGINEERING
 TO INSTALL CORRECT LIGHT POLE AS PER
 CITY OF WEST PALM BEACH REQUIREMENTS.
 IF ANY FURTHER QUESTIONS FEEL FREE TO
 CONTACT MANNY GONZALEZ AT PUBLIC UTILIT
 IES 561 659 8040 EXT. 2306

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-04-05 Cont ID  
Sent By mgonzale Date 2000-04-05 Time 12:23 Rev Time 4.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISOS
  
 1. PLACE VALVES ON STUBS
 2. HYDRANT LOCATIONS MUST BE APPROVED BY
 FIRE DEPARTMENT
 3. ANOTHER PLAN IS REQUIRED FOR WORK
 ALONG CONGRESS AVENUE.
  
 THESE SAME PLANS WHERE SUBMITTED FOR
 HEALTH DEPARTMENT APPROVAL ON 4-5-00

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-01-13 Cont ID  
Sent By lsmith Date 2000-01-13 Time 11:04 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER R. PITTMAN:SEE APPLICATION FOR NOTES
 NO OBJECTION WITH BUILDING PLAN WITHIN
 5' OF BUILDING FOOTPRINT EXCEPT AT TRUCK
 WELL WHERE WATER TABLE WILL SOMETIMES
 REACH 14.5' AND HEAVY DUTY SUMP PUIMP
 WILL BE NEEDED. (THESE ARE NOTES ON APP.
 RECORDED HERE BY LS 1/13/00

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2000-06-27 Cont ID  
Sent By mcarsill Date 2000-06-27 Time 14:30 Rev Time 0.45
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-03-29 Cont ID  
Sent By rturnque Date 2000-03-29 Time 14:20 Rev Time 0.45
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 1999-10-29 Cont ID  
Sent By rturnque Date 1999-10-29 Time 12:42 Rev Time 0.30
Received By rturnque Date 1999-10-29 Time 12:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-07-01 Cont ID  
Sent By bprusiec Date 1999-07-01 Time 15:12 Rev Time 0.00
Received By bprusiec Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2000-08-10 Cont ID  
Sent By cthirben Date 2000-08-10 Time 14:53 Rev Time 1.00
Received By cthirben Date 2000-08-10 Time 14:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2000-04-06 Cont ID  
Sent By ndenmark Date 2000-04-06 Time 14:07 Rev Time 0.50
Received By ndenmark Date 2000-04-06 Time 14:07 Sent To  
Notes
2001-01-08 00:00:00NO MECH REVISIONS TO REVIEW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-04-06 Cont ID  
Sent By ndenmark Date 1999-10-21 Time 13:45 Rev Time 0.50
Received By ndenmark Date 2000-04-06 Time 14:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-21 Cont ID  
Sent By ndenmark Date 1999-10-21 Time 13:41 Rev Time 1.00
Received By ndenmark Date 1999-10-21 Time 13:41 Sent To  
Notes
2001-01-08 00:00:00************DENIED/CORRECTED***********
 1) EXHAUST REQUIRED FROM JANITOR/UTILITY
 ROOM 1994 SMC 503.2
 2) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 3) PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1994 SMC 501.2
 JULY 10, 1999

Review Stop P PLUMBING
Rev No 7 Status P Date 2000-09-01 Cont ID  
Sent By pschmitz Date 2000-08-27 Time 10:10 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING REVIEW APPR.A/C CONDENSATE
 TIEING TO RWL DOWN SPOUT OUTSIDE OF THE
 BUILDING.PES 09-01-00

Review Stop P PLUMBING
Rev No 6 Status P Date 2000-08-10 Cont ID  
Sent By tlarge Date 2000-08-10 Time 21:05 Rev Time 0.33
Received By tlarge Date 2000-08-10 Time 20:44 Sent To  
Notes
2001-01-08 00:00:00REVISE DWV AT INTERCEPTOR.

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-06-05 Cont ID  
Sent By tlarge Date 2000-06-05 Time 16:41 Rev Time 1.75
Received By tlarge Date 2000-06-05 Time 16:41 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 DRY VENTS NOT PERMITTED PER SPC SEC.
 906.2.1.(SEE INTERCEPTOR).

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-04-24 Cont ID  
Sent By tlarge Date 2000-04-24 Time 11:23 Rev Time 1.25
Received By tlarge Date 2000-04-24 Time 11:23 Sent To  
Notes
2001-01-08 00:00:00REVISE IRRIG.,SAN.,DOMESTIC WATER.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-03-12 Cont ID  
Sent By tlarge Date 2000-03-12 Time 07:15 Rev Time 0.75
Received By tlarge Date 2000-03-12 Time 07:15 Sent To  
Notes
2001-01-08 00:00:00RELOCATE IRRIGATION PUMP,CONNECT TO
 WATER SERVICE.

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-10-01 Cont ID  
Sent By tlarge Date 1999-10-01 Time 18:36 Rev Time 2.50
Received By tlarge Date 1999-10-01 Time 18:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-07-10 Cont ID  
Sent By tlarge Date 1999-07-10 Time 14:23 Rev Time 8.00
Received By tlarge Date 1999-07-10 Time 14:22 Sent To  
Notes
2001-01-08 00:00:00SHTS.C-9 & C-10.-CLEANOUTS IN BLDG.
 SEWERS SHALL BE INSTALLED AND COMPLY W/
 STANDARD PLUMBING CODE SECS.710.2.4,
 711.2.2,711.2.3.
  
 SHT.C-11.-SUMP DETAIL SHALL COMPLY W/
 STD.PLBG.CODE SEC.717.2.(CONTINUATION
 F SUMP DISCHARGE IS SHOWN ON C-7,NOT
 C-4 AS NOTED.)CLARIFY SIZE OF DISCHARGE
 LINE.DETAIL SHOWS 6" & NOTE STATES 3".
  
 SHT.IR-4.-PLANS SHOW WATER SUPPLY FOR
 IRRIGATION SYSTEM FROM LAKE AND WELLS.
 SUBMIT COPY OF CONSUMPTIVE WATER USE
 PERMIT PER FLA.STATUTE 373.219.
  
 A WELL DRILLING PERMIT IS REQUIRED FROM
 SO.FLA.WATER MNGMT.DISTRICT FOR THE
 IRRIGATION WELLS PER FLA.STATUTE 373.342
  
 SHT.P1.1-VACUUM BREAKERS AND GATE VALVES
 ARE REQ'D.ON POLE HYDRANTS PER STD.PLBG.
 CODE SEC.606.3.4.1.,610.4.1,610.4.2.
  
 SHT.P1.1-DETAIL #3-WATER SUPPLY CONTROL
 SHALL COMPLY W/STD.PLBG.CODE SEC.610.4
  
 SHT.P1.1-WATER SUPPLY CONTROL FOR HOT
 WATER SHALL COMPLY W/STD.PLBG.CODE SEC.
 610.4.1.(CLARIFY 3/4" LINE SUPPLYING 1")
  
 SHT.P1.2-DETAIL#3-VENT SIZING DOESN'T
 COMPLY W/TABLE 920.2 OF STD.PLBG.CODE.
 (ALSO APPLIES TO SHT.1.1 DETAIL #2.)
  
 MIN.SIZE U/G DRAINAGE PIPE SHALL BE 2"
 PER STD.PLBG.CODE SEC.714.4 (SEE EEW ON
 SHT.P1.2 DETAIL#3).
  
 SUBMIT DETAIL OF INTERCEPTOR.COMPLY W/
 STD.PLBG.CODE SEC.1004.
  
 SUBMIT STORM/ROOF DRAINAGE RISER DIAGRAM
 INDICATE SQ.FOOTAGE DRAINED BY EA.DRAIN.
 COMPLY W/STD.PLBG.CODE SEC.1108,1109.
  
 INSTALLATION OF TRAP PRIMING DEVICES
 SHALL COMPLY W/STD.PLBG.CODE SEC.614.4.6
  
 SHT.P2.0-DETAIL#10.-FLOOR DRAIN IN PUMP
 ROOM IS NOT VENTED.COMPLY W/STD.PLBG.
 CODE SEC.908.1
  
 ROOF FAUCETS SHALL BE VALVED PER STD.
 PLBG.CODE SEC.610.4.1.

Review Stop REV REVISIONS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-27 Cont ID  
Sent By lsmith Date 1999-12-27 Time 08:32 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***