Plan Review Stops For Permit 99060864 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2000-01-13 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
1999-08-05 |
Time |
10:52 |
Rev Time |
16.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2000-08-04 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2000-08-04 |
Time |
10:13 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2000-09-11 |
Time |
14:05 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1-PAGE ESP2 FPL SHOWS A 1.25" RACEWAY | | RISER SHOWS 2" RACEWAYWHICH ONE??? | | | | 2-LIGHTING CONTACTOR TO BE SERVICE RATED | | | | 3-NO MAIN SHOWN, IF LIGHTING CONTACTOR | | IS TO BE USED THEN IT SHALL HAVE A | | MANUAL OVERRIDE FOR A DISCONNECT | | | | 4-NO METER SHOWN, NOTE 2 STATES METER | | BY OWNER? |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2000-06-21 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2000-06-21 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2000-09-11 |
Time |
14:04 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1- PG.ESP2 HAS A DETAIL FOR A HOUSE PAN. | | THE DIAGRAM SHOWS NO MAIN OR METER. | | A PANEL SCHEDULE IS ALSO REQUIRED,AND | | THE LIGHTING CONTACTOR HAS TO BE RATE | | FOR USE AS SERVICE EQUIPMENT!!!!!!!!! | | | | 2- PG.E-7 AS PER THE ORIGINAL NOTES FOR | | PAGE ME2 AND E-7 ATS1, AND ATS2 NEED | | TO HAVE DISCONNECTS INSTALLED UP ON | | THE MEZZ. LEVEL ON THE EMERGENCY SIDE | | OF THE TRANSFER SWITCHES! | | | | 3- TRANSFORMER "TB" HAS A COMBINED LOAD | | OF 195.2 KVA FROM THE TWO PANELS IT | | FEEDS.TRANSFORMER IS ONLY 150 KVA? | | YOU NEED TO SHOW A LOAD CALCULATION | | THAT WILL ALLOW THIS!ALL THE LIGHTS | | ATTACHED TO THESE PANELS IS DONE AT | | 100% AND NOT THE REQUIRED 125% THE | | CODE BOOK REQUIRES!!!!!! | | | | 4- STILL HAVE NEVER RECEIVED A LOAD CALC | | ON THE GENERATOR AND THE TWO 800A | | MAINS?MDP-A, AND MDP-B!!!!!!!!!!!! | | | | 5- ANY ADDITIONAL LOADS ADDED TO THESE | | PANELS AS DIRECTED ON THE DRAWINGS ON | | PG. E-6 WILL HAVE TO BE ADDED TO THE | | LOAD CALCULATION FOR THE BUILDING!!! |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2000-03-27 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2000-03-27 |
Time |
12:34 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2000-09-11 |
Time |
14:06 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1-NO MAIN SHOWN ON FIRE PUMP ON EMERGENC | | SIDE | | 2-HIGH BAY LIGHT FIXTURES SHALL MEET | | 410-30(C) |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
1999-10-25 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
1999-10-25 |
Time |
12:25 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2000-09-11 |
Time |
14:06 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1)THE 2 ATS'S NEED TO HAVE MEANS OF | | DISCONNECT AT THE TRANSFER SWITCH | | PER 225-8, AND 230-72 | | (SUFFICIENTLY REMOTE FROM THE OTHER | | MAINS DOES NOT MEAN OUTSIDE BUILDING | | 10'TO 15' IS REMOTE. | | | | 2)MAINS ARE ABOVE THE OFFICE AREA. | | HOW ARE MAINS ACCESSED! | | | | 3)MAINS ON THE SECOND FLOOR LIMIT YOU | | TOO 8' OF SERVICE ENTRANCE CONDUCTOR | | IN EACH SET, INSIDE THE BUILDING | | | | 4)PANEL SCHEDULES R, R1, SB, IS1, AND | | IS2 ARE MISSING FROM THE DRAWINGS. | | | | 5)PROVIDE THIS ADDITIONAL INFORMATION | | PRIOR TO FIRST ELECTRICAL INSPECTION |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
3 |
Status |
P |
Date |
2000-06-26 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2000-06-26 |
Time |
14:27 |
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PASSED WITH PROVISO (SITE LIGHTING REV) | | WHEN INSTALLING LIGHTING CONDUIT PLEASE | | REFER TO KIMLEY HORN ENGINEERING PLAN | | TO IDENTIFY ALL UTILITIES. | | MUST CALL SUNSHINE LOCATION SERVICE | | 48 HOURS PRIOR TO COMMENCEMENT | | LIGHT POLE DETAIL IS NOT SHOWN ON ANY | | SHEETS SUBMITTED BUT CONTRACTOR MUST | | COORDINATE WITH KIMLEY HORN ENGINEERING | | TO INSTALL CORRECT LIGHT POLE AS PER | | CITY OF WEST PALM BEACH REQUIREMENTS. | | IF ANY FURTHER QUESTIONS FEEL FREE TO | | CONTACT MANNY GONZALEZ AT PUBLIC UTILIT | | IES 561 659 8040 EXT. 2306 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2000-04-05 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2000-04-05 |
Time |
12:23 |
Rev Time |
4.00 |
Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PASSED WITH PROVISOS | | | | 1. PLACE VALVES ON STUBS | | 2. HYDRANT LOCATIONS MUST BE APPROVED BY | | FIRE DEPARTMENT | | 3. ANOTHER PLAN IS REQUIRED FOR WORK | | ALONG CONGRESS AVENUE. | | | | THESE SAME PLANS WHERE SUBMITTED FOR | | HEALTH DEPARTMENT APPROVAL ON 4-5-00 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2000-01-13 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2000-01-13 |
Time |
11:04 |
Rev Time |
0.50 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PER R. PITTMAN:SEE APPLICATION FOR NOTES | | NO OBJECTION WITH BUILDING PLAN WITHIN | | 5' OF BUILDING FOOTPRINT EXCEPT AT TRUCK | | WELL WHERE WATER TABLE WILL SOMETIMES | | REACH 14.5' AND HEAVY DUTY SUMP PUIMP | | WILL BE NEEDED. (THESE ARE NOTES ON APP. | | RECORDED HERE BY LS 1/13/00 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2000-06-27 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-06-27 |
Time |
14:30 |
Rev Time |
0.45 |
Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2000-03-29 |
|
|
Cont ID |
|
Sent By |
rturnque |
Date |
2000-03-29 |
Time |
14:20 |
Rev Time |
0.45 |
Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
1999-10-29 |
|
|
Cont ID |
|
Sent By |
rturnque |
Date |
1999-10-29 |
Time |
12:42 |
Rev Time |
0.30 |
Received By |
rturnque |
Date |
1999-10-29 |
Time |
12:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
1999-07-01 |
|
|
Cont ID |
|
Sent By |
bprusiec |
Date |
1999-07-01 |
Time |
15:12 |
Rev Time |
0.00 |
Received By |
bprusiec |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2000-08-10 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-08-10 |
Time |
14:53 |
Rev Time |
1.00 |
Received By |
cthirben |
Date |
2000-08-10 |
Time |
14:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
N |
Date |
2000-04-06 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-04-06 |
Time |
14:07 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
2000-04-06 |
Time |
14:07 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | NO MECH REVISIONS TO REVIEW |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2000-04-06 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
1999-10-21 |
Time |
13:45 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
2000-04-06 |
Time |
14:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
1999-10-21 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
1999-10-21 |
Time |
13:41 |
Rev Time |
1.00 |
Received By |
ndenmark |
Date |
1999-10-21 |
Time |
13:41 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ************DENIED/CORRECTED*********** | | 1) EXHAUST REQUIRED FROM JANITOR/UTILITY | | ROOM 1994 SMC 503.2 | | 2) PROVIDE OUTSIDE AIR CALCULATIONS PER | | ASHRAE 62-89 | | 3) PROVIDE AIR BALANCE SCHEDULE TO SHOW | | COMPLIANCE WITH 1994 SMC 501.2 | | JULY 10, 1999 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
7 |
Status |
P |
Date |
2000-09-01 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2000-08-27 |
Time |
10:10 |
Rev Time |
0.75 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PLUMBING REVIEW APPR.A/C CONDENSATE | | TIEING TO RWL DOWN SPOUT OUTSIDE OF THE | | BUILDING.PES 09-01-00 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
P |
Date |
2000-08-10 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-08-10 |
Time |
21:05 |
Rev Time |
0.33 |
Received By |
tlarge |
Date |
2000-08-10 |
Time |
20:44 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REVISE DWV AT INTERCEPTOR. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2000-06-05 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-06-05 |
Time |
16:41 |
Rev Time |
1.75 |
Received By |
tlarge |
Date |
2000-06-05 |
Time |
16:41 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ******************PROVISO*************** | | DRY VENTS NOT PERMITTED PER SPC SEC. | | 906.2.1.(SEE INTERCEPTOR). |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2000-04-24 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-04-24 |
Time |
11:23 |
Rev Time |
1.25 |
Received By |
tlarge |
Date |
2000-04-24 |
Time |
11:23 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REVISE IRRIG.,SAN.,DOMESTIC WATER. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2000-03-12 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-03-12 |
Time |
07:15 |
Rev Time |
0.75 |
Received By |
tlarge |
Date |
2000-03-12 |
Time |
07:15 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | RELOCATE IRRIGATION PUMP,CONNECT TO | | WATER SERVICE. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
1999-10-01 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-10-01 |
Time |
18:36 |
Rev Time |
2.50 |
Received By |
tlarge |
Date |
1999-10-01 |
Time |
18:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
1999-07-10 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-07-10 |
Time |
14:23 |
Rev Time |
8.00 |
Received By |
tlarge |
Date |
1999-07-10 |
Time |
14:22 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SHTS.C-9 & C-10.-CLEANOUTS IN BLDG. | | SEWERS SHALL BE INSTALLED AND COMPLY W/ | | STANDARD PLUMBING CODE SECS.710.2.4, | | 711.2.2,711.2.3. | | | | SHT.C-11.-SUMP DETAIL SHALL COMPLY W/ | | STD.PLBG.CODE SEC.717.2.(CONTINUATION | | F SUMP DISCHARGE IS SHOWN ON C-7,NOT | | C-4 AS NOTED.)CLARIFY SIZE OF DISCHARGE | | LINE.DETAIL SHOWS 6" & NOTE STATES 3". | | | | SHT.IR-4.-PLANS SHOW WATER SUPPLY FOR | | IRRIGATION SYSTEM FROM LAKE AND WELLS. | | SUBMIT COPY OF CONSUMPTIVE WATER USE | | PERMIT PER FLA.STATUTE 373.219. | | | | A WELL DRILLING PERMIT IS REQUIRED FROM | | SO.FLA.WATER MNGMT.DISTRICT FOR THE | | IRRIGATION WELLS PER FLA.STATUTE 373.342 | | | | SHT.P1.1-VACUUM BREAKERS AND GATE VALVES | | ARE REQ'D.ON POLE HYDRANTS PER STD.PLBG. | | CODE SEC.606.3.4.1.,610.4.1,610.4.2. | | | | SHT.P1.1-DETAIL #3-WATER SUPPLY CONTROL | | SHALL COMPLY W/STD.PLBG.CODE SEC.610.4 | | | | SHT.P1.1-WATER SUPPLY CONTROL FOR HOT | | WATER SHALL COMPLY W/STD.PLBG.CODE SEC. | | 610.4.1.(CLARIFY 3/4" LINE SUPPLYING 1") | | | | SHT.P1.2-DETAIL#3-VENT SIZING DOESN'T | | COMPLY W/TABLE 920.2 OF STD.PLBG.CODE. | | (ALSO APPLIES TO SHT.1.1 DETAIL #2.) | | | | MIN.SIZE U/G DRAINAGE PIPE SHALL BE 2" | | PER STD.PLBG.CODE SEC.714.4 (SEE EEW ON | | SHT.P1.2 DETAIL#3). | | | | SUBMIT DETAIL OF INTERCEPTOR.COMPLY W/ | | STD.PLBG.CODE SEC.1004. | | | | SUBMIT STORM/ROOF DRAINAGE RISER DIAGRAM | | INDICATE SQ.FOOTAGE DRAINED BY EA.DRAIN. | | COMPLY W/STD.PLBG.CODE SEC.1108,1109. | | | | INSTALLATION OF TRAP PRIMING DEVICES | | SHALL COMPLY W/STD.PLBG.CODE SEC.614.4.6 | | | | SHT.P2.0-DETAIL#10.-FLOOR DRAIN IN PUMP | | ROOM IS NOT VENTED.COMPLY W/STD.PLBG. | | CODE SEC.908.1 | | | | ROOF FAUCETS SHALL BE VALVED PER STD. | | PLBG.CODE SEC.610.4.1. |
|
|
Review Stop |
REV |
REVISIONS |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
1999-12-27 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
1999-12-27 |
Time |
08:32 |
Rev Time |
1.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|