Plan Review Details - Permit 99060774
Plan Review Stops For Permit 99060774
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-21 Cont ID  
Sent By dpalmer Date 1999-06-21 Time 16:33 Rev Time 0.00
Received By dpalmer Date 1999-06-21 Time 16:33 Sent To  
Notes
2001-01-08 00:00:00WIRE ON PANEL SCHD. FOR 10KW HEAT
 NOT RATED.#14
 FAN CIRCUT WIRE ALSO NOT RATED FOR 20A
 BRK.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-29 Cont ID  
Sent By cthirben Date 2000-03-29 Time 07:36 Rev Time 0.00
Received By cthirben Date 2000-03-29 Time 07:42 Sent To  
Notes
2001-01-08 00:00:00 
  
 *****************PROVISO****************
  
 1. RETURN AIR SHOULD NOT BE INSTALL IN
 GARAGE.NEEDS TO BE RELOCATED.
  
 2. A/C DROP REQUIRED IN POWDER ROOM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-08-17 Cont ID  
Sent By jleech Date 1999-07-10 Time 09:01 Rev Time 0.00
Received By cthirben Date 2000-03-29 Time 07:25 Sent To  
Notes
2001-01-08 00:00:001.ENERGY CALKS CALL FOR 14 SEER. A/C
 PLAN SHOWS ONE 14 SEER AND ONE 12 SEER.
 2.DROP MISSING IN POWDER ROOM.
 3.TOTAL CFMS. WITHOUT POWDER ROOM IS
 2040. A/H CAPACITY IS 2000.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-02-20 Cont ID  
Sent By tlarge Date 2000-02-20 Time 13:47 Rev Time 0.20
Received By tlarge Date 2000-02-20 Time 13:47 Sent To  
Notes
2001-01-08 00:00:00REVISED SANITARY RISER.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-08-18 Cont ID  
Sent By fknapp Date 1999-08-18 Time 15:44 Rev Time 0.00
Received By fknapp Date 1999-08-18 Time 15:46 Sent To  
Notes
2001-01-08 00:00:00APPROVED BY TIM LARGE

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-08-19 Cont ID  
Sent By fknapp Date 1999-08-19 Time 12:59 Rev Time 4.00
Received By fknapp Date 1999-08-18 Time 15:48 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1)PROVIDE CURRENT PRODUCT APPROVAL FOR
 ENTEGRA ROOF TILE
 SH-7500 ALUMINUM SINGLE HUNG WINDOW
 ALUMINUM TUBE MULLIONS
  
 2)PROVIDE SOIL REPORT
  
 CITY AMENDMENTS 104.2.2
 SUBMIT PRIOR TO FIRST INSPECTION
  
 SBC 1012.1.1 ENTRY DOOR AND GUEST HOUSE
 DOOR MUST HAVE 32" CLEAR OPENING

Review Stop Z ZONING
Rev No 1 Status P Date 1999-06-11 Cont ID  
Sent By gjoyce Date 1999-06-11 Time 13:48 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***