Plan Review Details - Permit 99060720
Plan Review Stops For Permit 99060720
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2001-05-18 Cont ID  
Sent By lmartine Date 2001-05-18 Time 09:02 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-03-02 Cont ID  
Sent By lmartine Date 2001-03-02 Time 06:53 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-03-02 00:00:00APPROVE NEW STAIR AT REAR OF BUILDING

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-01-18 Cont ID  
Sent By jwitmer Date 2001-01-18 Time 11:13 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-18 00:00:00SBC 104.2.2- ADDITIONAL INFORMATION
 REQUESTED, SHOP DRAWINGS OF STAIRS,
 SHOW ATTACHMENT TO FOUNDATION & STRUC-
 TURE.
  
 SHEET A-4 NORTH ELEVATION- SECOND FLOOR
 WINDOW & FIRST FLOOR FRENCH DOORS THAT
 DO NOT SHOW A 3/4 HR. RATING WILL
 REQUIRE APPROVED OPENING PROTECTION AS
 PER SBC 1006.2.4/1011.2.3.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-11-06 Cont ID  
Sent By lmartine Date 2000-11-06 Time 15:54 Rev Time 0.00
Received By wlehnhar Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISION NOTES
 ----------------
  
 EXTERIOR STAIR
 1]
 STAIR SHALL BE PROTECTED FROM ADJACENT
 PROPERTY,SEE SECTION 1006.2.2 SBC.
 {SEE ATTACHED COPY}
  
 2]
 PROVIDE CONNECTION DETAIL FOR STAIR AND
 BUILDING TIE IN.
  
 3]
 SUBMIT HANDRAIL,GUARDRAIL DETAILS.
  
 4]
 LANDINGS SHALL COMPLY WITH 1007.4 SBC
 {48" OR EQUAL TO WIDTH OF STAIRS}
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 659-8096
 EXT. 8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-10-24 Cont ID  
Sent By lmartine Date 2000-10-24 Time 07:00 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISION NOT APPROVED
  
 PLANS ARE NOT CLEAR AS TO WHAT HAPPENED
 TO THE REAR ADDITION.
  
 PROVIDE SECOND SET OF ARCH. AND STRUCT.
 PAGES.
  
 STRUCTURAL NOTES,ASCE7-93 AND SBC1994
 ARE NOT CURRENT.
  
 SUBMIT MANUFACTURES SPECIFICATIONS FOR
 1HR. GLASS BLOCK.
  
 SUBMIT DETAILS FOR NEW STEEL STAIRS AT
 REAR,DETAILS FOR NEW TRELLIS ON SECOND
 FLOOR ROOF.
  
 REVIEWED BY:
 LUIS MARTINEZ
 659 8096
 EXT. 8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-08-05 Cont ID  
Sent By lmartine Date 1999-07-14 Time 17:45 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By dpalmer Date 2001-03-29 Time 19:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2001-02-28 Cont ID  
Sent By dpalmer Date 2001-02-28 Time 17:52 Rev Time 0.00
Received By dpalmer Date 2001-02-28 Time 17:52 Sent To  
Notes
2001-02-28 00:00:00***************** UNSAT ***************
  
 1)NOTE: SAME NOTES FROM REVIEW ON
 1/17/01.
  
 ALL BRANCH CIRCUITS ARE TO BE LABELED ON
  
 PLANS. CIRCUIT #`S ARE TO CORRELATE W/
 PANEL SCHEDULES.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2001-01-17 Cont ID  
Sent By dpalmer Date 2001-01-17 Time 20:44 Rev Time 0.00
Received By dpalmer Date 2001-01-17 Time 10:46 Sent To  
Notes
2001-01-17 00:00:00******************* UNSAT **************
  
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 ~#SON PLANS AND CORRELATE WITH PANEL
 SCHEDULE. PLEASE NOTE THAT OUTLETS ARE
 SHOWN ON PLANS WITH NO CIRCUIT #`S??
 IF OUTLETS BOXES ARE FOR FUTURE? THEN
 STILL MUST HAVE OUTLETS THAT MEET LOCAL
 CODE OF 210-50. PALM BCH COUNTY
 AMENDMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-19 Cont ID  
Sent By dpalmer Date 2000-09-19 Time 20:12 Rev Time 0.00
Received By dpalmer Date 2000-09-19 Time 20:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-25 Cont ID  
Sent By dpalmer Date 2000-03-25 Time 19:15 Rev Time 0.00
Received By dpalmer Date 2000-03-25 Time 19:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-07-13 Cont ID  
Sent By lmartine Date 1999-07-13 Time 17:46 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2001-02-22 Cont ID  
Sent By mcarsill Date 2001-02-22 Time 15:48 Rev Time 0.00
Received By mcarsill Date 2001-02-22 Time 15:48 Sent To  
Notes
2001-02-22 00:00:001) EXTERIOR STAIRS TO BE SLIP RESISTANT
 TO PREVENT ACCIDENTS FROM INCLEMENT
 WEATHER.
 2) THE FIRE RATED WINDOWS AND DOORS
 WHEN INSTALLED MUST BE LABELED AND
 BE INSTALLED IN ACCORDANCE WITH
 NFPA 80, FIRE DOORS AND WINDOWS.
 STAIRS AND FIRE RATED WINDOWS AFTER
 INSTALLATION ARE TO BE INSPECTED BY
 CONSTRUCTION SERVICES AND FIRE RESCUE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2001-01-26 Cont ID  
Sent By mcarsill Date 2001-01-26 Time 09:16 Rev Time 0.00
Received By mcarsill Date 2001-01-26 Time 09:16 Sent To  
Notes
2001-01-26 00:00:001) PLEASE PROVIDE INFORMATION ON HOW THE
 STAIR WILL BE CONNECTED AND SUPPORTED.
 2) PLEASE PROVIDE PRODUCT INFORMATION
 ON THE RATED FIRE DOORS AND WINDOWS
 THAT ARE PLANNED FOR THE SITE.
 3) PLEASE SUBMIT SHOP DRAWINGS FOR
 STAIR.
 4) THE BUILDING WILL REQUIRE A FIRE
 ALARM SYSTEM. SEPARATE PLANS AND PERMIT
 REQUIRED PRIOR TO STARTING WORK.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2000-11-03 Cont ID  
Sent By mcarsill Date 2000-11-02 Time 19:00 Rev Time 0.00
Received By mcarsill Date 2000-11-02 Time 19:00 Sent To  
Notes
2001-01-08 00:00:00THIS PLAN REVIEW WAS FOR THE EXIT STAIRS
 PLANNED FOR THE SOUTH SIDE OF THE
 BUILDING.
  
 1) PLEASE PROVIDE DETAILS ON FIRE RATED
 WINDOWS AND FRAMES TO THIS OFFICE.
 2) STAIRS ARE TO BE SLIP RESISTANT.
 3) STAIRS TO MEET ALL OF THE
 REQUIREMENTS FOR NEW STAIRS PER NFPA
 101, THE LIFE SAFETY CODE, 1985
 EDITION. THE STAIRS ARE ALLOWED TO BE
 36" WIDE BASED ON OCCUPANT LOADS OF
 LESS THAN 50 PERSONS.
 4) PLEASE SUBMIT SHOP DRAWINGS FOR THE
 STAIRS.
 5) ANY AND ALL OPENINGS WITHIN 10 FEET
 OF THE STAIRS ARE TO BE PROTECTED BY
 FIRE RATED WINDOWS AND DOORS.
 6) HOW IS STAIR SUPPORTED AND FASTENED
 TO THE BUILDING.
 7) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, THE LIFE SAFETY CODE,1985
 EDITION.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-10-03 Cont ID  
Sent By mcarsill Date 2000-10-03 Time 11:32 Rev Time 0.00
Received By mcarsill Date 2000-10-03 Time 11:32 Sent To  
Notes
2001-01-08 00:00:001) NO SECOND MEANS OF EGRESS SHOWN FROM
 THIRD FLOOR. PLEASE PROVIDE A SECOND
 MEANS OF EGRESS FROM THE THIRD FLOOR.
 SEVERAL TELEPHONE CONVERSATIONS HAVE
 OCCURRED WITH THE OWNER AND AT LEAST
 TWO MEETINGS HAVE TAKEN PLACE TO
 DISCUSS THIS MATTER.
 2) PLANS DO NOT SHOW EXIT SIGNS OR
 EMERGENCY LIGHTING EQUIPMENT.
 3) PLANS DO NOT SHOW RATED WALLS OR
 RATED DOORS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-07-13 Cont ID  
Sent By lmartine Date 1999-07-13 Time 17:46 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2001-08-07 Cont ID  
Sent By pkrauss Date 2001-08-07 Time 15:47 Rev Time 0.30
Received By pkrauss Date 2001-08-07 Time 15:47 Sent To  
Notes
2001-08-07 00:00:00AS BUILT DRAWING.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-04-27 Cont ID  
Sent By pkrauss Date 2001-04-27 Time 11:29 Rev Time 0.35
Received By pkrauss Date 2001-04-27 Time 11:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By ndenmark Date 2001-01-24 Time 09:40 Sent To  
Notes
2001-01-24 00:00:00REVISION DATED 12-10-00 AS SHOWN M-1,
 M-2 AND M-3

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-10-03 Cont ID  
Sent By ndenmark Date 2000-10-03 Time 13:54 Rev Time 0.50
Received By ndenmark Date 2000-10-03 Time 13:54 Sent To  
Notes
2001-01-08 00:00:00THIS MECH APPROVAL IS FOR FUTURE A/C
 EQUIPMENT AND HAS NOT BEEN REVIEWED FOR
 OUTSIDE AIR REQUIREMENTS OR FAN SHUT
 DOWN REQUIREMENTS THIS IS FOR EXHAUST
 FANS AND RELATED DUCT AS SHOWN ON M-1
 M-2 AND M-3 DATED JUNE 8, 2000

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-14 Cont ID  
Sent By cthirben Date 2000-03-14 Time 15:32 Rev Time 1.00
Received By cthirben Date 2000-03-14 Time 15:27 Sent To  
Notes
2001-01-08 00:00:00NO A/C PLAN SUBMITTED FOR REVIEW
 MECHANICAL PLANS TO BE SUBMITTED AT TIME
 OF APPLICATION
 * LOOK FOR FIRE RATED WALLS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 1999-06-14 Cont ID  
Sent By ndenmark Date 1999-06-14 Time 11:47 Rev Time 0.33
Received By ndenmark Date 1999-06-14 Time 11:47 Sent To  
Notes
2001-01-08 00:00:00NO A/C PLANS INCLUDED FOR PLAN REVIEW
 SUBMIT MECHANICAL PLANS AT TIME OF MECH
 PERMIT APPLICATION LOOK FOR RATED WALLS

Review Stop P PLUMBING
Rev No 8 Status P Date 2001-04-30 Cont ID  
Sent By jleech Date 2001-04-30 Time 17:12 Rev Time 1.00
Received By jleech Date 2001-04-30 Time 17:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 7 Status F Date 2001-03-20 Cont ID  
Sent By jleech Date 2001-03-20 Time 09:53 Rev Time 1.00
Received By jleech Date 2001-03-20 Time 09:53 Sent To  
Notes
2001-03-20 00:00:00MINIMUM PLUMBING FIXTURES SHOULD BE FROM
 THE 94 SPC NOT THE 97. MINIMUM BATHROOM
 FACILITYS FOR FEMALES IS 2 W/C AND 2 LAV
 TABLE 407.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 6 Status F Date 2001-02-27 Cont ID  
Sent By jleech Date 2001-02-27 Time 17:55 Rev Time 1.50
Received By jleech Date 2001-02-27 Time 17:55 Sent To  
Notes
2001-02-27 00:00:00DENIED;
  
 1. MINIMUM PLUMBING FICTURES NOT MET.
 94 SPC 407.
 BATHROOM FIXTURES REQUIRED ON ALL
 FLOORS AS SHOWN ON ORIGINAL PLANS.
  
 2.P-4 WATER RISER SHOWS BATHROOMS ON
 SECOND FLOOR. WHATS UP?
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 5 Status F Date 2001-01-19 Cont ID  
Sent By jleech Date 2001-01-19 Time 11:47 Rev Time 2.50
Received By jleech Date 2001-01-19 Time 11:47 Sent To  
Notes
2001-01-19 00:00:00DENIED;
  
 THE FOLLOWING REVIEW NOTES FROM
 TIMOTHY LARGE HAVE NOT BEEN ADDRESSED.
  
 1.SUBMIT SQUIRE FOOTAGE OF SPACE FOR
 OCCUPANT LOAD TO ENSURE COMPLIANCE
 WITH SPC TABLE 407. SEE SPC SEC.
 407.1.3 FOR ALLOWABLE DEDUCTIBLE AREAS
  
 2.SHOW DIMENSIONS OF TOILET ROOMS COMPLY
 WITH FIG. 28 OFSACBC AND SHOW REQUIRED
 WHEELCHAIR TURNING SPACE IN TOILET
 ROOMS PER FACBC SEC. 4.2.3.
  
 3.SHOW FIXTURE CLEARANCES FOR HANDICAP
 FIXTURES PER SACBC SEE SEC. 4.15-4.19.
  
 4.URINAL SHALL BE INSTALLED AT HANDICAP
 HEIGHT AND COMPLY WITH SACBC SEC. 4.18.
 SHOW DETAILS OF ON DRAWINGS.
  
 5.A MAX. OF 4 FIXTURE UNITS ARE
 PERMITTED ON WET VENTS PER SPC 911.1
 (SEE URINAL / LAV.)
 SHTS. P-1 AND P-2 WHERE NOT WITH PLANS
  
 6.INDICATE SLOPE OF STORMWATER PIPING ON
 PLAN. COMPLY WITH TABLES 1108.1 AND
 1108.2 OF SPC.
  
 NOTE ON PAGE A-1 (PLUMBING ROUGH HAS
 BEEN INSTALLED) DOES NOT ALLOW
 CONTRACTOR TO CIRCUMVENT CODES.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-09-16 Cont ID  
Sent By tlarge Date 2000-09-16 Time 05:47 Rev Time 1.00
Received By tlarge Date 2000-09-16 Time 05:23 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT SQUARE FOOTAGE OF SPACE FOR
 OCCUPANT LOAD TO ENSURE COMPLIANCE WITH
 SPC TABLE 407.SEE SPC SEC.407.1.3.FOR
 ALLOWED DEDUCTIBLE AREAS.
  
 2)SHOW DIMENSIONS OF TOILET ROOMS.COMPLY
 W/FIG.28 OF FACBC AND SHOW REQD.WHEEL-
 CHAIR TURNING SPACE IN TOILET ROOMS PER
 FACBC SEC.4.2.3.
  
 3)SHOW FIXTURE CLEARANCES FOR HANDICAP
 FIXTURES PER FACBC.SEE SECS.4.15-4.19.
  
 4)URINAL SHALL BE INSTALLED AT H.C.
 HEIGHT AND COMPLY W/FACBC SEC.4.18.
  
 5)A MAX.OF 4 FIXTURE UNITS ARE PERMITTED
 ON WET VENTS PER SPC 911.1(SEE URINAL/
 LAV.)
  
 6)SHOW COMPLETE SIZE OF SCUPPERS AND
 SUBMIT DETAIL.COMPLY W/SPC APPENDIX"A"
 FOR SECONDARY DRAINAGE REQS.
  
 7)INDICATE SLOPE OF STORMWATER PIPING ON
 PLAN.COMPLY W/TABLES 1108.1 & 1108.2 OF
 SPC.
  
 8)ROOF DRAINAGE CALCULATIONS SHALL
 INCLUDE 1/2 THE AREA OF ANY VERTICAL
 WALLPER SPC SEC.1108.3.
  
 9)A DRINKING FOUNTAIN IS REQD.ON THE 2ND
 FLOOR PER SPC TABLE 407.
  
 10)COMPILE PLANS INTO 2 SETS.IT APPEARS
 THE ARCH. DRAWINGS ARE ONLY IN ONE SET.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 11)VOID OLD PLUMBING SHEETS.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-03-18 Cont ID  
Sent By tlarge Date 2000-03-18 Time 06:54 Rev Time 1.00
Received By tlarge Date 2000-03-18 Time 06:53 Sent To  
Notes
2001-01-08 00:00:00SHOW SQ.FOOTAGE OF SPACE FOR OCCUPANT
 LOAD TO ENSURE COMPLIANCE W/SPC TABLE
 407.SHT.A-1 SHOWS FUTURE FIXTURES.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A),4.15.CLEARLY SHOW
 COMPLIANCE W/ABOVE NOTED CODE SECS.ON
 THE PLANS.
  
 SHOW DIMENSIONS OF TOILET ROOMS.COMPLY
 W/FIG.28 OF FACBC AND SHOW REQD.WHEEL-
 CHAIR TURNING SPACE IN TOILET ROOMS PER
 FACBC SEC.4.2.3.
  
 3" SOIL/WASTE STACKS TO UPPER FLOORS MAY
 BE UNDERSIZED FOR FUTURE BUILDOUT PER
 SPC TABLES 714.1,714.2.
  
 SHOW FIXTURE CLEARANCES FOR H.C.FIXTURES
 PER FACBC.
  
 URINAL SHALL BE INSTALLED AT H.C.HEIGHT
 AND COMPLY W/FACBC SEC.4.18.

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-07-28 Cont ID  
Sent By pschmitz Date 1999-07-28 Time 07:41 Rev Time 1.00
Received By kstevens Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO
 (1) WATER HEATER TP 3/4", PAN DRAIN 1"
 RUN SEPERATELY TO THE OUT SIDE 6"
 ABOVE GRADE.SEC.507.8.4&507.8.2.
 (2) ALL PUBLIC REST RM'S TO HAVE HOT
 WATERFEC 97 SEC412.1 ABD.2.3.2
 (3) REVISIONS TO FOLLOW AS PER
 JAY SAUNDRERS ARCH.
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-08-05 Cont ID  
Sent By tlarge Date 1999-07-13 Time 13:01 Rev Time 1.00
Received By sgraham Date 1999-08-05 Time 11:07 Sent To  
Notes
2001-01-08 00:00:00INSTALLATION OF HANDICAP PLBG.FIXTURES
 SHALL COMPLY W/F.A.C.B.C.1997 EDITION.
  
 SIZE OF HANDICAP STALLS IN RESTROOMS
 SHALL COMPLY W/F.A.C.B.C.SEC.4.17.3.1997
 EDITION.(SEE EXCEPTION:NEW CONSTRUCTION)
  
 INDICATE OCCUPANT LOAD ON PLAN TO
 DETERMINE MIN.PLBG.FIXTURE REQ'S.PER
 SEC.407 AND TABLE 407 OF STD.PLBG.CODE.
  
 SUBMIT SANITARY AND WATER ISOMETRICS
 THAT REFLECT ENTIRE SCOPE OF PLBG.WORK
 TO BE DONE PER SPC SEC.104.2.1.
  
 FLOOR DRAINS ARE REQ'D.IN TOILET ROOMS
 PER SPC SEC.409.4.1.1.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-07-19 Cont ID  
Sent By gjoyce Date 1999-07-19 Time 10:20 Rev Time 0.75
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***