Plan Review Details - Permit 99060166
Plan Review Stops For Permit 99060166
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-16 Cont ID  
Sent By dpalmer Date 1999-06-16 Time 16:51 Rev Time 0.00
Received By dpalmer Date 1999-06-16 Time 16:50 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
  
 NOTE:NEED TO SUBMIT PLANS WITH AIC
 RATING DERIVED FROM FAULT CURRENT
 CALCULATIONS.215-5
 NOTE:RECEPTS.SERVING KITCHEN COUNTER
 SPACE ARE TO BE GFI/GFI PROTECTED.
 ART.210-8-A-6
 NOTE:GROUNDING ELECTRODE CONDUCTOR
 ALSO CONNECTED TO BLDG.STEEL.
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:REQ`D RECEPTS.MISSING.210-52A
  
 NEED TO SUBMIT REVISED PLANS BEFORE
 ROUGH INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-01 Cont ID  
Sent By ndenmark Date 1999-07-01 Time 13:51 Rev Time 0.33
Received By ndenmark Date 1999-07-01 Time 13:51 Sent To  
Notes
2001-01-08 00:00:00DRYERVENT TO BE INSTALLED PER 1994 SMC

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-09-02 Cont ID  
Sent By tlarge Date 1999-09-02 Time 14:19 Rev Time 0.50
Received By tlarge Date 1999-09-02 Time 14:19 Sent To  
Notes
2001-01-08 00:00:00SUBMIT CORRECT BTU LOAD FOR SYSTEM.
 SGC SEC.305.3.1.
  
 INDICATE GAS SUPPLY PRESSURE ON PLANS.
 COMPLY W/SGC SEC.305.2.
  
 SHOW LENGTH OF PIPING FROM POINT OF
 DELIVERY TO MOST REMOTE OUTLET PER SGC
 SEC.305.4.
  
 INDICATE TYPE OF PIPING TO BE INSTALLED.
 SGC.SEC.306.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-06-30 Cont ID  
Sent By tlarge Date 1999-06-30 Time 15:11 Rev Time 0.65
Received By tlarge Date 1999-06-30 Time 15:11 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
 NEW GAS DRAWING REQ.-SHOW ALL CUT
 LENGTHS OF PIPE,DISTANCE OF GAS METER
 FROM SOURCE OF IGNITION,TYPR OF PIPING
 TO BE USED,ETC.PER STANDARD GAS CODE
 SEC.104.2.1

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-06-30 Cont ID  
Sent By jcaloger Date 1999-06-30 Time 12:00 Rev Time 30.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-06-07 Cont ID  
Sent By gjoyce Date 1999-06-07 Time 17:10 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00REAR S/B MUST BE 10'