Plan Review Details - Permit 99060166
Plan Review Stops For Permit 99060166 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
1999-06-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
1999-06-16 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
1999-06-16 |
Time |
16:50 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ***************PROVISO****************** | | | | NOTE:NEED TO SUBMIT PLANS WITH AIC | | RATING DERIVED FROM FAULT CURRENT | | CALCULATIONS.215-5 | | NOTE:RECEPTS.SERVING KITCHEN COUNTER | | SPACE ARE TO BE GFI/GFI PROTECTED. | | ART.210-8-A-6 | | NOTE:GROUNDING ELECTRODE CONDUCTOR | | ALSO CONNECTED TO BLDG.STEEL. | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | OUTSIDE BEDROOMS. | | NOTE:REQ`D RECEPTS.MISSING.210-52A | | | | NEED TO SUBMIT REVISED PLANS BEFORE | | ROUGH INSPECTION. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
1999-07-01 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
1999-07-01 |
Time |
13:51 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
1999-07-01 |
Time |
13:51 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | DRYERVENT TO BE INSTALLED PER 1994 SMC |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
1999-09-02 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-09-02 |
Time |
14:19 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
1999-09-02 |
Time |
14:19 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SUBMIT CORRECT BTU LOAD FOR SYSTEM. | | SGC SEC.305.3.1. | | | | INDICATE GAS SUPPLY PRESSURE ON PLANS. | | COMPLY W/SGC SEC.305.2. | | | | SHOW LENGTH OF PIPING FROM POINT OF | | DELIVERY TO MOST REMOTE OUTLET PER SGC | | SEC.305.4. | | | | INDICATE TYPE OF PIPING TO BE INSTALLED. | | SGC.SEC.306. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
1999-06-30 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
1999-06-30 |
Time |
15:11 |
Rev Time |
0.65 |
Received By |
tlarge |
Date |
1999-06-30 |
Time |
15:11 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ***************PROVISO****************** | | NEW GAS DRAWING REQ.-SHOW ALL CUT | | LENGTHS OF PIPE,DISTANCE OF GAS METER | | FROM SOURCE OF IGNITION,TYPR OF PIPING | | TO BE USED,ETC.PER STANDARD GAS CODE | | SEC.104.2.1 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
1999-06-30 |
|
|
Cont ID |
|
Sent By |
jcaloger |
Date |
1999-06-30 |
Time |
12:00 |
Rev Time |
30.00 |
Received By |
jcaloger |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
1999-06-07 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
1999-06-07 |
Time |
17:10 |
Rev Time |
|
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REAR S/B MUST BE 10' |
|
|
|
Account Summary | Usage Policy | Privacy Policy