Plan Review Details - Permit 99051036
Plan Review Stops For Permit 99051036
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-06-26 Cont ID  
Sent By jleech Date 1999-06-26 Time 11:38 Rev Time 0.50
Received By jleech Date 1999-06-26 Time 11:37 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
 1. SEER RATING ON A/C DRAWINGS MUST BE
 THE SAME AS ENERGY CALKS.
 2. FIRE STAT REQUIRED ON 5 TON UNITS
 RETURN AIR SIDE OF AIR HANDLER.
 3. BATHROOM VENTS MUST CONFORM TO 503.3
 OF THE STANDARD MECHANICAL CODE.
 4. GAS DRYER TO VENT TO OUTSIDE.
 5. GAS WATER HEATER MUST HAVE VENT TO
 OUT.