Plan Review Details - Permit 99041328
Plan Review Stops For Permit 99041328
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-09 Cont ID  
Sent By dpalmer Date 1999-06-09 Time 21:13 Rev Time 0.00
Received By dpalmer Date 1999-06-09 Time 21:13 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
  
 NOTE:PRINT SHOWS MAIN DISC..IF SO THEN
 NEEDS TO BE DRAWN ON RISER DIAGRAM!!!
 ART.215-5
 NOTE:NEED FAULT CURRENT CALCULATIONS
 FOR AIC RATING.215-5
 NOTE:GROUNDING ELECTRODE COND.TO GROUND
 ROD AND BLDG.STEEL.
 NOTE:210-8-A-6 REQ`MENTS FOR RECEPTS.
 SERVING KITCHEN COUNTER TO BE GFI/OR
 PROTECTED.
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:ART.210-52A OUTLET SPACING.2`6`12`
 RULE.
  
 NEED CHANGES BEFORE ROUGH INSPECTION
 IS CALLED IN!!!!

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-06-12 Cont ID  
Sent By jleech Date 1999-06-12 Time 10:44 Rev Time 0.50
Received By jleech Date 1999-06-12 Time 10:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-07-13 Cont ID  
Sent By tlarge Date 1999-07-13 Time 07:28 Rev Time 0.33
Received By tlarge Date 1999-07-13 Time 07:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-15 Cont ID  
Sent By tlarge Date 1999-06-15 Time 17:06 Rev Time 0.65
Received By bstaples Date 1999-06-15 Time 17:06 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SANITARY RISER THAT COMPLIES W/
 THE STANDARD PLUMBING CODE.SPC 104.2.1.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-06-28 Cont ID  
Sent By bstaples Date 1999-06-28 Time 17:09 Rev Time 1.50
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-05-04 Cont ID  
Sent By gjoyce Date 1999-05-04 Time 10:46 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***