Plan Review Details - Permit 99041039
Plan Review Stops For Permit 99041039
Review Stop E ELECTRICAL
Rev No 2 Status P Date 1999-07-01 Cont ID  
Sent By dpalmer Date 1999-07-01 Time 13:58 Rev Time 0.00
Received By dpalmer Date 1999-07-01 Time 13:58 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-05-27 Cont ID  
Sent By jleahy Date 1999-05-27 Time 10:36 Rev Time  
Received By jleahy Date   Time   Sent To  
Notes
2001-01-08 00:00:00***************DENIED******************
  
 NEED ELEC. SHOWN FOR UPSTAIRS BATH/
 GFI/LTS.210-52D
 NEW BATH BY KITCHEN ELEC.?
 NEW LOCATION FOR HWH NEEDS DISC.AND TO
 BE HARDWIRED.
 CHECK RECEPTS. IN KITCHEN.GFI REQ`D FOR
 ALL REC. SERVING KIT. COUNTER SPACE
 210-8A6
 210-52B/210-52C1/210-52C3/210-52
 PLEASE CHECK ALL REC. LOCATIONS THAT
 NEED TO MEET NEC.D.V.P

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 1999-07-08 Cont ID  
Sent By ndenmark Date 1999-07-08 Time 13:42 Rev Time 0.25
Received By fknapp Date 1999-07-08 Time 13:42 Sent To  
Notes
2001-01-08 00:00:00NO MECHANICAL INCLUDED

Review Stop P PLUMBING
Rev No 4 Status P Date 1999-07-06 Cont ID  
Sent By tlarge Date 1999-07-06 Time 15:54 Rev Time 0.33
Received By tlarge Date 1999-07-06 Time 15:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 1999-07-02 Cont ID  
Sent By tlarge Date 1999-07-02 Time 09:37 Rev Time 0.50
Received By tlarge Date 1999-07-02 Time 09:37 Sent To  
Notes
2001-01-08 00:00:00NEED BTU LOAD OF EXIST.SYSTEM TO ENSURE
 PROPER GAS PIPE SIZING PER STANDARD GAS
 CODE.

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-07-01 Cont ID  
Sent By tlarge Date 1999-07-01 Time 11:05 Rev Time 0.75
Received By tlarge Date 1999-07-01 Time 11:05 Sent To  
Notes
2001-01-08 00:00:00SHOWER DOWNSTREAM OF WATER CLOSET SHALL
 BE VENTED PER SPC SEC.913.2.
  
 SHOW SHOWER DIMENSIONS ON PLAN.(L X W).
 COMPLY W/COUNTYWIDE AMENDMENTS TO SPC
 SEC.409.8.2.1.
  
  
 SPC SEC.104.2.1.
  
 SIZE OF WASTE STACK SHALL COMPLY W/SPC
 SEC.909.3.1.
  
 IF SINK AND D/W ARE NEW SHOW ON SAN.
 RISER DIAGRAM.SPC SEC 104.2.1.
  
 INDICATE TYPE OF PIPING TO BE USED FOR
 GAS INSTALLATION. STD.GAS CODE SEC.306.
  
 SUBMIT CALCULATIONS FOR COMBUSTION AIR.
 COMPLY W/STD.GAS CODE SEC.402.4
  
 SUBMIT EXIST.BTU LOAD ON SYSTEM FROM
 GUEST HOUSE TO ENSURE PROPER SIZING OF
 GAS SYSTEM.STD.GAS CODE SEC.305.1.1.&
 SHOW DELIVERY PRESSURE OF GAS.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-05-27 Cont ID  
Sent By pschmitz Date 1999-05-27 Time 09:24 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00UNSAT: ISOMETRIC FOR GAS & DWV OLSO
 COMBUSTION AIR FOR GAS WTR HTR.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 1999-07-14 Cont ID  
Sent By fknapp Date 1999-07-14 Time 16:32 Rev Time 1.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1)PLANS SHALL BEAR THE NAME,SIGNATURE
 AND ADDRESS OF PERSON RESPONSIBLE FOR
 DESIGN.
 2)PROVIDE DETAIL OF CONSTRUCTION FOR NEW
 EXTERIOR OPENINGS AND WALLS.
 3)PROVIDE DETAIL FOR WINDOW AND DOOR
 BUCK CONNECTIONS
 4)PROVIDE PRODUCT APPROVAL FOR EXTERIOR
 DOOR
  
 CITY AMENDMENTS 104.2
  
 SUBMIT PROVISO PRIOR TO FRAMING
 INSPECTION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 1999-07-13 Cont ID  
Sent By fknapp Date 1999-07-13 Time 14:56 Rev Time 2.00
Received By fknapp Date 1999-07-14 Time 16:24 Sent To  
Notes
2001-01-08 00:00:00BLDG DENIED SEE CHECKLIST

Review Stop Z ZONING
Rev No 1 Status P Date 1999-04-28 Cont ID  
Sent By gjoyce Date 1999-04-28 Time 08:24 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***