Plan Review Details - Permit 99040821
Plan Review Stops For Permit 99040821
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-07 Cont ID  
Sent By dpalmer Date 1999-06-07 Time 17:58 Rev Time 0.00
Received By jleahy Date   Time   Sent To  
Notes
2001-01-08 00:00:00****************PROVISO****************
  
 NEED FAULT CURRENT CALCULATIONS FOR AIC
 RATING.215-5
 NOTE:SERVICE GROUNDING ELECTRODE SYSTEM
 TO GROUND ROD AND BLDG. STEEL.
 NOTE:REQ`MENTS FOR KITCHEN RECEPTS.
 ART.210-8-A-6
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-06-04 Cont ID  
Sent By ndenmark Date 1999-06-04 Time 09:21 Rev Time 0.25
Received By ndenmark Date 1999-06-04 Time 09:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-07-02 Cont ID  
Sent By tlarge Date 1999-07-02 Time 10:54 Rev Time 0.50
Received By tlarge Date 1999-07-02 Time 10:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-02 Cont ID  
Sent By pschmitz Date 1999-06-11 Time 10:28 Rev Time 0.50
Received By tlarge Date 1999-06-11 Time 10:28 Sent To  
Notes
2001-01-08 00:00:00SUBMIT NEW SANITARY RISER DIAGRAM THAT
 COMPLIES W/THE STANDARD PLBG.CODE.SEC.
 104.2.1
 SHOW FIXTURE CLEARANCES PER SPC SEC.403.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-06-22 Cont ID  
Sent By bstaples Date 1999-06-22 Time 10:48 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-07-03 Cont ID  
Sent By jwitmer Date 1999-07-03 Time 13:19 Rev Time 0.33
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***