Plan Review Details - Permit 99040125
Plan Review Stops For Permit 99040125
Review Stop E ELECTRICAL
Rev No 3 Status P Date 1999-07-27 Cont ID  
Sent By dpalmer Date 1999-07-27 Time 11:02 Rev Time 0.00
Received By dpalmer Date 1999-07-27 Time 11:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 1999-07-27 Cont ID  
Sent By dpalmer Date 1999-07-01 Time 18:13 Rev Time 0.00
Received By dpalmer Date 1999-07-01 Time 18:13 Sent To  
Notes
2001-01-08 00:00:00**************UNSAT*********************
  
 NOTE:STILL NEED AIC RATING OF EQUIPMENT
 FROM FAULT CURRENT CALCULATIONS.
 NOTE:STILL NEED TO HAVE GROUNDING ELEC.
 CONDUCTOR TO GO TO BLDG.STEEL.
 NOTE:DEDICATED CIRCUTS FOR GARAGE DOOR
 OPENERS NOT ON LOAD CALCULATIONS.
 CHANGE FOR SECOND FLOOR IS O.K.`D
 NEED THE ABOVE INFORMATION BEFORE ROUGH
 INSPECTION IS CALLED.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 1999-07-27 Cont ID  
Sent By dpalmer Date 1999-06-02 Time 13:31 Rev Time 0.00
Received By dpalmer Date 1999-06-02 Time 18:34 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
  
 NOTE:ART.215-5 NEED FAULT CURRENT
 CALCULATIONS.
 NEED AIC RATING!
 NOTE: GRND. TO BLDG. STEEL ALSO.
 NEED AIC RATING BEFORE ROUGH INSPECTION
 IS CALLED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-04-24 Cont ID  
Sent By jleech Date 1999-04-24 Time 14:57 Rev Time 0.50
Received By jleech Date 1999-04-24 Time 14:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-06-07 Cont ID  
Sent By bstaples Date 1999-06-07 Time 13:34 Rev Time 0.50
Received By bstaples Date 1999-04-24 Time 14:58 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-06-15 Cont ID  
Sent By bstaples Date 1999-06-07 Time 13:34 Rev Time 2.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-04-08 Cont ID  
Sent By gjoyce Date 1999-04-08 Time 10:23 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***