Plan Review Details - Permit 99040095
Plan Review Stops For Permit 99040095
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-02 Cont ID  
Sent By dpalmer Date 1999-06-02 Time 10:30 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
  
 SHEET A,NEED FAULT CURRENT CALCULATIONS.
 NEED AIC RATING TO BE LISTED ON PANEL.
 ART 215-5
 NOTE:PG.2OF6 ALL RECEPTS SERVING KITCHEN
 COUNTER MUST BE GFI OR GFI PROTECTED.
 ART:210-8-A-6
 NOTE:PG. 2OF6 REC.REQ`D WITHIN 6'
 OF DOOR.ART.210-52A
 NOTE:PG.3OF6 SMOKE DETECTORS REQ`D
 INSIDE AND OUTSIDE BEDROOMS.
 NOTE:PG.3OF6 RECEPTS.REQ`D IN HALLWAYS
 ART.210-52H
 NOTE:PG.3OF6 RECEPTS. REQ`D 2'OF WALL
 ART.210-52A
 NEED CHANGES TO BE MADE BEFORE ROUGH
 INSPECTION IS CALLED IN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-04-24 Cont ID  
Sent By jleech Date 1999-04-24 Time 14:59 Rev Time 0.50
Received By jleech Date 1999-04-24 Time 14:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-04-24 Cont ID  
Sent By jleech Date 1999-04-24 Time 14:59 Rev Time 0.50
Received By jleech Date 1999-04-24 Time 14:59 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-06-08 Cont ID  
Sent By jcaloger Date 1999-06-08 Time 10:52 Rev Time  
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-06-08 Cont ID  
Sent By fcounter Date 1999-06-08 Time 12:01 Rev Time  
Received By fcounter Date   Time   Sent To  
Notes
***NONE***