Plan Review Details - Permit 99031479
Plan Review Stops For Permit 99031479
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lsmith Date 2000-03-14 Time 08:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-07-21 Cont ID  
Sent By jcaloger Date 1999-05-10 Time 14:22 Rev Time 0.25
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00*****************DENIED****************
 NEED TO GIVE MORE DETAILED INFORMATION
 ON ALL ELECTRICAL.DRAW IN SWITCH LEGS
 SMOKE DETECTORS REQ`D INSIDE AND OUTSIDE
 BEDROOMS.
 LIGHTS REQ`D BY 210-70 AT MEANS OF
 EGRESS.
 NOTE:210-8-A-6 RECEPTS.SERVING KITCHEN
 COUNTER SPACE.
 YOU SHOW 6-GANG BOX BUT ONLY SHOW ONE
 SWITCH.
 ALSO PLEASE HAVE ELECTRICAL RISER
 DIAGRAM AND LOAD CALCULATIONS DRAWN
 ON SAME PAGE.
 PLEASE DRAW IN NEW PANEL SCHED.WITH
 AIC RATING OF EQUIPMENT.
 215-5

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-21 Cont ID  
Sent By jcaloger Date 1999-05-10 Time 14:22 Rev Time 0.00
Received By bstaples Date 1999-07-19 Time 16:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-07-21 Cont ID  
Sent By tlarge Date 1999-07-02 Time 13:44 Rev Time 0.50
Received By tlarge Date 1999-07-02 Time 13:44 Sent To  
Notes
2001-01-08 00:00:00CLEARLY SHOW ALL SHOWER DIMENSIONS ON
 PLAN.(L X W).MIN.1024 SQ.IN.REQ'D & MIN.
 30" WIDE.PER SPC SEC.408.8.1,409.8.2.1
 OF COUNTYWIDE AMEND.
  
 SHOW LOCATION OF WASHING MACHINE OUTLET
 SPC 104.2.1.
  
 SHOW LOCATION OF WATER HEATERS.SPC
 401.2.1
  
 SUBMIT SANITARY RISER DIAGRAM THAT
 COMPLIES W/STD.PLBG.CODE.
  
 SHOW FIXTURE CLEARANCES OF W.C'S ON PLAN
 PER SPC SEC.403.4.
  
 VENTING OF WATER CLOSETS SHALL COMPLY
 W/COUNTYWIDE AMEND.TO PLBG.CODE SEC.
 911.1.3.
  
 KIT.SINK NOT PROPERLY VENTED.SPC 901.2.
  
 SHOW ALL FIXTURES ON SAN.RISER.SPC 104.2
  
 DRY VENTS NOT PERMITTED.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-21 Cont ID  
Sent By jcaloger Date 1999-05-10 Time 14:22 Rev Time 0.65
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00ISOMETRTIC SHALL CLEARLY REFLECT SCOPE
 OF WORK BEING PERFORMED.(ALL AREAS ARE
 NOT SHOWN.)SPC 104.2.1.
  
 IDENTIFY ALL FIXTURES ON SAN.RISER.
 SPC 104.2.1.
  
 CLEARLY SHOW ALL DIMENSIONS OF TOILET
 AND BATH ROOMS AND SHOW ALL FIXTURE
 CLEARANCES.SPC 104.2.1,403.4.
  
 SHOW ALL SHOWER DIMENSIONS ON PLANS.
 SPC 408.8.1.
  
 CLEARLY SHOW ON THE PLANS WHAT PLBG.IS
 NEW AND WHAT IS EXISTING.SPC 104.2.1.
  
 SHOW LOCATION OF WASHING MACHINE PER
 TABLE 407 OF SPC.
  
 REJECTED AGAIN ON 6/18/99-CORRECTIONS
 NOT DONE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-07-21 Cont ID  
Sent By jcaloger Date 1999-05-10 Time 14:22 Rev Time 1.50
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE PERMIT NOTES NO P, M OR E PERMITTED
 MUST SUBMIT PERMIT AND PLANS FOR P,E &E