Plan Review Details - Permit 99030676
Plan Review Stops For Permit 99030676
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-01 Cont ID  
Sent By fknapp Date 2000-02-01 Time 14:57 Rev Time 0.00
Received By dpalmer Date 2000-02-01 Time 10:39 Sent To  
Notes
2001-01-08 00:00:00************ PROVISO*******************
  
 1)NOTE: PLEASE SHOW EXISTING SERVICE
 SIZE.
  
 2)NOTE: PLEASE CHECK HEATSTRIP ON AHU
 HEAT STRIPS ARE USUALLY 5,71/2 AND 10KW
 STRIPS?? SHOW TOTAL SQ.FT. FOR LOAD CALC
 RE-DO LOAD CALCS.
  
 3)NOTE: WP GFI RECEPT IN BACK OF
 DWELLING. AS PER 210-52E
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROAL BEFORE ROUGH
 ELECTRICAL INSPECTION.IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-12-03 Cont ID  
Sent By tlarge Date 1999-12-02 Time 07:24 Rev Time 0.00
Received By dpalmer Date 1999-12-03 Time 11:49 Sent To  
Notes
2001-01-08 00:00:00***********UNSAT***********************
  
 1)NOTE: NEED LOAD CALCULATIONS AS PER
 220-3-D-1
 2)NOTE: NEED TO SHOW SIZE OF EXISTING
 SERVICE TO INCLUDE SERVICE WIRE SIZE.
 3)NOTE: NEED TO SHOW NEW PANEL SCHEDULE
 FOR ADDITION OF NEW CIRCUTS TO EXISTING
 PANEL. DINING AREA REQ`S 20 AMP BRANCH
 CIRCUTS AS PER CODE.
 4)NOTE: ALSO AS PER 210-52D BATH REC IS
 TO ON IT`S OWN 20 AMP BRANCH CIRCUT.
 5)NOTE: PLEASE SHOW EXISTING LOCATION
 OF REC AT REAR OF RESIDENCE AS REQ`D BY
 210-52 E IF NO REC EXIST THEN ONE NEEDS
 TO BE ADDED TO REAR OF ADDITION.
 6)NOTE: NEED TO HAVE SMOKE DETECTORS
 INSIDE AND OUTSIDE ALL NEW BEDROOMS
 AS REQ`D BY NFPA-72 2-2.1.1.1 1993/1996
 EDDITION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS OR I CAN BE OF ANY ASST.
 PLEASE CONTACT ME AT 659-8096 EXT8372

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-02-01 Cont ID  
Sent By tlarge Date 1999-12-02 Time 07:23 Rev Time 0.33
Received By fknapp Date 1999-12-02 Time 07:22 Sent To E
Notes
2001-01-08 00:00:00PLUMBING HAS BEEN DELETED-FK

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2000-02-01 Cont ID  
Sent By fknapp Date 2000-02-01 Time 14:27 Rev Time 2.00
Received By fknapp Date 2000-02-01 Time 08:07 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2000-01-27 Cont ID  
Sent By fknapp Date 2000-01-27 Time 11:19 Rev Time 2.00
Received By fknapp Date 2000-01-27 Time 11:19 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************DENIED******************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR NEW EXTERIOR WINDOW.
  
 2)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR STORM PANELS COMPLETE
 WITH INSTALLATION SCHEDULE AND KEY PLAN
 WITH SPECIFIC ANCHORS TO BE USED.
  
 3)PROVIDE ENERGY CALCULATIONS.
  
 4)PROVIDE DETAIL OF FAMILY ROOM WALL AT
 STORAGE ROOM.
  
 5)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-01-13 Cont ID  
Sent By fknapp Date 2000-01-13 Time 08:39 Rev Time 3.00
Received By fknapp Date 2000-01-12 Time 16:41 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************DENIED******************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR:
 NEW EXTERIOR DOORS AND WINDOWS
 ROOF COVERING
 MISSILE IMPACT RESISTANCE INFORMATION
  
 2)PROVIDE ENERGY CALCULATIONS
  
 3)PROVIDE BEAM HEIGHT ELEVATIONS
  
 4)PROVIDE ROOF SHEATHING NAILING ZONES
 COMPLYING WITH SBC FIG 2306.1
  
 5)PROVIDE WINDOW AND DOOR BUCK
 CONNECTION DETAIL FOR WINDLOAD
 RESISTANCE SBC 1606
  
 6)PROVIDE VIEW OF EXISTING BACK WALL TO
 SHOW HOW ACCESS WILL BE OBTAIN AND ANY
 DEMOLITION TO BE DONE.
  
 7)RAFTERS SPECIFIED,#2-2 X 8'S WILL ONLY
 SPAN 13'-9" PLEASE REVISE TO COMPLY. #2-
 2 X 10'S RAFTERS WILL SPAN 16'-5"
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUE,IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 1999-12-07 Cont ID  
Sent By fknapp Date 1999-12-07 Time 10:24 Rev Time 3.00
Received By fknapp Date 1999-12-07 Time 07:45 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************DENIED******************
  
 SBC104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR:
 NEW EXTERIOR DOORS AND WINDOWS
 ROOF COVERING
 MISSILE IMPACT RESISTANCE INFO
  
 2)PROVIDE COMPLETE FLOOR FRAMING PLAN
  
 3)PROVIDE ADDRESS AND PHONE# OF DESIGNER
  
 4)PROVIDE ENERGY CALCULATIONS INCLUDING
 MANUEL J
  
 5)PROVIDE BEAM HEIGHT ELEVATIONS
  
 6)PROVIDE COMPLETE DETAIL OF STAIRS TO
 COMPLY WITH SBC 1006,1007,1015
  
 7)PROVIDE INTERIOR WALL SECTION DETAIL
  
 8)PROVIDE TRUSS PLAN LAYOUT WITH DESIGN
 INFORMATION SBC 1606 OR ASCE-7-95
  
 9)PROVIDE ROOF SHEATHING NAILING ZONES
 COMPLYING WITH SBC FIG.2306.1
  
 10)PROVIDE WINDOW AND DOOR BUCK
 CONNECTION DETAIL FOR WINDLOAD
 RESISTANCE SBC 1606
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED,IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 2 Status P Date 2000-02-01 Cont ID  
Sent By gjoyce Date 2000-02-01 Time 15:07 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 1999-04-19 Cont ID  
Sent By gjoyce Date 1999-03-19 Time 13:58 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***