Plan Review Details - Permit 99030502
Plan Review Stops For Permit 99030502
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-07-14 Cont ID  
Sent By jcaloger Date 1999-06-03 Time 10:54 Rev Time 1.50
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED SEE PROVISO ON SHEET A-1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-22 Cont ID  
Sent By jleahy Date 1999-05-26 Time 16:35 Rev Time 0.00
Received By dpalmer Date 1999-05-26 Time 10:47 Sent To  
Notes
2001-01-08 00:00:00**************DENIED********************
  
 NEED RISER DIAGRAM TO SHOW COMPLETE
 SERVICE!
 IF TWO SEPARATE EXIST THEN NOW THEY NEED
 TO BE GROUPED AS PER ART. 230-72
 NEED NEW LOAD CALCS. DO TO ADDITIONAL
 ELECTRICAL WORK.
 NOTE MEANS OF EGRESS TO PORCH REQ`S
 SWITCH FOR LIGHTING.210-70
  
 **************PROVISO 6/22/99***********
 NEED TO SUBMIT AIC RATING FOR EQUIP.
 AND PANEL SCHED. ART.215-5
 NOTE:OUTSIDE LIGHT REQ`D 210-70
 NOTE:NOT TO USE DISC.AS RACEWAY.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 1999-06-03 Cont ID  
Sent By jcaloger Date 1999-06-03 Time 10:54 Rev Time  
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 1999-06-03 Cont ID  
Sent By jcaloger Date 1999-06-03 Time 10:54 Rev Time  
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-14 Cont ID  
Sent By ndenmark Date 1999-05-28 Time 14:30 Rev Time 0.25
Received By bstaples Date 1999-05-28 Time 14:30 Sent To  
Notes
2001-01-08 00:00:00NO A/C PLAN INCLUDED, SUBMIT A/C PLANS
 WITH MECHANICAL PERMIT APPLICATION
 APPROVED SEE NOTE ON SHEET A-1

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-07-12 Cont ID  
Sent By tlarge Date 1999-07-12 Time 15:50 Rev Time 0.33
Received By tlarge Date 1999-07-12 Time 15:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-14 Cont ID  
Sent By pschmitz Date 1999-04-15 Time 11:01 Rev Time 0.50
Received By bstaples Date 1999-06-22 Time 14:10 Sent To  
Notes
2001-01-08 00:00:00ISOMETRIC FOR DWV.
  
 REVIEW 6/22/99.-SIZE ALL SECTIONS OF THE
 SAN.ISOMETRIC.SPC 104.2.1.
  
 FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC SEC.913.2
  
 SIZE OF TUB FIXTURE DRAIN SHALL COMPLY
 W/SPC SEC.714.4.& SHALL NOT BE "S"
 TRAPPED.SPC.SEC.1001.5.2.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-07-14 Cont ID  
Sent By gjoyce Date 1999-07-14 Time 11:10 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***