Plan Review Details - Permit 99020717
Plan Review Stops For Permit 99020717
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-21 Cont ID  
Sent By jgomez Date 1999-06-21 Time 10:34 Rev Time 0.00
Received By jgomez Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED BY JAKE. SEE APPLICATION & DWGS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-03-04 Cont ID  
Sent By ndenmark Date 1999-03-04 Time 14:10 Rev Time 0.50
Received By ndenmark Date 1999-03-04 Time 14:10 Sent To  
Notes
2001-01-08 00:00:00********** PROVISO:********************
 NO CONDENSATE LINE SHOWN ON PLAN. ROUTE
 PER 1994 SMC 304.8
 R/A LOCATION IS WITHIN 10 FOOT OF THE
 COOKING EQUIPMENT, THIS IS ACCEPTABLE
 FOR THE 1994 SMC, IT IS EXPECTED THAT
 THE 1997 SMC WILL BE ADOPTED IN JUNE,
 1999 AND THIS LOCATION WILL NO LONGER
 BE ACCEPTABLE PER 1997 SMC 409. ANY
 PERMITS ISSUED AFTER THIS WILL REQUIRE
 COMPLIANCE WITH THIS SECTION OF THE CODE

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-03-13 Cont ID  
Sent By pschmitz Date 1999-03-13 Time 09:22 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00MASTER ,PLAN MODEL # III .

Review Stop R ROOF PLAN REVIEW
Rev No 6 Status P Date 2000-04-04 Cont ID  
Sent By jgomez Date 2000-04-04 Time 18:18 Rev Time 0.25
Received By jgomez Date 2000-04-04 Time 18:17 Sent To  
Notes
2001-01-08 00:00:00NOTES:
 PERMIT TYPE ON SCREEN #1 WAS CHANGED
 FROM BLD-RES TO MASTER TO ALLOW PERMITS
 TO BE PRINTED. ORIGINAL PERMIT
 APPLICATION WAS SUBMITTED FOR A BLD-RES
 AND LATER ON THE APPLICANT WANTED TO GET
 A MASTER PERMIT. SUCH CHANGE WAS NEVER
 REVISED ON THIS SCREEN. THEREFORE, I
 HAD TO CHANGE THE PERMIT TYPE TO AVOID
 MORE CONFUSION AND BE ABLE TO REFER TO
 THIS MASTER NUMBER AS THE MASTER FOR
 TYPE III MODEL, INCLUDING STORM PANELS.
 J.G. 4-4-00.

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 1999-10-28 Cont ID  
Sent By jgomez Date 1999-10-28 Time 14:35 Rev Time 0.50
Received By jgomez Date 1999-10-28 Time 14:35 Sent To  
Notes
2001-01-08 00:00:00 
 CHECKLIST FOR PROVISO GIVEN ON 10/15/99:
 1-PROVIDE COMPLETE SPECIFICATIONS AND
 DETAILS FOR CONSTRUCTION OF CEILING AT
 PORCH. SEC. 104.2.2 CITY AMENDMENTS.
 NOTE: ALCOA RIGID VINYL SIDING AND
 SOFFIT PRODUCT APPROVAL DOESN'T
 INCLUDE INSTALLATION AT PORCHE'S
 CEILING.
 2-SPECIFY ATTIC VENTILATION FOR NEW
 SOFFIT SYSTEM AS PER SEC 2309.7 SBC/94

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 1999-10-15 Cont ID  
Sent By jgomez Date 1999-10-15 Time 14:41 Rev Time 0.25
Received By jgomez Date 1999-10-15 Time 14:41 Sent To  
Notes
2001-01-08 00:00:00VINYL SIDING PRODUCT APPROVAL PROVISO:
 1-PROVIDE MANUFACTURER'S INSTALLATION
 SPECIFICATIONS.
 2-PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR INSTALLATION AT
 PORCH'S CEILING.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 1999-10-07 Cont ID  
Sent By jgomez Date 1999-10-07 Time 10:18 Rev Time 0.25
Received By jgomez Date 1999-10-07 Time 10:18 Sent To  
Notes
2001-01-08 00:00:00ROOF SHINGLES PRODUCT APPROVAL. JG.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 1999-09-20 Cont ID  
Sent By jgomez Date 1999-09-20 Time 11:14 Rev Time 1.00
Received By jgomez Date 1999-09-20 Time 11:14 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST - MODEL III
 1-ENGINEER OF RECORD TO REVIEW ALL TRUSS
 DRAWINGS PRIOR TO SUBMITTAL.
 2-ENGINEERED TRUSSES:
 *REVISE MEAN ROOF HEIGHT.
 *CLARIFY NOTE SAYING THAT IF PORCHES
 EXIST, THEY ARE NOT EXPOSED TO WIND.
 WHY? WHAT DOES DOL STANDS FOR ?
 DEFLECTION?
 *REVISE DESIGN CRITERIA DATA ON TRUSS
 LAYOUT. IT DOESN'T MATCH THE DESIGN
 CRITERIA ON ENGINEERED TRUSSES.
 *WHY NOT ALL ENGINEERED TRUSSES SHOW
 THE DESIGN CRITERIA USED TO DETERMINE
 ALL THE LOADS?
 3-CHECK/REVISE ALL HURRICANE ANCHORS
 SPECIFIED. WILL THEY RESIST THE
 HORIZONTAL LOADS CALCULATED BY THE
 ENGINEERED TRUSSES.
 4-PROVIDE A COMPLETE DETAIL FOR ALUMINUM
 CEILING AT PORCH.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-04-06 Cont ID  
Sent By jgomez Date 1999-04-06 Time 16:41 Rev Time 0.00
Received By jgomez Date   Time   Sent To O
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO