Plan Review Stops For Permit 23070476 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2023-07-18 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-07-18 |
Time |
10:41 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-07-18 |
Time |
10:41 |
Sent To |
|
|
Notes |
2023-07-18 10:42:09 | SUITE 215 IS NOT A RECOGNIZED SUITE NUMBER, PLEASE | | PROVIDE A FLOOR PLAN SHOWING EVERY SUITE ON THAT FLOOR. | | PLEASE EMAIL TO [email protected] FOR FURTHER | | QUESTIONS YOU CAN ALSO CALL 561-805-6659 |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2023-07-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2023-07-26 |
Time |
13:06 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2023-07-26 |
Time |
13:06 |
Sent To |
|
|
Notes |
2023-07-26 13:06:23 | COMMERCIAL ASBESTOS | | TO THE BUILDING CONTRACTOR: | | PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION | | THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE. | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING | | THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS | | PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM | | BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION | | WILL BE GIVEN TIMELY. | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | CAN BE FOUND ON THEIR WEBSITE: | | HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC | | ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION | | -RENOVATION.HTML | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | [email protected]. THE INFORMATION SHOULD BE IN | | PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT | | LINE. | | JAMES A. WITMER BN, PX, SFP, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | TEL: 561-805-6717 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2023-07-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2023-07-26 |
Time |
13:05 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2023-07-26 |
Time |
12:48 |
Sent To |
|
|
Notes |
2023-07-26 13:05:18 | ENTRY DOOR VERSES CORRIDOR. CORRIDOR WIDTH 58 INCHES, | | 1/2 OF REQUIRED CORRIDOR WIDTH (44/2= 22 INCHES CLEAR | | CORRIDOR WIDTH. 58-22= 36 INCH DOOR IN QUESTION. MEETS | | 1/2 OF REQUIRED CORRIDOR WIDTH. J WITMER 7-26-23. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2023-07-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-07-28 |
Time |
17:08 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-07-28 |
Time |
07:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
Rev No |
1 |
Status |
P |
Date |
2023-07-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-07-28 |
Time |
17:09 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-07-28 |
Time |
17:09 |
Sent To |
|
|
Notes |
2023-07-28 17:10:08 | VOICE AND DATA AS PER PLAN JLEAHY |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2023-07-17 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-07-17 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-07-17 |
Time |
14:37 |
Sent To |
|
|
Notes |
2023-07-17 14:38:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS AN INDICATION OF WHAT APPEARS TO BE A | | DOUBLE SWING ENTRY DOOR, # 1, HOWEVER, IF IT WERE TO | | SWING OUT IT APPEAR TO RESTRICT THE CORRIDOR EGRESS | | WIDTH. | | | | PER NFPA 1 | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | APPLICABLE CODES AND STANDARDS | | | | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO | | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE | | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. | | | | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS | | | | 7.2.1.4.3 DOOR LEAF ENCROACHMENT | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | OF EGRESS SHALL | | LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF | | AN AISLE, A CORRIDOR, | | A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF | | THE FOLLOWING | | CONDITIONS ARE MET: | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | EXISTING | | BUILDING. | | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF | | 7.2.1.4.3.2. | | 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS | | OF EGRESS SHALL | | NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED | | WIDTH OF AN AISLE, | | A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR | | LEAF IS EQUIPPED | | WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT | | REQUIRED BY THE PROVISIONS | | OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS | | TRAVEL. | | | | | | PLEASE REVIEW AND CORRECT AND/OR PROVIDE THE REMINAING | | CORRIDOR WIDTH DIMENSION IN COMPLIANCE WITH THE | | REQUIREMENT. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
amcgrego |
Date |
2023-07-14 |
Time |
11:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
|
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2023-07-21 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-07-21 |
Time |
08:46 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-07-21 |
Time |
08:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2023-07-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-07-28 |
Time |
17:08 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-07-28 |
Time |
17:08 |
Sent To |
|
|
Notes |
2023-07-26 13:08:28 | ARCHITECTURAL SHEETS SIGNED DIGITALLY. J WITMER 7-26-23 | 2023-07-21 08:47:26 | PLUMBING SIGNATURES PASSED. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
cibaven |
Date |
|
Time |
|
Rev Time |
|
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|