2023-07-26 13:46:09 | FBC 107.2.1 |
| |
| PROVIDE POST SECTION FOR THE PROPOSED FENCE, ELEVATION |
| DRAWING WITH DIMENSION. |
| |
| PLEASE MAKE SURE TO COMPLY TO THE FOLLOWING BELOW AS |
| WELL FOR A POOL FENCE. |
| |
| |
| R4501.17.1.1 THE TOP OF THE BARRIER SHALL BE AT LEAST |
| 48 INCHES |
| (1219 MM) ABOVE GRADE, MEASURED ON THE SIDE OF THE |
| BARRIER |
| WHICH FACES AWAY FROM THE SWIMMING POOL. |
| THE MAXIMUM VERTICAL CLEARANCE BETWEEN GRADE AND THE |
| BOTTOM |
| OF THE BARRIER SHALL BE 2 INCHES (5MM) MEASURED ON THE |
| SIDE OF |
| THE BARRIER WHICH FACES AWAY FROM THE SWIMMING POOL. |
| WHERE THE TOP OF THE POOL STRUCTURE IS ABOVE |
| GRADE, THE BARRIER MAY BE AT GROUND LEVEL OR |
| MOUNTED ON TOP OF THE POOL STRUCTURE. WHERE |
| THE MAXIMUM VERTICAL CLEARANCE BETWEEN THE |
| TOP OF THE POOL STRUCTURE AND THE BOTTOM OF THE |
| BARRIER SHALL BE 4 INCHES (102 MM). |
| |
| R4501.17.1.8 ACCESS GATES, WHEN PROVIDED, SHALL BE |
| SELF-CLOSING AND SHALL COMPLY WITH THE REQUIREMENTS OF |
| SECTIONS R4501.17.1.1 THROUGH R4501.17.1.7 AND |
| SHALL BE EQUIPPED WITH A SELF-LATCHING LOCKING DEVICE |
| LOCATED ON THE POOL SIDE OF THE GATE. WHERE THE |
| DEVICE RELEASE IS LOCATED NO LESS THAN 54 INCHES |
| (1372 MM) FROM THE BOTTOM OF THE GATE, THE DEVICE |
| RELEASE MECHANISM MAY BE LOCATED ON EITHER SIDE OF |
| THE GATE AND SO PLACED THAT IT CANNOT BE REACHED BY A |
| YOUNG CHILD OVER THE TOP OR THROUGH ANY OPENING OR |
| GAP FROM THE OUTSIDE. GATES THAT PROVIDE ACCESS TO |
| THE SWIMMING POOL MUST OPEN OUTWARD AWAY FROM THE |
| POOL. THE GATES AND BARRIER SHALL HAVE NO OPENING |
| GREATER THAN 1/2 INCH (12.7 MM) WITHIN 18 INCHES (457 |
| MM) OF THE RELEASE MECHANISM |
| |
| ALL DOORS PROVIDING DIRECT ACCESS FROM THE |
| HOME TO THE POOL MUST BE EQUIPPED WITH A |
| SELF-CLOSING, SELF-LATCHING DEVICE WITH |
| POSITIVE MECHANICAL LATCHING/LOCKING |
| INSTALLED A MINIMUM OF 54 INCHES (1372 MM) |
| ABOVE THE THRESHOLD, WHICH IS APPROVED BY |
| THE AUTHORITY HAVING JURISDICTION. |
| |