Plan Review Details - Permit 23070005
Plan Review Stops For Permit 23070005
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-07-18 Cont ID  
Sent By pleduc Date 2023-07-18 Time   Rev Time 0.00
Received By pleduc Date 2023-07-18 Time 09:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-19 Cont ID  
Sent By aoliver Date 2023-07-19 Time 08:27 Rev Time 0.00
Received By aoliver Date 2023-07-17 Time 13:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-14 Cont ID  
Sent By aoliver Date 2023-07-14 Time 10:14 Rev Time 0.00
Received By aoliver Date 2023-07-12 Time 08:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-10 Cont ID  
Sent By lmarchan Date 2023-07-10 Time 09:27 Rev Time 0.00
Received By lmarchan Date 2023-07-05 Time 11:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-07-18 Cont ID  
Sent By ccole Date 2023-07-18 Time 08:07 Rev Time 0.00
Received By ccole Date 2023-07-18 Time 07:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-07-13 Cont ID  
Sent By ccole Date 2023-07-13 Time 08:35 Rev Time 0.00
Received By ccole Date 2023-07-13 Time 08:30 Sent To  
Notes
2023-07-13 08:37:211ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23070005
 7/12/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PERMIT APPLICATION INDICATES BACKFLOW #6 RPPA
 FOR 2" WATER SERVICE, HOWEVER THE BF TABLE ON SHEET EX
 1 SITE PLAN INDICATES BACKFLOW #6 RPPA IS A ZURN MODEL
 350 ASTDA DDCA FOR FIRE LINE. PLEASE CORRECT ONE OR THE
 OTHER- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-07-06 Cont ID  
Sent By ccole Date 2023-07-06 Time 08:04 Rev Time 0.00
Received By ccole Date 2023-07-06 Time 08:04 Sent To  
Notes
2023-07-06 08:04:521ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23070005
 7/6/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT A MANUFACTURER'S SPEC SHEET FOR THE BACKFLOW
 PREVENTER INDICATING THE SELECTED DEVICE MEETS THE
 REQUIREMENTS OF NSF/ANSI/CAN 61 (0.25% MAX WEIGHTED
 AVERAGE LEAD CONTENT)- SEC. CIV WPB UTILITIES
 CROSS-CONNECTION MANUAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status P Date 2023-07-14 Cont ID  
Sent By aoliver Date 2023-07-14 Time 10:14 Rev Time 0.00
Received By aoliver Date 2023-07-14 Time 10:14 Sent To  
Notes
2023-07-14 10:14:41APPROVED BY DALTON GRIFFITHS

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date 2023-07-10 Cont ID  
Sent By lmarchan Date 2023-07-10 Time 09:27 Rev Time 0.00
Received By lmarchan Date 2023-07-10 Time 09:27 Sent To  
Notes
2023-07-10 09:27:39DENIED PER DGRIFFITHS - NO SUPPORTING DOCUMENTS
 PROVIDED FOR REVIEW