Plan Review Details - Permit 23061516
Plan Review Stops For Permit 23061516
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2023-07-05 Cont ID  
Sent By lbond Date 2023-07-05 Time 16:52 Rev Time 0.00
Received By lbond Date 2023-07-05 Time 16:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-07-20 Cont ID  
Sent By lbond Date 2023-07-20 Time 13:47 Rev Time 0.00
Received By lbond Date 2023-07-20 Time 13:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-05 Cont ID  
Sent By lbond Date 2023-07-05 Time 16:58 Rev Time 0.00
Received By lbond Date 2023-07-05 Time 16:58 Sent To  
Notes
2023-07-05 17:04:13FBC 107.2.1 PLEASE CLARIFY
  
 WHISPERMAT EXACT SPECS, THERE ARE DIFFERENT TYPE THAT
 WILL COMPLY WITH THE SPECIFIC FLOORING MATERIAL
 SELECTED.
  
 PLEASE PROVIDE FLOOR FINISH SCHEDULE FOR EACH ROOMS
 WITH NEW FLOORING WITH NOA CUT SHEET TO MEET CODE
 REQUIREMTMENT BELOW:
  
 WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23061516
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 7.5.2023
 ACTION: DENIED
  
 A-3 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR
 TILE, STONE, MARBLE FLOORING, ENGINEERED WOOD, LVT ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6-INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. (TILE
 & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED FLOOR
 AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 A TRANSMITTAL LETTER / NARRATIVE LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 LOUIS BOND, AIA, NCARB
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-07-12 Cont ID  
Sent By rperdomo Date 2023-07-12 Time 12:23 Rev Time 0.00
Received By rperdomo Date 2023-07-12 Time 12:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-07-24 Cont ID  
Sent By pleduc Date 2023-07-24 Time   Rev Time 0.00
Received By pleduc Date 2023-07-24 Time 09:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-07-06 Cont ID  
Sent By pleduc Date 2023-07-06 Time   Rev Time 0.00
Received By pleduc Date 2023-07-06 Time 14:08 Sent To  
Notes
2023-07-06 14:17:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF NEW FLOORING ON ONE OF THE
 FLOOR PLANS HOWEVER, THERE IS NO SPEC SHEET NOR A
 PRODUCT NAME FOR THE ACTUAL PROPOSED FLOORING.
  
 FLOORING CAN HAVE DIFFERENT TYPES AND CAN BE
 MANUFACTURED AROUND THE WORLD BUT NOT ALL ARE TESTED
 AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING
 TYPE, PRODUCT NAME AND, IF APPLICABLE, THE PRODUCT SPEC
 SHEETS INDICATING THE FIRE BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED, BUT NEEDS TO BE INDICATED ON THE
 PLAN.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
 2) THERE ARE INDICATION OR WLL & CEILIGN WORK
 THROUGHOUT THE UNIT.
  
 DO NOT PAINT OVER FIRE ALARM DEVICES/EQUIPMENT.
  
 THE FA SYSTEM SHALL BE MAINTAINED THROUGHOUT DEMO AND
 CONSTRUCTION.
  
 ANY WORK/DAMAGE ON THE FA SYSTEM SHALL BE
 CORRECTED/REPAIRED UNDER SEPARATE PERMIT AND SHOP
 DRAWING BY FA CONTRACTORS.
  
 PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A
 NOTE OF ACKNOWLEDGMENT ON THE FLOOR PLAN.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-24 Cont ID  
Sent By lmarchan Date 2023-07-24 Time 10:46 Rev Time 0.00
Received By lmarchan Date 2023-07-20 Time 13:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-19 Cont ID  
Sent By cmontell Date 2023-07-19 Time 12:53 Rev Time 0.00
Received By cmontell Date 2023-07-19 Time 12:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-07-19 Cont ID  
Sent By cmontell Date 2023-07-19 Time 12:53 Rev Time 0.00
Received By cmontell Date 2023-07-19 Time 12:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-07-10 Cont ID  
Sent By rwbrown Date 2023-07-10 Time 14:07 Rev Time 0.00
Received By rwbrown Date 2023-07-10 Time 14:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-07-20 Cont ID  
Sent By lbond Date 2023-07-20 Time 13:47 Rev Time 0.00
Received By lbond Date 2023-07-20 Time 13:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-07-05 Cont ID  
Sent By lbond Date 2023-07-05 Time 16:52 Rev Time 0.00
Received By lbond Date 2023-07-05 Time 16:52 Sent To  
Notes
***NONE***