Plan Review Details - Permit 23061473
Plan Review Stops For Permit 23061473
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-29 Cont ID  
Sent By eroseber Date 2023-07-29 Time 12:06 Rev Time 0.00
Received By eroseber Date 2023-07-29 Time 12:06 Sent To  
Notes
2023-07-29 12:10:02PLAN REVIEWER: ED ROSEBERRY PX2909
 EMAIL: [email protected]
 PH: 772-359-3502
 ***PRIMARY CONTACT IS EMAIL***
  
  
 1. PLEASE SUBMIT LEGIBLE SCHEDULE SHOWING LOCATION,
 MRH, AND WALL ZONE FOR REPLACEMENT FENESTRATION. THIS
 IS A LISTING OF PRODUCTS DESCRIBING UNIT 1, 2....ETRC.
 FBC 107.2
 2. PLEASE SUBMIT FBC/NOA FOR ALL REPLACEMENT
 FENESTRATION, WITH SPECIFIC MODELS, SIZES, AND DESIGN
 PRESSURE TABLES HIGHLIGHTED. FBC 107.2
 3. PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO
 THE PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR
 FBC B 1405.4. ***NOTE*** THIS IS NOT USUALLY INCLUDED
 IN FBC/NOA. COMPLIANCE MUST BE SHOWN SEPARATELY.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2023-07-29 Cont ID  
Sent By eroseber Date 2023-07-29 Time 12:10 Rev Time 0.00
Received By eroseber Date 2023-07-11 Time 12:02 Sent To  
Notes
***NONE***