2023-07-24 16:14:55 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 23061432 |
| 7/24/2023 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS C-201 & P402: PLEASE SHOW THE LOCATION OF THE |
| BACKFLOW PREVENTER FOR THE POTABLE WATER SERVICE- SEC. |
| 608.1 FBC P, & SEC. C WPB UTILITIES CROSS CONNECTION |
| MANUAL. PLEASE NOTE THE INSTALLATION SHALL BE DONE |
| UNDER A SEPARATE PERMIT- SECS. 105.1 &107.2.1 WPB. |
| |
| 2) A1.0 & A1.3: PLEASE SHOW THE ACCESSIBLE ROUTE/PATH |
| OF TRAVEL FROM BUILDING #3 TO BUILDING #1 RESTROOMS |
| FROM THE MOST REMOTE POINT OF BUILDING #3 AND INCLUDE |
| THE LENGTH OF THE ROUTE- SECS. 403.3.1 & 403.3.3 FBC P. |
| |
| 3) P303: SHOW KEYNOTE #206 IN THE KEYNOTES BOX- SEC. |
| 107.2.1 WPB. |
| |
| 4) P303 & P603: SHOW THE PIPE RUNS FROM THE SUMP PUMPS |
| TO THE RECOVERY TANK AND INCLUDE THE PIPE SIZES- SEC. |
| 803.2 FBC P. |
| |
| 5) A1.2, P303: THE TANK IS LABELED RECIRC. ON A1.2 & |
| RECOVERY TANK ON P303. PLEASE PROVIDE A BRIEF NARRATIVE |
| TO CLARIFY THE FUNCTION OF THE TANK AND THE SYSTEM- |
| SEC. 107.2.1 WPB. |
| |
| A) PROVIDE AN EQUIPMENT SCHEDULE FOR THE TANK LISTING |
| MAKE AND MODEL AND CAPACITY. |
| |
| B) PLACE A NOTE TO INDICATE THE CHEMICALS IN THE TANK |
| SHALL NOT BE DRAINED INTO THE SANITARY SEWER SYSTEM |
| WITHOUT BEING THOROUGHLY DILUTED, NEUTRALIZED OR |
| TREATED BY PASSING THROUGH AN APPROVED DILUTION OR |
| NEUTRALIZING DEVICE- SEC. 803.1 FBC P. |
| |
| 6) P701: SHOW A CHECK VALVE AND FULL OPEN VALVE WILL BE |
| INSTALLED ON THE DISCHARGE PIPES OF THE SUMP PUMPS- |
| SEC. 712.2 FBC P. |
| |
| 7) P402, P603, & P801: PROVIDE THE MAKE AND MODEL OF |
| THE EMERGENCY EYE WASH STATION; INDICATE IT CONFORMS TO |
| ISEA Z358.1, AND IS EQUIPPED WITH AN ASSE 1071 MIXING |
| VALVE FOR TEPID WATER DELIVERY BETWEEN 60-100 DEGREES |
| F.- SECS. 411.1 & 411.3 FBC P. |
| |
| 8) A1.6 & P303 ROOF DRAINAGE: |
| |
| A) PROVIDE THE RAIN FALL RATE- SEC. 1106.1 FBC P. |
| |
| B) PROVIDE ROOF AREA AND GPM FLOW CALCULATIONS- 1106.2. |
| |
| C) PROVIDE THE GUTTER AND DOWNSPOUT SIZES- 1106.3 & |
| 1106.6. |
| |
| D) SHOW DOWNSPOUT LOCATIONS- 1106.3. |
| |
| E) SHOW THE DRAINAGE DISPOSAL LOCATIONS- SEC. 1101.2. |
| |
| 9) CONCERNING THE BACKFLOW PREVENTER, A PERMIT |
| APPLICATION SHALL BE SUBMITTED PRIOR TO MAIN PLUMBING |
| PLAN APPROVAL. YOU CAN SUBMIT AN APPLICATION TBD (TO BE |
| DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| EMAILING A COMPLETED PERMIT APPLICATION TO |
| [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| CHANGE THE REVIEW STATUS TO PASS. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |