Plan Review Details - Permit 23061410
Plan Review Stops For Permit 23061410
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-07-12 Cont ID  
Sent By jleahy Date 2023-07-12 Time 11:23 Rev Time 0.00
Received By jleahy Date 2023-07-12 Time 11:23 Sent To  
Notes
2023-07-12 11:55:17 
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FAULT CURRENT IS LISTED AT 65K. PLEASE SHOW CALCULATION
 PER 110.9, AND 110.10 AND LABELED PER 110.24.
  
 PLEASE SUBMIT THE SPECIFICATION FOR THE CHARGERS 110.3
  
 PLEASE SUBMIT A COST BREAKDOWN FOR THE INSTALLATION
 SHOWING LABOR AND ALL MATERIALS TO COMPLETE THIS KOB.
 165K FBC 109.2.1

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-06-30 Time 11:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By llouie Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved