Plan Review Details - Permit 23061338
Plan Review Stops For Permit 23061338
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-07-12 Cont ID  
Sent By rperdomo Date 2023-07-12 Time 11:48 Rev Time 0.00
Received By rperdomo Date 2023-07-12 Time 11:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-07-06 Cont ID  
Sent By pleduc Date 2023-07-06 Time   Rev Time 0.00
Received By pleduc Date 2023-07-06 Time 14:42 Sent To  
Notes
2023-07-06 15:01:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SPEC SHEET STATES:
  
 INSTALLATION GUIDELINES
  
 1) EXHAUST IS AIMED AWAY FROM OR PARALLEL TO THE
 STRUCTURE.
  
 2) EXHAUST IS NOT DIRECTED AT PLAY AREAS, PATIOS OR
 OTHER AREAS WHERE PEOPLE CONGREGATE.
  
 3) THE NEAREST WINDOW, VENT, DOOR OR SIMILAR STRUCTURE
 OPENING IS AT LEAST 5 FEET FROM THE EXHAUST END OF THE
 GENERATOR.
  
 4) GENERATOR SET MUST BE INSTALLED A MINIMUM OF 18
 INCHES FROM STRUCTURE PER NFPA 37, HOWEVER, ACTUAL
 DISTANCE MAY DIFFER BASED ON STATE AND LOCAL CODES.
  
 5) WINDOWS & DOORS ON ADJACENT WALLS ARE CLOSED.
  
 6) FURNACE AND OTHER SIMILAR INTAKES ARE AT LEAST 10
 FEET FROM EXHAUST END OF GENERATOR.
  
  
 THE FLOOR PLAN DOES NOT INDICATE DETAILS IN COMPLIANCE
 WITH THE INSTALLATION GUIDELINES.
  
 PLEASE REVIEW AND PROVIDE THE APPLICABLE SPECIFIC
 DETAILS/DIMENSIONS.
  
  
  
 2) THERE ARE INDICATIONS OF A NG LINE HOWEVER, THERE
 ARE NO DETAILS PER NFPA 54, INCLUDING SERVICE LINE
 LEENGTH, DEPTH OF COVERAGE, NEW GAS METER DIMENSION
 FROM AN ELECTICAL SPARK SOURCE, ETC.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE ALL
 APPLICABLE AND REQUIRED DIMENSIONS.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-07-03 Cont ID  
Sent By rwbrown Date 2023-07-03 Time 06:11 Rev Time 0.00
Received By rwbrown Date 2023-07-03 Time 06:10 Sent To  
Notes
2023-07-03 06:15:021ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.5 - PLEASE SUBMIT THE GAS
 DOCUMENTS. INCLUDE:
 A) A SITE PLAN SHOWING THE LOCATION OF THE GENERATOR.
 INCLUDE DETAILS THAT WOULD INDICATE SETBACKS FROM
 PROPERTY LINES AND DISTANCES FROM STRUCTURE OPENINGS
 AND AIR INTAKES.
 B) PLEASE SUBMIT A GAS RISER DIAGRAM THAT INCLUDES ANY
 OF THE FOLLOWING APPLICABLE ITEMS. LOCATION OF
 SHUT-OFFS, THE PIPING MATERIAL, GAS PIPE SIZING METHOD
 AND BTU LOADS, VENTING OF APPLIANCES, COMBUSTION AIR
 CALCULATIONS, APPLIANCE SCHEDULE, THE TYPE OF GAS
 PROPOSED, METER LOCATION, AND THE EXISTING GAS SYSTEM
 (LABELING EXISTING AND NEW FOR CLARITY).
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-06-30 Time 12:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-07-20 Cont ID  
Sent By cmontell Date 2023-07-20 Time 12:38 Rev Time 0.00
Received By cmontell Date 2023-07-20 Time 12:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-07-03 Cont ID  
Sent By rwbrown Date 2023-07-03 Time 06:10 Rev Time 0.00
Received By rwbrown Date 2023-07-03 Time 06:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-07-17 Cont ID  
Sent By ecolon Date 2023-07-17 Time 16:44 Rev Time 0.00
Received By ecolon Date 2023-07-17 Time 16:40 Sent To  
Notes
2023-07-17 16:44:46SUBMIT A SITE PLAN ILLUSTRATING THE LOCATION OF THE
 PROPOSED GENERATOR. PLEASE INCLUDE DETAILS SUCH AS
 SETBACKS FROM THE PROPERTY LINE. AS PER SEC. 94-305 (4)
 - MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR
 FEET INTO A SETBACK.
  
  
 **** REVIEWED BY ****
  
 ERIK COLON
 5618221398
 [email protected]