Plan Review Details - Permit 23061126
Plan Review Stops For Permit 23061126
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-05 Cont ID  
Sent By lbond Date 2023-07-05 Time 11:29 Rev Time 0.00
Received By lbond Date 2023-07-05 Time 11:29 Sent To  
Notes
2023-07-05 11:40:12FBC 1072.1
  
 SHOW EXISTING INTERIOR CONDITIONS FOR ENTIRE HOUSE AND
 DEMO PLAN.
  
 PROVIDE NEW WINDOWS SILL AND HEADER DETAILS.
 SAME FOR NEW DOORS HEADER AND THRESHOLD.
  
 PROVIDE DOOR AND WINDOW SCHEDULE THAT INCLUDED DESIGN
 PRESSURE, WALL ZONE WIND LOAD AND NOA THAT ARE
 DOCUMENTED IN SUPPORTING DOCS.
  
 PLEASE RESPOND TO BUILDING COMMENTS WITH NARRATIVE FOR
 EACH ITEM.
  
 LOUIS BOND, AIA, NCARB
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-06-28 Cont ID  
Sent By mpeterso Date 2023-06-28 Time 10:26 Rev Time 0.00
Received By mpeterso Date 2023-06-28 Time 09:15 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-06-27 Cont ID  
Sent By ccole Date 2023-06-27 Time 15:18 Rev Time 0.00
Received By ccole Date 2023-06-27 Time 14:28 Sent To  
Notes
2023-06-27 15:19:161ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23061126
 6/27/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. PLEASE REVIEW THE COMMENTS
 AND NOTE THAT GAS CAN BE SUBMITTED UNDER A SEPARATE
 PERMIT BY REQUEST.
  
 1) SHEET E-1 SHOWS A GAS FIRED TANKLESS WATER HEATER,
 RANGE, AND DRYER IN THE PANEL SCHEDULE. THESE APPEAR TO
 BE NEW INSTALLATIONS BECAUSE THERE ARE NO PREVIOUS GAS
 PERMIT RECORDS ON FILE IN THE WPB BUILDING DEPT. PLEASE
 SUBMIT COMPLETE GAS PLANS AND A GAS RISER DRAWING IN
 COMPLIANCE WITH- SECS. 107.2.1 & 107.3.5.3 WPB. THE
 RISER SHALL INCLUDE ALL NEW AND EXISTING GAS PIPING AND
 APPLIANCES AT THE RESIDENCE- SEC. G2412.3 & G2412.4 FBC
 RES. REFER TO FBC RES. CHAPTER 24 FUEL GAS AND PROVIDE-
  
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE RANGE
 AND DRYER AND INDICATE HOW THE AIR WILL BE PROVIDED. -
 SEC. G2407.1 FBC RES. PLEASE NOTE IF USING THE STANDARD
 INDOOR AIR METHOD PER SEC. G2407.5.1 THE MINIMUM
 REQUIRED VOLUME IS 50 CU.FT. PER 1000 BTUH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-17 Cont ID  
Sent By avolcy Date 2023-07-17 Time 16:45 Rev Time 0.00
Received By avolcy Date 2023-06-26 Time 11:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-07-14 Cont ID  
Sent By hmoser Date 2023-07-14 Time 07:56 Rev Time 0.00
Received By hmoser Date 2023-07-14 Time 07:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-06-27 Cont ID  
Sent By ccole Date 2023-06-27 Time 14:35 Rev Time 0.00
Received By ccole Date 2023-06-27 Time 13:43 Sent To  
Notes
2023-06-27 14:36:011ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23061126
 6/27/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 01: THE PLAN INDICATES A NEW SHOWER AND
 POSSIBLY A NEW WASHING MACHINE. PLEASE PROVIDE A
 SANITARY DRAINAGE AND VENT ISOMETRIC DRAWING- SEC.
 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-06-28 Cont ID  
Sent By mpeterso Date 2023-06-28 Time 10:27 Rev Time 0.00
Received By mpeterso Date 2023-06-28 Time 10:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-07-17 Cont ID  
Sent By gvolcy Date 2023-07-17 Time 16:44 Rev Time 0.00
Received By avolcy Date 2023-07-17 Time 16:43 Sent To  
Notes
2023-07-17 16:45:3807.17.2023 - FAILED
  
 PROVIDE THE PROPOSED ELEVATIONS TO REFLECT THE NEW
 DOORS/WINDOWS.
  
 **REVIEWED BY:**
 GAISHA (ANNE CLERISSE) VOLCY
 PLANNER
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved