Plan Review Details - Permit 23061040
Plan Review Stops For Permit 23061040
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-07-25 Cont ID  
Sent By jbrooks Date 2023-07-25 Time 12:19 Rev Time 0.00
Received By jbrooks Date 2023-07-25 Time 07:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-13 Cont ID  
Sent By jbrooks Date 2023-07-13 Time 14:39 Rev Time 0.00
Received By jbrooks Date 2023-07-13 Time 08:13 Sent To  
Notes
2023-07-13 14:39:54JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY
 CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER/ARCHITECT; TO CORRECT
 DESIGN PRESSURES & NAILING PATTERNS. EXAMPLE: THE
 CORRECT DESIGN PRESSURE FOR EXPOSURE D; ZONE 3; GABLE
 ROOF 0 TO 7 DEGREES; MEAN ROOF HEIGHT UP TO 15 FT AS
 PER TABLE R301.2(2) & TABLE R301.2(3) OF THE 2020 FBC R
 IS -131.42.
 2. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL10450-R17 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-03 Cont ID  
Sent By jbrooks Date 2023-07-03 Time 08:45 Rev Time 0.00
Received By jbrooks Date 2023-07-03 Time 07:54 Sent To  
Notes
2023-07-03 08:46:31JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL10450-R16
 HAS BEEN REVISED TO FL10450-R17. PLEASE PROVIDE A
 COMPLETE SET TO INCLUDE COVER PAGES; IT COVERS MULTIPLE
 PRODUCTS & INSTALLATION METHODS. SELECT PRODUCT &
 INSTALLATION METHOD TO BE USED. ALL APPLICABLE DETAILS
 AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE
 PRODUCT APPROVAL DRAWINGS.
 2. SEC. 107.2.1.2 CITY AMENDMENTS. ROOF ZONES SPECIFIED
 ON THE CALCULATIONS SUBMITTED ARE INCORRECT. ARCHITECT
 NEEDS TO USE THE REVISED ZONES AND PROVIDE THE ZONES
 DIMENSIONS AS REQUIRED BY FIGURE R301.2(7)
 FBC-RESIDENTIAL OF CURRENT 2020 CODE.
 3. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY
 CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ARCHITECT/ENGINEER; TO INCLUDE
 PROPOSED SYSTEM WITH PAGE NUMBER OF SYSTEM USED.
 4. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE ROOF SLOPE(S), MEAN ROOF
 HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW POSITIVE
 DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-25 Cont ID  
Sent By jbrooks Date 2023-07-25 Time 12:20 Rev Time 0.00
Received By jbrooks Date 2023-07-19 Time 08:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-13 Cont ID  
Sent By jbrooks Date 2023-07-13 Time 14:40 Rev Time 0.00
Received By jbrooks Date 2023-07-12 Time 09:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-03 Cont ID  
Sent By jbrooks Date 2023-07-03 Time 08:46 Rev Time 0.00
Received By jbrooks Date 2023-06-30 Time 12:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-07-25 Cont ID  
Sent By jbrooks Date 2023-07-25 Time 12:20 Rev Time 0.00
Received By jbrooks Date 2023-07-25 Time 07:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-07-13 Cont ID  
Sent By jbrooks Date 2023-07-13 Time 14:38 Rev Time 0.00
Received By jbrooks Date 2023-07-13 Time 14:15 Sent To  
Notes
2023-07-13 14:38:59JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
  
 SUBMITTED SIGNED AND SEALED ENHANCED NAILING
 CALCULATIONS IS A COPY OF A WET SIGNATURE. PLEASE
 UPLOAD A VALID ELECTRONICALLY SIGNED PLAN/DOCUMENT TO
 PROJECTDOX
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 PLEASE UPLOAD A VALID ELECTRONICALLY SIGNED
 PLAN/DOCUMENT TO PROJECTDOX
 PAPER PLANS/DOCUMENTS FOR SIGNATURE REVIEW WILL NO
 LONGER BE ACCEPTED BY THE CITY OF WEST PALM BEACH
 BUILDING DEPRTMENT.
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6656.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved